1" FRP BONDEDENTRY FITTING (TYP.)2 SENSOR-NO TANK VACUUMSENSOR ASSEMBLY KIT W/MOUNTING BRACKET1" MONITORING CONDUIT(ROUTED TO INTERSTITIAL)(ROBROY THROUGH SUMP ONLY)2" BELLxMALE ADAPTER (TYP.)3" OVER 2" FIBERGLASSCROSSOVER CONTAINS VACUUMTUBING ONLY FROM FILL SUMPNOTE: SENSOR SHALL BEINSTALLED ON THE SAMESIDE OF PIPINGPENETRATIONS AS SHOWNJ-BOX (TYP.)2 SENSOR-NO TANK VACUUMSENSOR ASSEMBLY KIT W/MOUNTING BRACKET2" CAP. DRILL HOLES IN ENDAND INSTALL GROMMETS FORTUBING PASS THROUGHNOTE: THE LAST 2 FEET(MINIMUM) OF CONDUITS THATENTER THE DOUBLE WALL SUMPSHALL BE PVC COATED RIGID.1" CONDUIT HOMERUN TOBLDG. TURBINE POWER2" BELLxMALE ADAPTER (TYP.)2" FLEX CONNECTOR2" INSIDE 3" FRP PIPE TO FILL SUMP2" INSIDE 3" D.W. FRP BONDED ENTRYFITTING W/ TEST PORT & PLUG2" CAP. DRILL HOLES IN END AN INSTALLGROMMETS FOR TUBING PASS THROUGH2" INSIDE 3" FRP PRODUCTMANIFOLD TO DISPENSERS(VACUUM MONITORED)2" INSIDE 3" D.W. FRP BONDED ENTRYFITTING W/ TEST PORT & VACUUM TUBINGLOOPED TO VAC SENSOR ASSEMBLY (TYP.)CONDUIT LOOP FROM FILL SUMPSENSORS (ROBROY THROUGHSUMP ONLY)1" FRP BONDED ENTRY FITTING (TYP.)VEEDER-ROOT .1 GPHMAGNOSTRICTIVE PROBE TANKLEVEL PROBE W/ TLS CAP & RING.OVERFILL ALARM SET @ 90%CAPACITY. USE 4" FLOAT IN INSTALLKIT2" INSIDE 3" FRPPRODUCT MANIFOLDTO DISPENSER(VACUUM MONITORED)1" POWER & MONITORINGCONDUIT HOME RUNS TO BLDG.(ROBROY THROUGH SUMP ONLY)1" FRP BONDEDENTRY FITTING (TYP.)2" INSIDE 3" D.W. FRPBONDED ENTRY FITTING W/TEST PORT & 1/4" PLUG.40" DIA. ACCESSMANHOLE3" OVER 2" FIBERGLASSCROSSOVER CONTAINSVACUUM TUBING ONLYFROM FILL SUMP2" INSIDE 3" D.W. FRPBONDED ENTRY FITTINGW/ TEST PORT & PLUGMINI HYDROSTATICSENSOR IN BRINE FACTORYSUPPLIED RESERVOIRVEEDER ROOT .1 GPHMAGNOSTRICTIVE PROBETANK LEVEL PROBE W/ TLSCAP & RING. OVERFILLALARM SET @ 90% CAPACITY.USE 4" FLOAT IN INSTALL KITTANK GAUGE ADAPTER & CAPSUMP LIQUID MONITORING SENSOR(IN SENSOR HOLDER BELOW APEXOF TANK AT LOWEST POINT)NOTE: THE LAST 2 FEET(MINIMUM) OF CONDUITS THATENTER THE DOUBLE WALL SUMPSHALL BE PVC COATED RIGID.3 SENSOR NO-TANK FOR REGULAR OR 2SENSOR-NO TANK VACUUM SENSORASSEMBLY KIT W/ MOUNTING BRACKET2 HP VARIABLE SPEED TURBINE W/ 3GPH ELECTRONIC LEAK DETECTIONW/ SIPHON PORT FOR VACUUMSOURCE2 HP VARIABLE SPEED TURBINE W/3 GPH ELECTRONIC LEAK DETECTIONW/ SIPHON PORT FOR VACUUM SOURCEDESIGNED BY:DRAWN BY:CHECKED BY:ALLIANCE PM:PROJECT NO:BP REPM:ALLIANCE Z&DM:SITE ADDRESS:DRAWING TITLE:SHEET NO:VERSION:UNDERGROUND STORAGETANK STANDARDSELEMENT TPO1V-15.0 2023 SERIESCA-4795AAKTAFCONFIDENTIALITY STATEMENT:DEVELOPMENT INFORMATION:THE RECIPIENT OF THESE MATERIALS UNDERSTANDS THATCOPYRIGHT IN THE MATERIALS IS OWNED BY BP, AND ALSO, THATTHE MATERIALS CONTAIN PRIVILEGED AND CONFIDENTIAL BUSINESSINFORMATION OF BP. ACCORDINGLY, THE RECIPIENT AGREES TORETAIN THESE MATERIALS IN STRICT CONFIDENCE AND AGREES NOTTO DISCLOSE THESE MATERIALS TO ANY OTHER PARTY ANDFURTHER AGREES NOT TO MAKE COPIES OF THE MATERIALS. THERECIPIENT AGREES TO USE THE MATERIALS ONLY FOR THE LIMITEDPURPOSE FOR WHICH BP HAS MADE THE MATERIALS AVAILABLE, ANDRECIPIENT AGREES TO RETURN ALL MATERIALS TO BP EITHER UPONCOMPLETION OF THE INTENDED PURPOSE OR UPON THE REQUESTOF BP, WHICHEVER COMES FIRST.BP DOES NOT AND CANNOT WARRANT THAT THE PLANS FORPETROLEUM STORAGE AND DISPENSING ARE COMPLIANT WITH ALLLEGAL REQUIREMENTS THAT EXIST OR AS THEY MAY BE APPLIED INTHE FUTURE. NOR DOES BP WARRANT THAT A FUELING STORAGEAND DELIVERY SYSTEM CONSTRUCTED IN CONFORMITY WITH THESEPLANS WILL BE FREE OF ALL LEAKS. YOU ARE ACCORDINGLYSTRONGLY ENCOURAGED TO CONSULT WITH A FUELING STATIONENGINEER OF YOUR CHOOSING TO INDEPENDENTLY EVALUATEWHETHER THESE PLANS ARE TRULY SUFFICIENT FORCONSTRUCTING THE STORAGE AND DELIVERY SYSTEM AT YOURSTATION.PIPE AND TANK DESIGN DISCLAIMER:bpSEAL:DATENO. REVISION DESCRIPTION1 1/30/2024 INITIAL ISSUE2 2/7/2024 ISSUE FOR PERMIT345678910BP WEST COAST PRODUCTS, LLCFT-44607 S. AIRPORT WAYSTOCKTON, CA 95206TURBINESUMP DETAILS 2081091071052123" PEA GRAVEL MIN. TOPREVENT LOAD TRANSFERTO TOP OF TANK104THICKEN CONCRETE SLAB TO BELOWWHERE SECONDARY CONTAINMENTOF SUMP ENDS (TYP.). DIMENSIONREQUIRED VARIES WITH FIELDCONDITIONS112" MIN. CROWN(TYP. ALL OPENINGS)6" WIDE DETECTABLEUNDERGROUNDMARKING TAPE EMPIREMAGNATEC #31-143(8" MIN. - 12" MAX.)1912172131681751242 SENSOR-NO TANK VACUUMSENSOR ASSEMBLY KIT W/MOUNTING BRACKET2" BALL VALVE2-IN-1 SENSOR BOX2"x24" FLEX (TYP.)SEAL OFF W/ DRAIN18714814212648" DOUBLE WALLBRINE FILLED SUMP22" MANWAYAFT-3202AREGULAR AND PREMIUM STP SUMP - ELEVATIONSCALE: 1" = 1'-0"207204205CONTRACTOR TO INSTALLCLEVIS AND COTTER PIN142148126142148126163204205213105109107208LOOP VACUUM TUBING FROMPRODUCT PIPING TO VAC SENSOR18712418717548" DOUBLE WALL BRINEMONITORED SUMP147126148142MINI HYDROSTATIC SENSOR IN BRINEFACTORY SUPPLIED RESERVOIR2 HP VARIABLE SPEED TURBINEW/ 3 GPH ELECTRONIC LEAKDETECTION W/ SIPHON PORTFOR VACUUM SOURCE1051091072082123" PEA GRAVEL MIN. TOPREVENT LOAD TRANSFERTO TOP OF TANK1912172-IN-1 SENSOR BOXSEAL OFF W/ DRAIN191SEAL-OFF (TYP.)1682" BALL VALVE48" DOUBLE WALL BRINEMONITORED SUMPSUMP LIQUID MONITORING SENSOR(IN SENSOR HOLDER BELOW APEXOF TANK AT LOWEST POINT)AFT-32021752"x24" FLEX (TYP.)1" POWER & MONITORINGCONDUIT HOME RUNS TOBLDG. (ROBROYTHROUGH SUMP ONLY)1871" FRP BONDEDENTRY FITTING (TYP.)12421318840" DIA. ACCESSMANHOLE104THICKEN CONCRETE SLAB TO BELOW WHERESECONDARY CONTAINMENT OF SUMP ENDS(TYP.). DIMENSION REQUIRED VARIES WITHFIELD CONDITIONS112" MIN. CROWN(TYP. ALL OPENINGS)6" WIDE DETECTABLEUNDERGROUNDMARKING TAPE EMPIREMAGNATEC #31-143(8" MIN. - 12" MAX.)VEEDER ROOT .1 GPH MAGNOSTRICTIVEPROBE TANK LEVEL PROBE W/ TLS CAP &RING. OVERFILL ALARM SET @ 90%CAPACITY. USE 4" FLOAT IN INSTALL KITTANK GAUGE ADAPTER & CAP207204205CONTRACTOR TO INSTALLCLEVIS AND COTTER PIN2" INSIDE 3" D.W. FRPBONDED ENTRY FITTING W/TEST PORT & 1/4" PLUG.1263" OVER 2" FIBERGLASSCROSSOVER CONTAINSVACUUM TUBING ONLYFROM FILL SUMP1481421" FRP BONDED ENTRY FITTING (TYP.)124LOOP VACUUM TUBING FROMPRODUCT PIPING TO VAC SENSOR1" HOMERUN TO BLDGTURBINE POWER (ROBROYTHROUGH SUMP ONLY)1872" INSIDE 3" FRP PRODUCTMANIFOLD TO 20K TANK(VACUUM MONITORED)1481422" INSIDE 3" D.W. FRP BONDED ENTRYFITTING W/ TEST PORT & VACUUM TUBINGLOOPED TO VAC SENSOR ASSEMBLY (TYP.)12622" MANWAYCDIESEL STP SUMP - ELEVATIONSCALE: 1" = 1'-0"1481422" INSIDE 3" D.W. FRP BONDED ENTRYFITTING W/ TEST PORT & PLUG126187124VEEDER ROOT .1 GPHMAGNOSTRICTIVE PROBE TANKLEVEL PROBE W/ TLS CAP &RING. OVERFILL ALARM SET @90% CAPACITY. USE 4" FLOAT ININSTALL KIT20520417514848" DOUBLE WALL BRINEMONITORED SUMP2" INSIDE 3" FRP PRODUCTLINE TO DISPENSERS(VACUUM MONITORED)1421" CONDUIT HOMERUN TO BLDG.TURBINE POWER (ROBROYTHROUGH SUMP ONLY)1262" INSIDE 3" D.W. FRP BONDED ENTRYFITTING W/ TEST PORT & VACUUM TUBINGLOOPED TO VAC SENSOR ASSEMBLY (TYP.)1471052131881241871631072081092 HP VARIABLE SPEED TURBINEW/ 3 GPH ELECTRONIC LEAKDETECTION W/ SIPHON PORTFOR VACUUM SOURCEJ-BOX (TYP.)22" MANWAYLOOP VACUUM TUBING FROMPRODUCT PIPING TO VAC SENSORNOTE: THE LAST 2 FEET (MINIMUM)OF CONDUITS THAT ENTER THEDOUBLE WALL SUMP SHALL BE PVCCOATED RIGID.BREGULAR AND PREMIUM STP SUMP - PLANSCALE: 1" = 1'-0"DDIESEL STP SUMP - PLANSCALE: 1" = 1'-0"NOTE: INDICATES ITEMS FOUND ONMATERIALS LIST SHEETS FM-1 & FM-2#NOTE:IST PUMP CONTROLS ARE TIED TOVEEDER-ROOT TLS-450. SEEVEEDER-ROOT SHEET FOR DETAILS.112" MIN. CROWN(TYP. ALLOPENINGS)6" WIDE DETECTABLEUNDERGROUNDMARKING TAPE EMPIREMAGNATEC #31-143(8" MIN. - 12" MAX.)104THICKEN CONCRETE SLAB TOBELOW WHERE SECONDARYCONTAINMENT OF SUMP ENDS(TYP.). DIMENSION REQUIREDVARIES WITH FIELD CONDITIONSMINI HYDROSTATIC SENSORIN BRINE FACTORYSUPPLIED RESERVOIR2 HP VARIABLE SPEED TURBINEW/ 3 GPH ELECTRONIC LEAKDETECTION W/ SIPHON PORTFOR VACUUM SOURCE2081091071052123" PEA GRAVELMIN. TO PREVENTLOAD TRANSFERTO TOP OF TANK110J-BOX (TYP.)2172-IN-1 SENSOR BOX1871" CONDUIT1" FRP BONDEDENTRY FITTING (TYP.)124188191SEAL-OFF (TYP.)VACUUM SENSORASSEMBLY KIT W/MOUNTING BRACKET213SUMP LIQUID MONITORINGSENSOR HOLDERAFT-320222" MANWAYVEEDER ROOT .1 GPH MAGNOSTRICTIVEPROBE TANK LEVEL PROBE W/ TLS CAP &RING. OVERFILL ALARM SET @ 90%CAPACITY. USE 4" FLOAT IN INSTALL KIT2062042072" INSIDE 3" D.W. FRPBONDED ENTRY FITTINGW/ TEST PORT & VACUUMTUBING LOOPED TO VACSENSOR ASSEMBLY (TYP.)1262" INSIDE 3" FRPPIPE TO FILL SUMP142148LOOP VACUUM TUBINGFROM PRODUCT PIPINGTO VAC SENSOR48" DOUBLE WALL BRINEMONITORED SUMP1682" BALL VALVE1051071082 HP VARIABLESPEED TURBINE W/65 PSI CHECK VALVEEB20 DIESEL STP SUMP - ELEVATIONSCALE: 1" = 1'-0"FB20 DIESEL STP SUMP - PLANSCALE: 1" = 1'-0"187VACUUM SENSORASSEMBLY KIT W/MOUNTING BRACKET213J-BOX (TYP.)188187TO SUMP SENSOR1" FRP BONDEDENTRY FITTING (TYP.)1201051071082 HP VARIABLESPEED TURBINE W/65 PSI CHECK VALVESUMP LIQUID MONITORINGSENSOR HOLDERAFT-32021283" INSIDE 4" FRP PIPETO DISPENSERS157148893" INSIDE 4" D.W. BONDEDFRP ENTRY FITTING91122" MANWAY2" INSIDE 3" D.W. FRPBONDED ENTRYFITTING W/ TEST PORT& PLUG1262" INSIDE 3"FRP PIPE TOFILL SUMP1421481763"X18" FLEX CONNECTOR1842"X3" REDUCE GALV. ELBOW1051071082 HP VARIABLESPEED TURBINE W/65 PSI CHECK VALVE183GALV. NIPPLE185GALV. TEE204206207LEVEL GAUGE LOCATION48" DOUBLE WALL BRINEMONITORED SUMPGALV. UNION18540" DIA. ACCESSMANHOLE2/27/2024 REVISED PER C.E.H. COMMENTSTHE REGULAR AND PREMIUMSTP SUMPS WILL BE IDENTICALTHE REGULAR AND PREMIUMSTP SUMPS WILL BE IDENTICAL3/26/2024 REVISED PER C.E.H. COMMENTS5/3/2024 REVISED PER C.E.H. COMMENTS1" CONDUIT HOMERUN TOBLDG. TURBINE POWER(ROBROY THROUGH SUMPONLY)1871" CONDUIT HOMERUN TOBLDG. TURBINE POWER(ROBROY THROUGH SUMPONLY)NOTE: ONE (1) CONDUITPENETRATION NOTSHOWN FOR CLARITY.1241" FRP BONDED ENTRY FITTING (TYP.)124124772" CAP. DRILL HOLES IN ENDAND INSTALL GROMMETSFOR TUBING PASS THROUGH16376/12/2024 REVISED PER C.E.H. COMMENTS77777