My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2024
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
S
>
SIKORSKY
>
2050
>
2800 - Aboveground Petroleum Storage Program
>
PR0544293
>
COMPLIANCE INFO_2024
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
10/17/2024 2:30:30 PM
Creation date
10/17/2024 2:27:05 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2800 - Aboveground Petroleum Storage Program
File Section
COMPLIANCE INFO
FileName_PostFix
2024
RECORD_ID
PR0544293
PE
2832 - AST FAC 10 K - </=100 K GAL CUMULATIVE
FACILITY_ID
FA0023280
FACILITY_NAME
JC AIR ACADEMY INC
STREET_NUMBER
2050
Direction
E
STREET_NAME
SIKORSKY
STREET_TYPE
ST
City
STOCKTON
Zip
95206
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
2050 E SIKORSKY ST STOCKTON 95206
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
14
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Environmental Health Department <br />AMENDED <br />9/12/2024 <br />CP22 - AST Non-Qualified Inspection Report <br />Date: <br />September 03, 2024 <br /> Facility Address: <br /> 2050 E SIKORSKY ST, STOCKTON <br /> Facility Name: <br /> JC AIR ACADEMY INC <br />SUMMARY OF VIOLATIONS <br />(CLASS I, CLASS II, or MINOR - Notice to Comply) <br />RemarksItem # <br />CORRECTIVE ACTION: Immediately perform the brittle fracture evaluation of 12,000 gallon field-constructed <br />aboveground tanks after tank repair, alteration, reconstruction, or change in service that might affect the risk of a <br />discharge, and take appropriate action. Submit proof of correction to the EHD. <br />This is (Class 2) Violation. <br />Code of Fed Regulations 112.7(e), 112.8(c)(6) 4030014 - Tanks inspected and tested by qualified person in accordance <br />with industry standards. <br />OBSERVATION: Facility failed to ensure that tanks are inspected and tested by an appropriately qualified person in <br />accordance with industry standards. The 12,000 gallon tank was not tested on schedule or by qualified personnel. <br />Testing must be tested monthly and annually by a qualify personnel . <br />REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container for integrity on a regular schedule <br />and whenever you make material repairs. <br />CORRECTIVE ACTION: Immediately ensure that all tanks are inspected and tested by an appropriately qualified <br />person in accordance with industry standards. Submit proof of correction/ test results to the EHD. <br />This is (Class 2) Violation. <br /> 55 <br />Code of Fed Regulations 112.7(e), 112.8(c)(6) 4030015 - Aboveground containers tested or inspected for integrity <br />based on industry standards. <br />OBSERVATION: Facility failed to test and inspect each aboveground container for integrity based on industry <br />standards, as discussed in the SPCC Plan: On a regular schedule. Inspecting each container’s supports , foundations, <br />and outside for signs of deterioration, discharges, or accumulation of oil inside diked areas. <br />REGULATION GUIDANCE: REGULATION GUIDANCE: 112.8(c)(6) Test or inspect each aboveground container for <br />integrity on a regular schedule and whenever you make material repairs. <br />CORRECTIVE ACTION: Immediately conduct the necessary integrity inspection on 12,000 gallon tank based on <br />industry standards, on a regular schedule, after making material repairs, using non-destructive testing, inspecting <br />each container’s supports , foundations, and outside for signs of deterioration, discharges, or accumulation of oil inside <br />diked areas. Maintain testing and inspection records. Submit a copy of the test/ inspection results to the EHD. <br />This is (Class 2) Violation. <br /> 56 <br />Code of Fed Regulations 112.7(e), 112.8(c)(6) 4010021 - Written Inspection/testing procedures kept, inspection/testing <br />records signed, kept for 3 years. <br />OBSERVATION: The facility failed to keep written procedures and records of inspections and tests, including integrity <br />tests, for at least three years. Copies of inspection and testing records for 2022. 2023, and 2024 were not found on <br />site. <br />REGULATION GUIDANCE: 112.7(e), Conduct inspections and tests required by this part in accordance with written <br />procedures that you or the certifying engineer develop for the facility. You must keep these written procedures and a <br />record of the inspections and tests, signed by the appropriate supervisor or inspector, with the SPCC Plan for a period <br /> 57 <br />FA0023280 PR0544293 SC001 09/03/2024 <br />EHD Rev. 12/06/2021 CP22 - AST Non-Qualified OIRPage 7 of 9 <br />1868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjgov.org/EHD
The URL can be used to link to this page
Your browser does not support the video tag.