Laserfiche WebLink
Underground Storage Tank <br />Secondary Containment Testing Report Form <br />All tests marked “Fail” and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 5 <br />Test Method Developed by Manufacturer Industry Standard Professional Engineer <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used:F.F.S. Incon TS-STS Sump Tester w/ + or – 0.002” graduations <br />Sump/UDC ID T-1 87 STP T-2 91 STP T-3 DSL STP UDC #1-2 <br />Sump Manufacturer Western Fiberglass Western Fiberglass Western Fiberglass Bravo B-2000 <br />Sump Depth (inches)49” 52” 53” 10” <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />21” 16” 16” Pipe enters <br />through <br />bottom of UDC <br />Test Start Time 9:00am 9:00am 10:07am 9:00am <br />Initial Reading 3.0041” 4.7611” 4.1591” 0.3201” <br />Test End Time 9:15am 9:15am 10:22am 9:15am <br />Final Reading 3.0035” 4.7606” 4.1585” 0.3194” <br />Change in Reading -0.0006” -0.0005” -0.0006” -0.0007” <br />Pass/Fail Criteria + or – 0.002” + or – 0.002” + or – 0.002” + or – 0.002” <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Sump/UDC ID UDC #3-4 <br />Sump Manufacturer Bravo B-2000 <br />Sump Depth (inches)10” <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Pipe enters <br />through <br />bottom of UDC <br /> <br />Test Start Time 9:00am <br />Initial Reading 2.2378” <br />Test End Time 9:15am <br />Final Reading 2.2371” <br />Change in Reading -0.0007” <br />Pass/Fail Criteria + or – 0.002” <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br />8. SUMP/UDC TEST