Laserfiche WebLink
coo, GUJI <br /> G'' E 0 <br /> DI 2 1�H RSE UNE <br /> 000 <br /> 2 ro AGU <br /> CC: �F- LI <br /> :20K IESE <br /> Od <br /> 000 <br /> c. #813 is listed at each UDC.#813 is a PLILD mount.Are you installing leak detectors in each UDC? <br /> Alternatively,you don't have any of these mounts located where leak detectors are shown (#812) in the <br /> turbine sumps. <br /> d. #823 is listed at each tank sump and UDC.This is a sensor kit (330020-536)that contains a 304 and 208 <br /> sensors. But you have these sensors listed separately on sheet T&L7 and in this diagram (#806 and#815) <br /> as well as this kit (#823).Are you installing 2 sets of 304 and 208?You do not have#315 listed at the <br /> UDCs but the quantity listed for this 208 sensor is 23, but there are only 11 listed in the diagram. <br /> e. #808 are probes shown in the fill sumps. Probes are typically not located here. <br /> f. #808 is shown 4 times on this diagram (at each fill sump) but you only have a quantity of 2 listed on the <br /> materials sheet (T&L7). Ensure this matches the correct amount to be installed throughout your plan. <br /> g. #812 is shown 4 times on the diagram (at each turbine sump) but you only have a quantity of 1 listed on <br /> the materials sheet (T&L7). Ensure this matches the correct amount to be installed throughout your <br /> plan. <br /> h. Does the 91 product piping come out of both the 91 STP sump and 91 fill sump?As seen in purple <br /> below. Or is that dark dashed line an 87 product line based on one of the legends, if so,why is it <br /> connected to the 91 STP sump?There are two different legends on this page. See snippets below. <br /> 23 <br />