Laserfiche WebLink
C.E.C. HAZARDOUS AREA NOTES bp <br /> ALL CONDUIT ENTERING AND LEAVING THE CLASSIFIED/ <br /> HAZARDOUS AREAS SHALL HAVE SEAL-OFFS PER C.E.C. 501.5(A) <br /> A. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> (UNDERGROUND TANK- FILL OPENING) <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: <br /> ANY PIT, BOX, OR SPACE BELOW GRADE LEVEL, ANY PART OF <br /> 0 WHICH IS WITHIN THE DIVISION 1 OR 2 CLASSIFIED LOCATION. <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION: <br /> UP TO 18 INCHES ABOVE GRADE LEVEL WITHIN A HORIZONTAL <br /> RADIUS OF 10 FEET FROM A LOOSE FILL CONNECTION AND WITHIN <br /> A HORIZONTAL RADIUS OF 5 FEET FROM A TIGHT FILL <br /> CONNECTION. <br /> B. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> (UNDERGROUND TANK-VENT DISCHARGING UPWARD) <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: <br /> N71023'00"E 116.6 1 ' WITHIN 5 FEET OF OPEN END OF VENT, EXTENDING IN ALL <br /> DIRECTIONS. <br /> F� EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION: ARCO <br /> �po SPACE BETWEEN 5 FEET AND 10 FEET OF OPEN END OF VENT, <br /> 00 EXTENDING IN ALL DIRECTIONS. BP WEST COAST PRODUCTS, LLC <br /> (REMOTE PUMP - OUTDOORS) <br /> C. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: <br /> ANY PIT, BOX, OR SPACE BELOW GRADE LEVEL IF ANY PART IS <br /> WITHIN A HORIZONTAL DISTANCE OF 10 FEET FROM ANY EDGE OF <br /> B PUMP. <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION: <br /> WITHIN 3 FEET OR ANY EDGE OF PUMP, EXTENDING IN ALL <br /> DIRECTIONS. ALSO UP TO 18 INCHES ABOVE GRADE LEVEL WITHIN <br /> 0 10 FEET HORIZONTALLY FROM ANY EDGE OF PUMP. <br /> D. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> (DISPENSING DEVICE -PITS) <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: NU. UAIL KILVI�IVN ULZIUKIrIlUN <br /> A ANY PIT, BOX, OR SPACE BELOW GRADE LEVEL, ANY PART OF 'A 1/30/2024 INITIAL ISSUE <br /> WHICH IS WITHIN THE DIVISION 1 OR 2 CLASSIFIED LOCATION. 2/7/2024 ISSUE FOR PERMIT <br /> o')i E. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> 1// ji� 1 41 1 r /lr /y /V <br /> (DISPENSING DEVICE - DISPENSER) <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 1 LOCATION: <br /> SPACE CLASSIFICATION INSIDE THE DISPENSER ENCLOSURE IS <br /> COVERED IN ANSI/UL 87, "POWER OPERATED DISPENSING <br /> DEVICES FOR PETROLEUM PRODUCTS." <br /> F. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> D E (DISPENSING DEVICE - DISPENSER) <br /> 0 EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION <br /> WITHIN 18 INCHES HORIZONTALLY IN ALL DIRECTIONS EXTENDING <br /> E-STOP AND TO GRADE FROM (1) THE DISPENSER ENCLOSURE OR (2)THAT <br /> PORTION OF THE DISPENSER ENCLOSURE CONTAINING LIQUID SEAL: <br /> OVERFILL ALARM HANDLING COMPONENTS. <br /> G. TYPICAL C.E.C. ARTICLE 514 CLASS 1 LOCATION <br /> (DISPENSING DEVICE - OUTDOOR) <br /> EXTENT OF CLASS 1, GROUP D, DIVISION 2 LOCATION. <br /> UP TO 18 INCHES ABOVE GRADE LEVEL WITHIN 20 FEET <br /> HORIZONTALLY OF ANY EDGE OF ENCLOSURE. <br /> 0 <br /> CONFIDENTIAUTY STATEMENT: <br /> COPYRIGHTINT EMATERIALS OWNED BY BP,AND ALSO,THAT <br /> THE TERIALS NTAIN PRIVILISEGED AND CONFIDENTIAL BUSINESS <br /> INFORMATION OF BP.ACCORDINGLY,THE RECIPIENT AGREES TO <br /> RETAIN THESE MATERIALS IN STRICT CONFIDENCE AND AGREES NO <br /> TO DISCLOSE THESE MATERIALS TO ANY OTHER PARTY AND <br /> FURT ER AGREES NOT TO MAKE COPIES OF THE MATERIALS.THE <br /> REC IPIENT AGREES TO USE THE MATERIALS ONLY FOR THE LIMITED <br /> PURPOSE FOR WHICH BP HAS MADE THE MATERIALS AVAILABLE,AN <br /> RECIPIENT AGREES TO RETURN ALL MATERIALS TO BP EITHER UPON <br /> COMPLETION OF THE INTENDED PURPOSE OR UPON THE REQUEST <br /> OF BP,WHICHEVER COMES FIRST. <br /> P PE ;LAIMER: <br /> BP'nC)ESANNODTANTD CANNOT WARRANT THAT THE PLANS FOR <br /> ROLEUM STORAGE AND DISPENSING ARE COMPLIANT WIT ALL <br /> LEGAL REQUIREMENTS THAT EXIST OR AS THEY MAY BE APPLIED IN <br /> THE FUTURE.NOR DOES BP WARRANT THAT A FUELING STORAGE <br /> AND DELIVERY SYSTEM CONSTRUCTED IN CONFORMITY WITH THES <br /> PLANS WILL BE FREE OF ALL LEAKS.YOU ARE ACCORDINGLY <br /> MAXIMUM 100" STRONGLY ENCOURAGED TO CONSULT WITH A FUELING STATION <br /> ENGINEER OF YOUR CHOOSING TO INDEPENDENTLY EVALUATE <br /> E-STOP RADIUS WHETHER THESE PLANS ARE TRULY SUFFICIENT FOR <br /> CONSTRUCTING THE STORAGE AND DELIVERY SYSTEM AT YOUR <br /> STATION. <br /> MINIMUM 20' DEVELOPMENT INFORMATIION: <br /> E-STOP RADIUS UNDERGROUND STORAGE <br /> TANK STANDARDS <br /> ELEMENT TPOl <br /> /A V-15.0 2023 SERIES <br /> SITE ADDRESS: <br /> 4607 S. AIRPORT WAY <br /> STOCKTON, CA 95206 <br /> E-STOP <br /> DESIGNED BY- AAK AWANCE Z&DM: <br /> z z <br /> I F 7 1 DRAWN BY- TAF ALLIANCE PM: <br /> L _J VERSION: PRO&CT NO: <br /> DRAWING TITLE: CA-4795 <br /> AUTO AND TANK <br /> 14V HAZARDOUS <br /> AREA PLAN <br /> SHEET NO: <br /> AM/PM <br /> C-STORE <br /> 20 0 10 20 <br /> FE � l <br /> 1 INCH = 10 FEET <br />