Laserfiche WebLink
Vacuum Kit 3(diesel STP) Zone 7 Diesel vent, diesel fill-STP chase <br /> 330020-480 2 lines <br /> Vacuum Kit 4(1320 STP) Zone 8 B20 product <br /> Zone 9 B20 vent, B20 fill-STP chase <br /> 330020-480 2 lines <br /> iii. There aren't enough vacuum kits listed in T&L7 and the Shield, <br /> Harper&Co (4/11/2022) Equipment List.The diagram shows that there is a -480 kit in 4 of the <br /> STP sumps and one -485 kit in the 87 sump but there is only 1-480 kits listed on the Equipment <br /> list and 2 -480 kit listed on T&L7 <br /> 8. Sheet T&L2 <br /> a. Detail C6 <br /> i. Detail C6 has#209 pointing to what looks like a UDC but T&L7 <br /> shows#209 as single port spill platform. <br /> ii. What is this tube and where does it lead to? See highlighted item in <br /> the snippet below <br /> TMT POq <br /> -r. AV <br /> 9. Sheet T&L3 <br /> a. The detail shows wiring coming out of chase piping attaching to the drop tube in all of the fill sumps. <br /> What are these wires? <br /> 25 <br />