23 <br /> <br />c. #813 is listed at each UDC. #813 is a PLLD mount. Are you installing leak detectors in each UDC? <br />Alternatively, you don’t have any of these mounts located where leak detectors are shown (#812) in the <br />turbine sumps. <br />d. #823 is listed at each tank sump and UDC. This is a sensor kit (330020-536) that contains a 304 and 208 <br />sensors. But you have these sensors listed separately on sheet T&L7 and in this diagram (#806 and #815) <br />as well as this kit (#823). Are you installing 2 sets of 304 and 208? You do not have #315 listed at the <br />UDCs but the quantity listed for this 208 sensor is 23, but there are only 11 listed in the diagram. <br />e. #808 are probes shown in the fill sumps. Probes are typically not located here. <br />f. #808 is shown 4 times on this diagram (at each fill sump) but you only have a quantity of 2 listed on the <br />materials sheet (T&L7). Ensure this matches the correct amount to be installed throughout your plan. <br />g. #812 is shown 4 times on the diagram (at each turbine sump) but you only have a quantity of 1 listed on <br />the materials sheet (T&L7). Ensure this matches the correct amount to be installed throughout your <br />plan. <br />h. Does the 91 product piping come out of both the 91 STP sump and 91 fill sump? As seen in purple <br />below. Or is that dark dashed line an 87 product line based on one of the legends, if so, why is it <br />connected to the 91 STP sump? There are two different legends on this page. See snippets below.