Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />8. SUMP/UDC TEST <br />Test Method Developed by ❑ Manufacturer 0 Industry Standard ❑ Professional Engineer <br />Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br />Test Equipment Used: Incon STS <br />Sump/UDC ID <br />87 STP <br />91 STP <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />10:07 <br />10:23 <br />Initial Reading <br />4.6682 <br />4.7807 <br />Test End Time <br />10:22 <br />10:38 <br />Final Reading <br />4.6683 <br />4.7823 <br />Change in Reading <br />0.0001 <br />0.0016 <br />Pass/Fail Criteria <br />0.002 <br />0.002 <br />Tightness Test Results <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Sump/UDC ID <br />87 Fill <br />91 Fill <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />10:07 <br />10:07 <br />Initial Reading <br />4.7115 <br />5.8132 <br />Test End Time <br />1022 <br />10:22 <br />Final Reading <br />4.7130 <br />5.8130 <br />Change in Reading <br />0.0015 <br />0.0002 <br />Pass Fail Criteria <br />0.002 <br />0.002 <br />Tightness Test Results <br />N Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Additional copies of this page may be attached. <br />All tests marked "Fail' and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />