Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ® Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ® Hydrostatic <br /> Test Equipment Used: Caldwell Level Change Indicator <br /> Sump/UDC ID 1-87-PS 2-Diesel-PS <br /> Sump Manufacturer XERXES XERXES <br /> Sump Depth (inches) 38" 41" <br /> Sump Bottom to Top of 16" 18" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time See page 5 See page 5 <br /> Initial Reading Not tested Not tested <br /> Test End Time NA NA <br /> Final Reading NA NA <br /> Change in Reading NA NA <br /> Pass/Fail Criteria NA NA <br /> Tightness Test Results ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1&2 UDC 3&4 UDC 4-Sat <br /> Sump Manufacturer Bravo Bravo Bravo <br /> Sump Depth (inches) 30" 30" 30" <br /> Sump Bottom to Top of 9" 9" 10" <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 9:15 9:14 9:12 <br /> Initial Reading .001 .001 .001 <br /> Test End Time 9:45 9:44 9:42 <br /> Final Reading .001 .001 .001 <br /> Change in Reading 0 0 0 <br /> Pass/Fail Criteria > .002 > .002 > .002 <br /> Tightness Test Results ® Pass ❑ Fail ® Pass ❑ Fail ® Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />