Laserfiche WebLink
<br /> <br /> <br />the COMMENTS section. <br />Page 4 of 5 <br />Test Method Developed by Manufacturer Industry Standard Professional Engineer <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: Caldwell Level Change Indicator <br />Sump/UDC ID UDC 1&2 UDC 3&4 UDC 5&6 UDC 7&8 <br />Sump Manufacturer Total Cont. Total Cont. Total Cont. Total Cont. <br />Sump Depth (inches) 23" 23" 23" 23" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />13" 13" 12" 12" <br />Test Start Time 10:27 10:32 10:37 10:42 <br />Initial Reading .001 .001 .001 .001 <br />Test End Time 10:57 11:02 11:07 11:12 <br />Final Reading .001 .001 .001 .001 <br />Change in Reading 0 0 0 0 <br />Pass/Fail Criteria > .002 > .002 > .002 > .002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Sump/UDC ID UDC 9&10 <br />Sump Manufacturer Total Cont. <br />Sump Depth (inches) 27" <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />13" <br />Test Start Time 9:47 <br />Initial Reading .001 <br />Test End Time 10:17 <br />Final Reading .001 <br />Change in Reading 0 <br />Pass/Fail Criteria > .002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br /> <br />8. SUMP/UDC TEST (continued)