NOTE: NOTES: OUT OF HOLE INSTALLATION SEQUENCE: <br /> SEE TANK FUELING SITE PLAN FOR HYDROSTATIC EQUIPMENT SCHEDULE ALL STAGE I FILL AND VAPOR RISER ADAPTERS SHALL BE ELECTRICALLY GROUNDED TO PROMOTE NOTE: bp <br /> SPECIFIC TANK LAYOUT TANK #2B RESERVOIR THE RELAXATION OF STATIC CHARGE. ALL CAD WELDS W/ EXCEPTION OF "T" CONNECTIONS AT EACH TANK AND FINAL CAD WELD <br /> 0 ITEM DESCRIPTION THE BONDING AND GROUNDING FOR STATIC ELECTRICITY PROTECTION SHALL BE IN COMPLIANCE PER @ GROUND ROD NOTED IN SCHEDULE ON THIS SHEET MAY BE PREFABRICATED OUTSIDE <br /> NO. ALL APPLICABLE FEDERAL, STATE AND LOCAL CODES INCLUDING NFPA 30, FLAMMABLE AND THE TANK AREA AND BROUGHT TO SITE. <br /> COMBUSTIBLE LIQUIDS CODE, NFPA 77, RECOMMENDED PRACTICE ON STATIC ELECTRICITY, NFPA 70, <br /> HYDROSTATIC 1/2" 0 X 10' LONG COPPERBONDED GROUND ROD: CALIFORNIA ELECTRIC CODE, AND THE CALIFORNIA CODE OF REGULATIONS, SUBCHAPTER 15, 1 . MAKE "CABLE TO PIPING STEEL SURFACE" CADWELD CONNECTION CONNECTION WITH #4 <br /> RESERVOIR 0 G:) 11 ERICO" PART NO. 611300 (UL LISTED) PETROLEUM SAFETY ORDERS-REFINING, TRANSPORTATION AND HANDLING, ARTICLE 5, FIRE AND STRANDED WIRE TO EACH FILL AND STAGE I RISER OUTSIDE THE SUMP AREA. TO ASSURE <br /> OR EQUIVALENT EXPLOSIONS. <br /> 0 A COMPLETE CONNECTION, ANY PAINT OR COATING ON THE RISER SHALL BE REMOVED <br /> #4 AWG STRANDED BARE COPPER GROUND WIRE. PRIOR TO INSTALLATION OF THE CADWELD CONNECTION. <br /> PROVIDE TERMINAL CONNECTORS AT U-BOLT PER SECTION 6.4.1.3 OF NFPA 77, THE MEASURED TOTAL RESISTANCE IN THE GROUND PATH TO 2. APPLY "THERMOCAP" CATHODIC PROTECTION TO EACH OF THE CADWELDS ON RISERS. <br /> FILL SUMP 5 8 (TYP.) CONNECTIONS EARTH SHALL BE LESS THAN 1 MEGAOHM WHICH IS CONSIDERED ADEQUATE FOR RELAXATION OF <br /> TURBINE SUMP STATIC CHARGE. THE MAXIMUM ALLOWABLE GROUND PATH TO EARTH RESISTANCE FOR STATIC KE #4 STRANDED TO #4 STRANDED "T" CADWELD CONNECTIONS <br /> 6 (TYP.) CADWELD#4 WIRE CABLE TO GROUND ROD ELECTRICITY GROUNDING APPLICATIONS SHALL NOT EXCEED 100,000 OHMS. TO MAIN GROUND WIRE BACK TO GROUND ROD. THE CONDUCTORS SHALL HAVE 18" <br /> CONNECTION "ERICO" PART NO. GTT14AlL, USE MINIMUM COVER. EACH TANK SHALL HAVE SEPARATE GROUND WIRE TO GROUND ROD <br /> TO VENT STACK WELD METAL#32 PER SECTION 6.4.1.3 OF NFPA 77, THE RESISTANCE IN METALLIC BONDING AND OR GROUNDING 3. MAKE #4 STRANDED WIRE TO GROUND ROD CADWELD CONNECTION. CADWELD <br /> BOND GROUND WIRE TO CADWELD "T" CONNECTION FOR#4 BARE STRANDED SYSTEMS SHALL BE LESS THAN 10 OHMS. RESISTANCE HIGHER THAN 10 OHMS INDICATES CONNECTION MODEL NUMBER PER NUMBER OF TANKS. <br /> FILL SUMP ALL METALLIC RISERS AS WIRE CABLES. "ERICO" PART NO. TAC1 Ll L, USE#32 INADEQUATE CONNECTIONS. <br /> REQUIRED (TYP.)SEE CK) WELD METAL. A GROUNDING SYSTEM PER CEC CODE FOR CURRENT CARRYING CONDUCTORS SHALL BE NOTE: <br /> GROUND ROD BONDING DETAIL CONSIDERED MORE THAN ADEQUATE FOR A STATIC ELECTRICITY GROUNDING SYSTEM. ELECTRICAL CONDUIT, FUELING SYSTEM HARDWARE OR THE STATION ELECTRICAL GROUNDING <br /> 1 3 SYSTEM SHALL NOT BE USED FOR GROUNDING OR BONDING FILL AND VAPOR RISERS. <br /> INSTALL OUTSIDE OFCDCD--_�/ CLAMP, LIND EQUIPMENT P/N JR-1 50-6 (905)475-5086 PER THE NFPA 30, SECTION 5-6.3.4 ALL PARTS OF THE FILL PIPE ASSEMBLY, INCLUDING THE DROP <br /> TANK EXCAVATION <br /> IN NATIVE SOIL 4 TESTING: ARCO <br /> 4" NPT ADJUSTABLE COPPER GROUND CLAMPS, THE MINIMUM WIRE SIZE FOR BONDING AND GROUNDING SHALL BE COPPER AWG#4 MANNER.THAT WOULD POTENTIALLY PRODUCE STATIC DISCHARGE OR SPARKS OF ANY KIND. BP WEST COAST PRODUCTS,LLC <br /> 2 (TYP.) BURNDY GAR224C 4AWG GROUND CONNECTOR A 1/2" 0 BY 10' LONG COPPER CLAD STEEL GROUND ROD SHALL BE DRIVEN INTO NATIVE SOIL ONLY. <br /> FILL SUMP PLACING THE GROUND ROD INTO TANK PIT PEA GRAVEL SHALL NOT BE PERMITTED UNDER ANY THE FILL AND VAPOR RISERS SHALL BE TESTED AFTER INSTALLATION AND PERIODICALLY TO <br /> - OPW 104A-120OWT 12" H-20 RATED, BOLT DOWN WATER CONDITIONS. THE CONTRACTOR IS RESPONSIBLE FOR CLEARING ANY UNDERGROUND UTILITIES VERIFY BONDING AND GROUNDING COMPETENCY. <br /> 0 PRIOR TO INSTALLATION OF THE GROUND. <br /> 0 -14 TIGHT ACCESS COVER(USED IN DRIVE AREAS) THE MAXIMUM RESISTANCE FROM ANY FILL OR VAPOR ADAPTER TO THE BODY OF THE <br /> OPW 104A-1200 12" H-20 RATED, GRAVITY LID ACCESS THE GROUND ROD TO GROUND WIRE CONNECTION SHALL BE ACCESSIBLE THROUGH A H-20 RATED GROUND ROD SHALL NOT EXCEED 10 OHMS FOR A METALLIC RISER PIPE, SPILL CONTAINMENT <br /> 0 COVER(USED IN PLANTER AREAS) 12" DIAMETER MINIMUM ACCESS COVER TO ASSIST INSPECTION, MAINTENANCE AND TESTING. THE AND ADAPTER ASSEMBLIES. <br /> TURBINE SUMP x SCREW TYPE GROUND ROD CLAMP SHALL BE UL LISTED FOR DIRECT BURIAL. THE RESISTANCE THROUGH ANY COMPOSITE OR NONMETALLIC STAGE I CONTAINMENT FITTING <br /> ONE MAIN STRANDED#4 THHN CONDUCTOR SHALL BE RUN PAST EACH FILL SUMP. ONE STRANDED#4 SHALL BE MEASURED WITH A OHMMETER CAPABLE OF READING UP TO 10 MEGAOHMS. THE <br /> TANK #2A TANK #1 THHN CONDUCTOR SHALL BE ROUTED TO EACH FILL SUMP. INSTALLATION AT SUMP SHALL BE AS SUM COLLECTIVE RESISTANCE OF THESE SEMI-CONDUCTIVE ELEMENTS SHALL NOT EXCEED <br /> 3/4" DOUBLE WALL ENTRY FITTING. FOLLOWS AND MUST BE COMPLETED IN ORDER NOTED AS FOLLOWS: 100,000 OHMS. FOR THESE SYSTEMS, THE GROUND RESISTANCE TESTER MUST BE CONNECTED <br /> "BRAVO" MODEL NO. F-07S-0-DF TO THE GROUND CONDUCTOR CONNECTION ON THE COMPOSITE CONTAINMENT SYSTEM OR <br /> ADHESIVE- EP100 2 NEEDED PER PENETRATION RISER PIPE. NO. DATE REVISION DESCRIPTION <br /> FOR INSTALLATIONS WITHOUT AN EXPOSED GROUND ROD CONNECTION, TOTAL SYSTEM <br /> B B RESISTANCE SHALL BE MEASURED WITH A GROUND RESISTANCE TESTER BY A QUALIFIED 1/30/2024 INITIAL ISSUE <br /> FT-8 ELECTRICIAN FAMILIAR WITH GROUND TESTING. THE TWO POINT METHOD MAY BE USED WITH 2/7/2024 ISSUE FOR PERMIT <br /> THE SITE ELECTRICAL GROUNDING AS THE SECOND TEST POINT. <br /> THE NEC MAXIMUM GROUND PATH RESISTANCE FOR CURRENT CARRYING APPLICATIONS IS 25 <br /> OHMS. HOWEVER, GROUND ROD TO EARTH RESISTANCE UP TO 100 OHMS SHALL BE <br /> ACCEPTABLE FOR STATIC ELECTRICITY PROTECTION OF THE FILL AND VAPOR RISERS. <br /> #4 STRANDED BARE <br /> COPPER GROUND <br /> #4 STRANDED BARE TO GROUND CLAMPS GROUNDING OHMS NOTE: <br /> COPPER GROUND ON FILL RISERS TEST GROUNDING IMPEDANCE AT THE FILL RISERS. GROUNDING IMPEDANCE SHALL BE <br /> #4 STRANDED BARE (::D TO OTHER TANKS BELOW 25 OHMS PER CURRENT CEC CODE. IF IMPEDANCE IS OVER 25 OHMS, PLACE <br /> COPPER GROUND 3/4" GROUNDING ANOTHER GROUND ROD A MINIMUM 10 FEET AWAY FROM THE FIRST GROUND ROD <br /> TO GROUND ROD CLAMP W/TAP AND TIE THE RODS TOGETHER WITH SAME WIRE SIZE AND CONNECTIONS. MAKE SURE <br /> SCREW(TYP.) GROUND ROD IS INSTALLED INTO NATIVE SOIL. <br /> SEAL <br /> _ 8 3/4"0 x 12" LONG <br /> (D SOLID BRONZE ROD <br /> "T" CADWELD#4 4 (TYP.) <br /> STRANDED BARE COPPER <br /> WIRE CONNECTION TEST LEAD CONNECTED TO GROUND ROD <br /> (TYP.) (NOT LUG OR WIRING) <br /> 12" H-20 RATED 10 OHMS MAX <br /> ACCESS COVER <br /> #4 STRANDED BARE 2 <br /> #4 STRANDED BARE COPPER COPPER GROUND CONFIDENTIALITY STATEMENT: <br /> GROUND TO 3/4" 0 SOLID ROD 5 3/4" FRP BONDED #4 STRANDED WIRE TO #4 STRANDED BARE TO OTHER TANKS THE RECIPIENT OF THESE MATERIALS UNDERSTANDS THAT <br /> DOUBLE ENTRY BOOT 1/2"0 CADWELD GROUND COPYRIGHT IN THE MATERIALS IS OWNED BY BP,AND ALSO,THAT <br /> THE ATERIALS CONTAIN PRIVILEGED AND CONFIDENTIAL BUSINESS <br /> CADWELD "L" CONNECTION "BRAVO" MODEL NO. ROD CONNECTION COPPER GROUND MMATION OF Bp ACCORDINGLY,THE RECIPIENT AGREES TO <br /> INFOR <br /> TAIN THESE MATERIALS IN STRICT CONFIDENCE AND AGREES NO <br /> (TYP.) EXTERNAL -INTERNAL TO GROUND ROD RE <br /> F-07-GR TO DISCLOSE THESE MATERIALS TO ANY OTHER PARTY AND <br /> FURTHER AGREES NOT TO MAKE COPIES OF THE MATERIALS.THE <br /> SUMP WALL SUMP WALL RECIPIENT AGREES TO USE THE MATERIALS ONLY FOR THE LIMITED <br /> RECIPIENT AGREES TO RETURN ALL MATERIALS TO BP EITHER UPON <br /> -------------------------------------------------------------------------------------------------------------- <br /> COMPLETION OF THE INTENDED PURPOSE OR UPON THE REQUEST <br /> OF BP,WHICHEVER COMES FIRST. <br /> STATIC GROUNDING PLAN VIEW AND BONDING 0 �7 PIPE AND TANK DESIGN DISCLAIMER: <br /> BP DOES NOT AND CANNOT WARRANT THAT THE PLANS FOR <br /> PET OLEUM STORAGE AND DISPENSING ARE COMPLIANT WITH ALL <br /> A SCALE: 1" V-10" LEGAL REQUIREMENTS THAT EXIST OR AS THEY MAY BE APPLIED IN <br /> "T" CADWELD#4 THE FUTURE.NOR DOES BP WARRANT THAT A FUELING STORAGE <br /> Fl I I _1 AND D LIVERY SYSTEM CONSTRUCTED IN CONFORMITY WITH THES <br /> PLANS WI L BE FREE OF ALL LEAKS.YOU ARE ACCORDINGLY <br /> STRANDED BARE STRONGLY ENCOURAGED TO CONSULT WITH A FUELING STATION <br /> ENGINEER OF YOUR CHOOSING TO INDEPENDENTLY EVALUATE <br /> 1/2" 0 X 10' LONG AV- COPPER WIRE WHETHER THESE PLANS ARE TRULY SUFFICIENT FOR <br /> CONSTRUCTING THE STORAGE AND DELIVERY SYSTEM AT YOUR <br /> COPPER CLAD STEEL GROUND ROD DETAIL CONNECTION STATION. <br /> 12" H-20 RATED ACCESS COVER GROUND ROD IN (TYP.) <br /> NATIVE 4"0 BRONZE PIPE DEVELOPMENT INFORMATION <br /> 6 CLAMPS (TYP.) <br /> UNDERGROUNDSTORAGE <br /> CADWELD#4 WIRE CABLE TO GROUND ROD <br /> OR GROUND ROD CLAMP TANKSTANDARDS, <br /> 1/2" 0 X 10' LONG COPPER CLAD ELEMENT TP01 <br /> V-15.0 2023 SERIES <br /> CE) STEEL GROUND ROD IN NATIVE 4" FILL AND STAGE TERMINAL CONNECTION <br /> SOIL I RETURN PIPES 4 STRANDED BARE 5 <br /> #4 �TRANDED BARE 2 OPPER GROUND TO 3/4" 0 <br /> (TYP.) COPPER GROUND SOLID ROD CADWELD "L" <br /> 2 #4 AWG STRANDED FILL SIDE CONTAINMENT WIRE CONNECTION SITE ADDRESS, <br /> (TYP.) <br /> BARE COPPER GROUND CONTAINMENT SUMP (TYP.) ANCHORING PLATE <br /> WIRE (LFANK BOX (TYP.) (�ANK 4"0 COPPER GROUND L_2 A 4607 S. AIRPORT WAY <br /> 4 CLAMPS. "BURNDY No. 6 + 3/4"0 x 12" LONG BRONZE STOCKTON, CA 95206 <br /> GROUND ROD DETAIL (TYP.) FINISHED GAR224C" ROD (TYP.) <br /> SURFACE <br /> (TYP ) <br /> 0.-0� 'C�-0 RISER (TYP.) NOTE: DESIGNED BY: ALLIANCE Z&DM: <br /> FOR PENETRATIONS OF THE SUMP WALLS, SOLID AAK <br /> BRONZE STUD BOLTS ARE TO BE USED AND THE CHECKED BY: BP REPM <br /> x <br /> INTERIOR SUMP GROUND WIRES ARE TO BE <br /> 0 DRAWN BY: ALLIANCE PM <br /> 6 CONNECTED VIA TERMINAL CONNECTORS TO THE TAF <br /> CD <br /> (TYP.) ---------- BOLTS. BOLTS TO BE SEALED BOTH INSIDE AND OUT VERSION <br /> 1/2" 0 X 10' LONG COPPER CLAD 8 <br /> GROUND CLAMP AT FILL SUMP WITH GLASS MATT& RESIN. <br /> CA-4795 <br /> STEEL GROUND ROD IN NATIVE <br /> (TYP.) <br /> SOIL DRAWING TITLE <br /> @ UST GROUNDING <br /> U B L E <br /> COIL STATIC GROUND WIRE CABLE UP Y- WALL TANKS EXTREME CAUTION MUST BE OBSERVED WHILE USING ANY NON-INTRINSICALLY SAFE DETAILS <br /> DEVICE IN CLASSIFIED AREAS. SUMP MUST BE TESTED FOR VOLATILE VAPORS PRIOR <br /> T &SECURE TO SIDE OF GALVANIZED PEAGRAVEL TO USE. ELECTRICAL CONNECT MUST BE MADE WITH JUMPER WIRE SO FINAL <br /> STEEL RISER BACKFILL CONNECTION IS AWAY FROM CLASSIFIED AREAS. SHEET NO: <br /> NOTE: <br /> ------------.... ............... ALL EXTERIOR WIRE PENETRATIONS <br /> STATIC GROUNDING <br /> ARE REQUIRED TO BE CAD WELDED TO <br /> EARTH <br /> ELEVATION AND BONDING- I I " i�< I TESTING EXPOSED GROUND SYSTEM & BONDING- ENSURE EFFECTIVE GROUNDING. FT� 9 <br /> SCALE: 1" = V-10" (GROUND ROD INSTALLED IN SOIL NOT PEAGRAVEL BACKFILL) Dc SCALE: NONE TYPICAL FILL SUMP <br />