Laserfiche WebLink
Initial Setup Of The Console Using Workflow Wizard <br />Setup>Pumps and Lines>PLLD <br />0.2 gph (0.761ph) Line LeakTest <br />Touch to select the scheduling frequency of the 0.2 gph (0.761ph) periodic <br />tests: <br />Disabled - No manual, repetitive, or monthly 0.2 gph (0.761ph) testing is <br />allowed. This is the default. <br />Repetitive - After a dispense, a 3.0 gph (11.31ph) test is run, followed by a <br />0.2 gph (0.761ph) test. The test blockout period (the Precision Test Delay <br />in "Setup>Pumps and Lines>AII PLLD") is then observed. Following the <br />test blockout period, the test sequence repeats after the next dispense. <br />NOTE: If the 0.1 gph (0.3 Iph) test is set for Repetitive, this test must also <br />be set to Repetitive. This selection also enables manual 0.2 gph (0.761ph) <br />tests to run when manually started. <br />Monthly -The test is scheduled at the beginning of a new month and <br />remains scheduled until a test is passed. <br />Manual - 0.2 gph (0.761ph) tests run only when manually started in Diagnos- <br />tics> PLLD> Manual Tests <br />Setup>Pumps and Lines>PLLD <br />Low Pressure Shutoff Value <br />If a low pressure is detected during dispense, a low pressure alarm is trig- <br />gered. The dispenser also halts dispensing if the pressure is lower than the <br />value in this field. <br />Allowable selections: 0 to 25 psi (0 to 172kPa) <br />Default: 0.0 <br />Continuous Handle Timeout <br />If the dispenser handle remains off the hook for the period of time entered in <br />this field, the line is shut down by the console. <br />Allowable selections:1 to 16 hours. Default:16 hours <br />Fuel Out Limit <br />If the tank product level is below the limit entered in this field, the Fuel Out <br />Alarm is triggered. <br />Allowable selections: 0.00 to 15.00 in (0.00 to 381.00mm). Default: 10.00 in <br />(254mm). <br />Altitude Pressure Offset <br />0.1 gph (0.381ph) Line Leak Test I Allows you to set an altitude pressure adjustment for the absolute pressure <br />Touch to select the scheduling frequency of the 0.1 gph (0.381ph) precision transducer of plus or minus 5psi. <br />tests. Allowable selections: -5.0 to 5.0. Default: 0.0. <br />Disabled - No manual or automatic 0.1 gph (0.3 Iph) testing is allowed. This is the default. pump Comm Control Relay <br />Repetitive - After a dispense, a 3.0 gph (11.31ph) test is run, a 0.2 gph <br />(0.761ph) test is run, followed by the 0.1 gph (0.381ph) test. The test blockout <br />period (the Precision Test Delay in "Setup>Pumps and Lines>AII PLLD") <br />is then observed. Following the test blockout period, the test sequence <br />repeats after the next dispense. This selection also enables manual 0.1 gph <br />(0.381ph) testing tests to run when manually started. <br />Auto -The 0.1 gph (0.381ph) test is automatically scheduled to run 6 months <br />after the last passed 0.1 gph (0.381ph) test. This setting also gives you the <br />option to run the Passive 0.1 gph (0.381ph) Line LeakTest. <br />Manual - 0.1 gph (0.381ph) test runs only when manually started in Diagnos- <br />tics> PLLD> Manual Tests. <br />Passive 0.1 gph (0.381ph) Line LeakTest <br />[only available if the pipe type is user -defined and the 0.1 gph (0.381ph) Line <br />LeakTest is set to Auto]. <br />Enables a 0.1 gph (0.381ph) test to run after a passed 0.2 gph (0.761ph) test <br />without the 0.1 gph (0.381ph) test being actively scheduled. If the 0.1 gph <br />(0.381ph) test also passes, you are notified in Diagnostics> PLLD> 0.1 GPH <br />Tests. If it fails, there is no notification of the passive 0.1 gph (0.381ph) test. <br />Allowable selections: Yes, No (default is No). <br />Shutdown Rate <br />The line is shut down if a specified or less precise PLLD test fails. For exam- <br />ple, if you set the shutdown rate for 0.2 gph (0.761ph), the line will shut down <br />if it fails both the 3.0 gph (11.31ph) test and the 0.2 gph (0.761ph) test. <br />Allowable selections: 3.0 gph (11.31ph), 0.2 gph (0.761ph), 0.1gph (0.381ph), <br />or None (default is 3.0 gph (11.31ph). <br />Low Pressure Shutoff <br />If a low pressure is detected during dispense, the Low Pressure Alarm is <br />triggered. The dispenser also halts dispensing if this field is enabled and the <br />pressure is less than the Low Pressure Shutoff Value field below. <br />Allowable selections: Disabled, Enabled (default is Disabled). <br />This relay turns connects/breaks the communication with IQ Control Boxes. <br />It is used during some PLLD tests. <br />When there is pumping on the line in normal operation, the relay is closed <br />and the IQ Control Box can request the assistance from another pump <br />(Helper Mode). <br />The PLLD gross test (3.0 gph/11.3 Iph) is a "pump -off test" so the relay is <br />also closed during this test. <br />However, when a PLLD precision test (0.2 gph/0.76 Iph or 0.1 gph/0.38 Iph <br />test) begins, the relay is opened to prevent the IQ Control Box from request- <br />ing help from another pump while the test is running. <br />The IQ Box must be set to Manual PLLD mode and the relay selected must be <br />set in Setup > Devices (Relays) as a Pump Comm Control relay. <br />M <br />