CONSTRUCTION DETAILS FOR RECTANGULAR SHEET METAL DUCTS <br />MINIMUM METAL GAGES INCHES x 25,4= mm <br />DZ/ff = 2,63 g/roro <br />STEEL- U.S. <br />ALUMINUM <br />COPPER COLD <br />DUCT DIMENSION <br />OF RECTANGULAR <br />(GAGE) <br />B,&S INCHES <br />(GAGE) <br />ROLLED <br />(IN INCHES) <br />PERMISSIBLE GIRTH JOINTS AND LONGITUDINAL SEAMS <br />0.019 (26) 0.020 (24) <br />16 oz <br />UP THROUGH 12 <br />DRIVE SLIP, PLAIN "S" SLIP, OR 1" POCKET LOCK <br />10' <br />0.047' (NO, 18 GAGE) GALVANIZED STEEL 2' WIDE <br />36' <br />13 THROUGH 18 <br />DRIVE SLIP, PLAIN 'S' SLIP, OR 1' POCKET LOCK <br />0,05B'(NO,16 GAGE) GALVANIZED STEEL 2' WIDE <br />HEMMED 'S' SLIP, V BAR SLIP, OR 1' POCKET LOCK ON 5' CENTERS <br />1 1/8'x1 1/8'x1/8' ANGLE' <br />40' <br />1/8' STEEL x 1 1/2' <br />0.024 (24) <br />0.025 (22) <br />24oz <br />19 THROUGH 30 <br />HEMMED 'S' SLIP, 1' BAR SLIP, OR 1' POCKET LOCK ON 10' CENTERS <br />2'x2'xl/8' ANGLE' <br />OVER 60' <br />3/16' STEEL x 2'' <br />H❑RIZ❑NTAL <br />WITH 1'xl'xl/8' ANGLE ON CENTER LINE BETWEEN <br />18' <br />IN 18' GAGE 2 <br />NONE <br />SAME GAGE AS GALVANIZED STEEL DUCT, V <br />HEMMED 'S' SLIP, 1' BAR SLIP, OR 1' POCKET LOCK ON 10' CENTERS <br />0.024 <br />(24) <br />10' <br />WIDE OR (NO. 18 GAGE GALVANIZED STEEL WIRE) ON 10' CENTERS <br />NONE <br />WITH CROSS BREAK V STANDING SEAM ON 5' CENTERS <br />30' <br />1'x 18' GAGE <br />4' SLIP <br />1' BAR SLIP, REINFORCED BAR SLIP, OR POCKET LOCK, ON 5' CENTERS <br />1' x 1/8' 2 <br />20' <br />SAME GAGE AS GALVANIZED STEEL DUCT, F <br />WIDE OR (NO. 8 GAGE GALVANIZED STEEL WIRE) TIED TO 1' GALVANIZED <br />60' <br />V BAR SLIP, REINFORCED BAR SLIP, OR POCKET LOCK ON 10' <br />1 1/4'x 1 1/4' x 1/8' <br />UP TO 51 <br />18 <br />40' <br />CENTERS WITH 1'xl'xl/8' ANGLES ON CENTER LINE BETWEEN <br />BO' <br />1' x 1/8' 2 <br />OVER 51 <br />31 THROUGH 42 <br />1' STANDING SEAM ON 5' CENTERS <br />0.030 (22) <br />0.032 (20) <br />32 oz <br />UP TO 61 <br />INSIDE LONGITUDINAL STANDING SEAM WITH 1'x1 1'x1/8' <br />OF ROUND DUCT <br />FLANGE <br />OR SIDE OF <br />ANGLES ON 5' CENTERS ON EXTERIOR <br />1 1/2' BAR SLIP, REINFORCED BAR SLIP, OR POCKET LOCK, ON 4' CENTERS <br />ANGLE <br />HANGER <br />36' <br />1 1/2' x 1 1/2' x 1/6' <br />1/4' ROUND ROD OR 1' x I' x 1/8' ANGLE <br />48' <br />2' x 2 ' x 1/8' <br />1 1/2' BAR SLIP, REINFORCED BAR SLIP, OR POCKET LOCK, ON 8' CENTERS <br />60' <br />2' x 2 ' x 1/8' <br />5/16' ROUND ROD OR V x V x 1/8' ANGLE <br />43 THROUGH 54 <br />WITH I 1/2'x1 1/2'x 1/8' ANGLES ON CENTERS LINE BETWEEN <br />3/8' ROUND ROD DR 1' x 1' x 1/8' ANGLE <br />1— SPACED VERTICALLY NOT MORE THAN 12 FEET ON CENTERS. <br />2— SPACED HORIZONTALLY NOT MORE THAN 10 FEET ON CENTERS. <br />3— SPACED NOT MORE THAN 8 FEET ON CENTERS, <br />1 1/2' BAR SLIP, REINFORCED BAR SLIP, OR POCKET LOCK, ON 4' CENTERS <br />STANDING AND SPIRAL. <br />WITH CROSS BREAK <br />1 1/2' STANDING STEAM ON 3' CENTERS <br />0.036 (20) <br />0.040 (18) <br />36oz <br />55 THROUGH 60 <br />INSIDE LONGITUDINAL STANDING SEAM WITH 1 1/2'x1 1/2'x1/B' ANGLES <br />ON 4' CENTERS ON EXTERIOR <br />REINFORCED BAR SLIP, ANGLE SLIP, ALTERNATE BAR SLIP, OR ANGLE <br />REINFORCED POCKET LOCK ON 4' CENTERS USING 1 1/2'x 1 1/2'x 1/8' <br />ANGLES ON CENTER LINE BETWEEN <br />REINFORCED BAR SLIP, ANGLE SLIP, ALTERNATE BAR SLIP, OR ANGLE <br />0,036 (20) <br />0.040 (18) <br />36oz <br />61 THROUGH 84 <br />REINFORCED POCKET LOCK ON 8' CENTERS USING 1 1/2'x 1 1/2'x 1/8' <br />ANGLES & WITH 1 1/2'xl 1/2'x1/8' ANGLES 2' ON CENTERS IN BETWEEN <br />1 1/2' ANGLE REINFORCED STANDING SEAM ON 2' CENTERS USING <br />11/2'x 1 1/2'x 1/8' REINFORCING ANGLES INSIDE LONGITUDINAL STANDING <br />SEAMS WITH 1 1/2'x 1 1/2'x 1/8' ANGLES ON 2' CENTERS ON EXTERIOR <br />DUCT SUPPORT FOR SHEET METAL DUCTS <br />VERTICAL DUCTS <br />MAXIMUM SIDE <br />METAL STRAP DR <br />MAXIMUM <br />ALUMINUM <br />OF RECTANGULAR <br />ANGLE BRACKET <br />DIAMETER OF <br />STRAPS <br />RECTANGULAR DUCT <br />IN INCHES <br />ROUND DUCT <br />GIRTH <br />24' <br />1'x1/6'(STRAP)' <br />10' <br />0.047' (NO, 18 GAGE) GALVANIZED STEEL 2' WIDE <br />36' <br />1'xl'x 1/8'ANGLE' <br />20' <br />0,05B'(NO,16 GAGE) GALVANIZED STEEL 2' WIDE <br />48' <br />1 1/8'x1 1/8'x1/8' ANGLE' <br />40' <br />1/8' STEEL x 1 1/2' <br />60' <br />1 1/2'x1 1/2'x1/8' ANGLE' <br />60' <br />1/8' STEEL x 21, <br />OVER 60' <br />2'x2'xl/8' ANGLE' <br />OVER 60' <br />3/16' STEEL x 2'' <br />H❑RIZ❑NTAL <br />DUCTS <br />18' <br />IN 18' GAGE 2 <br />NONE <br />SAME GAGE AS GALVANIZED STEEL DUCT, V <br />22 <br />0.024 <br />(24) <br />10' <br />WIDE OR (NO. 18 GAGE GALVANIZED STEEL WIRE) ON 10' CENTERS <br />NONE <br />OVER 23 <br />UP TO 37 <br />30' <br />1'x 18' GAGE <br />4' SLIP <br />48' <br />1' x 1/8' 2 <br />20' <br />SAME GAGE AS GALVANIZED STEEL DUCT, F <br />WIDE OR (NO. 8 GAGE GALVANIZED STEEL WIRE) TIED TO 1' GALVANIZED <br />60' <br />1' x 1/8' 2 <br />1 1/4'x 1 1/4' x 1/8' <br />UP TO 51 <br />18 <br />40' <br />STEEL BAND AROUND DUCT ON 10' CENTERS <br />BO' <br />1' x 1/8' 2 <br />OVER 51 <br />0.047 <br />H❑RIZ❑NTAL DUCT TRAPEZE TYPE SUPPORT <br />MAXIMUM DIAMETER <br />UP TO 61 <br />16 <br />OF ROUND DUCT <br />FLANGE <br />OR SIDE OF <br />HORIZONTAL SUPPORT <br />RECTANGULAR DUCT <br />ANGLE <br />HANGER <br />36' <br />1 1/2' x 1 1/2' x 1/6' <br />1/4' ROUND ROD OR 1' x I' x 1/8' ANGLE <br />48' <br />2' x 2 ' x 1/8' <br />1/4' ROUND ROD OR 1' x 1' x 1/8' ANGLE <br />60' <br />2' x 2 ' x 1/8' <br />5/16' ROUND ROD OR V x V x 1/8' ANGLE <br />84' <br />2' x 2 ' x 1/8' <br />3/8' ROUND ROD DR 1' x 1' x 1/8' ANGLE <br />1— SPACED VERTICALLY NOT MORE THAN 12 FEET ON CENTERS. <br />2— SPACED HORIZONTALLY NOT MORE THAN 10 FEET ON CENTERS. <br />3— SPACED NOT MORE THAN 8 FEET ON CENTERS, <br />CONSTRUCTION <br />DETAILS <br />FOR <br />ROUND SHEET METAL DUCTS <br />DUCT DIAMETER <br />ALUMINUM <br />STEEL -THICKNESS <br />NOT USED <br />MAXIMUM WIDTH <br />B.& S. GAGE <br />IN INCHES <br />GIRTH <br />JDINTJL <br />(INCHES)MIN, <br />PRESSURE<2' W <br />PRESSURE<2' <br />WC <br />GRITH REINFORCEMENT <br />MAX. SPACDK AND <br />TYP. OF 4 (ONE PER SIDE) 4X6 BLOCKING W/ <br />ROUND <br />ROUND <br />PRESSURE >_2' < 10' WC <br />ANGLE SIZE <br />UP TO 9 <br />24 <br />0.019(26) <br />TRAP FORMED OF <br />2' SLIP <br />NONE <br />UP ER 9 4 <br />24 <br />(26) <br />4'SLIP <br />NONE <br />OVER 14 <br />UP TO 23 <br />22 <br />0.024 <br />(24) <br />FOOT TO DRAIN. <br />4' SLIP <br />NONE <br />OVER 23 <br />UP TO 37 <br />20 <br />0,030 <br />(22) <br />4' SLIP <br />NONE <br />OVER 37 <br />CONDENSATE DRAIN DETAIL N.T.S. <br />0,036 <br />1 1/4'x 1 1/4' x 1/8' <br />1 1/4'x 1 1/4' x 1/8' <br />UP TO 51 <br />18 <br />(20) <br />1 FLANGE <br />ON 72' <br />OVER 51 <br />0.047 <br />1 1/4'x 1 1/4' x 1/8' <br />1 1/4'x 1 1/4' x 1/8' <br />UP TO 61 <br />16 <br />(18) <br />FLANGE <br />ON 72' <br />OVER 61 <br />0,058 <br />1 1/2'x 1 1/2' x 1/8' <br />1 1/2'x 1 1/2' x 1/8' <br />UP TO 84 <br />1 14 <br />(16) <br />FLANGE <br />ON 48' <br />1- FOR PRESSURE < 2 INCHES WC (498 Pa), ANY <br />OF THE FOLLOWING JOINTS <br />ARE ACCEPTABLEI BUTT SLIP, <br />PIPE SLIP, PIPE LOCK, ROLL <br />SLIP, SNAP <br />SLIP, PLENUM LOCK AND COMPANION FLANGE. <br />2- ACCEPTABLE <br />LONGITUDINAL SEAMS FOR <br />PRESSURE < 2 INCHES WC (498Pa)I ACME (GROOVED), SNAP LOCK, <br />STANDING AND SPIRAL. <br />HOOD EXHAUST FAN <br />MECHANICAL NOTES. UP BLAST. EXHAUST DISCHARGE <br />SHALL BE DIRECTED UP AND DISCHARGE POINT HOOD <br />AWAY FROM THE SURFACE OF <br />1. ALL WORK AND MATERIALS SHALL BE PERFORMED AND INSTALLED IN ROOF W/ MIN. 40" ABOVE ROOF <br />COMPLIANCE WITH THE FOLLOWING CODES AS AMENDED AND ADOPTED PER CMC SECTION 510.8.2.1 1/4" GALVANIZED FLASHING <br />BY THE INSPECTION AUTHORITY. NOTHING IN THESE PLANS IS TO BE 24" VENTED ROOF CURB z STL. MESH SCREEN <br />CONSTRUED TO PERMIT WORK NOT CONFORMING TO THESE CODES OR TO BE LEVELED MASTIC ALL <br />OTHERS APPLICABLE TO THIS SUBJECT. W/ FLASHING. <br />AROUND <br />A. CALIFORNIA BUILDING CODE 2019 ROOF OPENING #12 TEK SHEET METAL —OPEN — <br />BLOCKING <br />B. CALIFORNIA MECHANICAL CODE 2019 SCREWS, 2 PER SIDE <br />ROOF <br />C. CALIFORNIA PLUMBING CODE 2019 (EE)) ROOF— PATCH & I I <br />D. CALIFORNIA ELECTRICAL CODE 2019 REPAIR AS REQUIRED I I ROOF JACK <br />E. NATIONAL FIRE PROTECTION ASSOCIATION <br />F. STATE OF CALIFORNIA ENERGY CONSERVATION REGULATION, TITLE 24 I I <br />2. DRAWINGS INDICATE DIAGRAMMATICALLY THE ARRANGEMENT OF 1/2" TH DED ROD <br />tl <br />PRINCIPLE APPARATUS, PIPING, DUCTWORK AND OTHER MATERIAL./ <br />FOLLOW DRAWINGS AS CLOSELY AS POSSIBLE, IN ORDER TO ACHIEVE ME TS A 2"X2°X7/B" TOP CHORD OF <br />METAL GLE CONNECT TRUSS CONNECT DUCT TO <br />A NEAT ARRANGEMENT OF PIPING, DUCTWORK, AND EQUIPMENT WHILE TRUSS W 2" OLT W/ NUT <br />STILL OVERCOMING OBSERVATIONS. AND WASHE JACK W/ #10 TEK SHEET VENT <br />3. DUCT SHALL BE INSULATED FLEXIBLE DUCTWORK CONTINUOUS INTERNAL 2x6 BLOCKI OFFSET D CT IN FIELD AS METAL SCREWS <br />LINER BONDED TO GALVANIZED STEEL WIRE HELIX. 1 POUND PER CU.FT. ' I I NEEDE TO LEAR LL CLE U AL <br />12"x18" OR MEMBER A WALL (LEA NCE <br />GLASS FIBER INSULATION , 1" THICK WHERE DUCTWORK IS WITHIN THE 10"x15" 16GA EXH US j <br />BUILDING THERMAL INSULATION ENVELOPE, 1 1/2" THICK WHERE DUCTWORK DUCT W/ 3M FIRE RR R f <br />IS OUTSIDE THE BUILDING THERMAL INSULATION ENVELOPE. DUCT WRAP 15A UL— 78 f BOF TOUSCHORD <br />SEAMLESS VAPOR BARRIER JACKET. EACH LENGTH SHALL HAVE A INSTALLED PER ITS LIST G <br />FACTORY INSTALLED METAL SLEEVE AT EACH END. DUCT SHALL & PER CMC SECTION 507. 3 i I_ ROOF JACK N.T.S. <br />COMPLY WITH UL -181 AND NEPA 90A & B. _ <br />GENFLEX, LAMBORN OR APPROVED EQUAL, MAX. OF 5' LENGTH. I I <br />4. ALL BRANCH DUCTS SHALL HAVE BALANCING DAMPERS WITH ACCESSIBLE <br />LOCKING TYPE QUADRANT. I <br />MAKE UP AIR DUCT <br />5. THERMOSTATS SHALL HAVE THE CAPACITY OF TERMINATING ALL <br />HEATING AT A TEMPERATURE NO MORE THAN 70 F, OF TERMINATING NOTE: INSTALL DRAW BANDS <br />1/2" THREADED ROD DO NOT CUT ANY ON BOTH ENDS OF <br />ALL COOLING AT A TEMPERATURE NOT LESS THAN 78 F, AND BE W/ NUTS CONNECTED I I TRUSS MEMBER /j10 WIRE FRO FLEx. DUCT (TYP.) <br />ADJUSTABLE TO PROVIDE A TEMPERATURE RANGE OF UP TO 5' TO BRACKET AT HOOD I I STRUCTURE RIGID DUCT <br />BETWEEN FULL HEATING AND FULL COOLING. (TYP. OF 4) ONE AT EACH CORNER <br />6. FACTORY ROOF CURB SHALL BE LEVELED. rkAlxl RIGID ELEeow <br />u—Dr>,r% I,CILIINV _ I I III/ <br />7. ALL EQUIPMENT SHALL COMPLY WITH THE CALIFORNIA ENERGY OR GYP. BD. GREASE FILTER SHALL <br />COMMISSION STANDARD, AND BE CERTIFIED BY THE MANUFACTURE. BE LISTED BY AN FLEX. FIBERGLASS DUCT <br />8. THE MECHANICAL CONTRACTOR SHALL PROVIDE THE OWNER COPIES PE MIN. CLEARANCE APPROVED LISTING SIZE AS SHOWN ON PLANS <br />PER CMC SECTION 50 .2.1 AND TESTING AGENCY <br />OF OPERATION, MAINTENANCE AND PREVENTATIVE MAINTENANCE STAINLESS STEEL MAKE—UP SMC SEC. 509.2.4 2X BLOCK AT <br />MANUALS FOR EACH MODEL AND TYPE OF MECHANICAL EQUIPMENT. PLENUM— GYP. BD. CEILING <br />9. ALL ROOF MOUNTED EQUIP. SHALL BE PERMANENTLY LABELED AS STUD WALL 3xDUCT DIA.(MIN.) <br />22 GA TYPE S.S. PERFORATED W/ 5/8" GYP. BD. EA.SIDE <br />TO THE AREA OR SPACE THAT SERVES. COMPENSATING HOOD PANEL L -BRACKET CONNECT HOOD CEILING <br />10. COORDINATE EXACT LOCATION OF AIR TERMINALS WITH THE LISTED HOODTO WALL <br />ARCHITECTURAL REFLECTED CEILING PLAN AND STRUCTURAL FRAMING. 6" COOKING STAINLESS STEEL SHEET METAL <br />MIN. SURFACE I I FLASHING. CADY CLIP- ONE AT \ <br />11. WORKMANSHIP: I I EACH CORNER SURFACE MOUNTED <br />ALL WORK SHALL BE DONE IN A NEAT AND WORKMAN LIKE MANNER I I STAINLESS STEEL PANEL CEILING DIFFUSER <br />ACCORDING TO THE BEST TRADE PRACTICE BY THOSE SKILLED IN I ON WALL FULL LENGTH <br />� OF HOOD & UP TO HOOD 24"x24" DROP—IN MODULE <br />THE PARTICULAR TRADE. PIPES, FIXTURES, EQUIPMENT, GRILLES, -H--- CEILING DIFFUSER <br />REGISTERS, ETC., TO BE INSTALLED LEVEL, SQUARE OR CENTERED, <br />ETC. , TO GIVE A NEAT AND PLEASING APPEARANCE. ALL EQUIPMENT <br />IS TO BE INSTALLED STRICTLY PER MANUFACTURER'S RECOMMENDATIONS. <br />GAS CONNECTION <br />COORDINATE ALL WORK WITH OTHER TRADES. M <br />-H W/ SHUT—OFF VALVE <br />12. ELECTRICAL VOLTAGE: 4" MIN. CL, FLEX CONNECTION 2 SUPPLY GRILLE DIFFUSER AIR CONDITIONING CONTRACTOR SHALL CONFIRM ALL SYSTEM s" MAX. TYPICAL N.T.S. <br />VOLTAGES BEFORE BIDDING AND ORDERING EQUIPMENT. FLOOR <br />13. THERMOSTATS SHALL BE WHITE ROGERS PROGRAMMABLE T'STAT. <br />PROVIDE LOW VOLTAGE (24V) WIRING IN CONDUIT BETWEEN COMPONENTS NOTE: DISCONNECT SWITCH <br />COMPONENTS AND EQUIPMENT OR EQUAL, PROGRAMMABLE T'STAT REFER <br />1— PROVIDE S.S. PANEL ENCLOSURE AROUND HOOD UP TO CEILING. SCHEDULE <br />EQUIPMENT <br />E FOR ROOF <br />14. ALL SUPPLY GRILLES SHALL BE METAL AIR MODEL 5500-65, 2— REPLACEMENT AIR (MAKE UP AIR) QUANTITY SHALL BE ADEQUATE TO EXHAUST FAN. <br />PROVIDE OPPOSED BLADE DAMPERS AT GYPSUM BOARD CEILING, PREVENT NEGATIVE PRESSURE IN THE COMMERCIAL COOKING AREA FROM <br />STANDARD OFF—WHITE FINISH. EXCEEDING 0.02" W.C. PER CMC SEC. 511.3 SECURE FAN TO CURB <br />15. ALL RETURN GRILLES SHALL BE METAL AIRE SERIES 7550R 5 KITCHEN HOOD WITH 1/4"0 LAG BOLTS. <br />STANDARD OFF—WHITE FINISH. N.T.S. 2 PER SIDE. <br />16. SIDEWALL SUPPLY / RETURN GRILLES SHALL BE METAL AIR SERIES <br />T54 STD OFF—WHITE FINISH. <br />17. PROVIDE VOLUME DAMPERS AT ALL SUPPLY GRILLES MAKE—UP AIR UNIT FACTORY CURB COLLAR I 1 1 It I I 1 1 <br />18. ALL SUPPLY AND RETURN DUCTS OPENING SHALL BE PROTECTED AND ANCHORED TO ROOF MANUF. ROOF CURB <br />COVERED WITH PLASTIC DURING CONSTRUCTION CURB 3/4" OVER FLOW DRAIN W/ WEATHER SEAL <br />19. RETURN AIR FILTERS SHALL HAVE A MINIMUM EFFICIENCY REPORT VALUE 1/2" MAKE UP WATER BY P.C. TO ROOF DRAIN BY P.C. <br />(MERV) OF 8, BASED ON ASHRAE 52.2-1999 <br />1111.11 �11T (CCT Cone CAITDV nnnD IAAAInnW LEVELED ROOF BACKDRAFT DAMPERI f <br />UUNU W/FLAJHINU <br />AND MECHANICAL OUTSIDE AIR INTAKE SEE DETAI 8 ROOF <br />21. HVAC REFRIGERATION AND FIRE SUPRESSION EQUIPMENT SHALL NOT CONTAIN <br />CFC AND HALON. \ <br />(E) ROOF SYSTEM SECURE CURB TO ROOF 4x4 6BLOCKING ALL AROUND <br />PATCH &REPAIR WITH 1/2"0 LAG BOLTS. SECURE BLOCKING AT EACH <br />AS REQUIRED END WITH "SIMPSON" JOIST <br />(TYP. OF 1 BOLT PER SIDE) HANGER LUS44 AT ROOF <br />DUCT — REFER TO TRUSSES <br />NOTE: PLANS FOR SIZE <br />1. ALL ROOF OPENNINGS SHALL BE <br />SUPLY DUCT VIN BETWEEN ROOF FRAME. DO NOT <br />CUT ANY ROOF FRAMING 31 ROOF MOUNTED EXHAUST FAN <br />N.T.S. <br />2. MAINTAIN MIN. 10' CLR. FROM <br />ANY EXHAUST FANS <br />1/2"THRU UNIT BASE <br />INTO <br />CONTINUOUS SEAL 6 SECTION AT MAKE-UP AIR UNIT <br />THRU UNIT BASE INTO <br />ROOFCURB-(2) PER <br />SIDE <br />NAIL STRIP WITH ROOF CURB TEE PLUG FOR <br />RIGID INSULATION BY M.C. CLEANN OUT, TYPICAL <br />8" HIGH ROOFCURB BY UNIT MFC. FOR ALL CHANGES <br />CANT STRIP ALL AROUND (EXTENDS ALL AROUND IN DIRECTION. <br />UNIT PERIMETER) <br />SHIM LEVEL W/ CONT. TEE W/ OPEN END <br />4x CUT TO FIT ROOF FOR OVERFLOW, UIJIT <br />SLOPE BY G C OF BELOW FLOOD LEVEL p� <br />2 3 0 1 Coffee Road #B ♦ Modesto, CA 95355 <br />Phone: 209 - 408-0674 p edmond@etjarchitect.com <br />IRCHITECT: <br />THE DRAWINGS, SPECIFICATIONS, DESIGN AND IDEAS <br />DESCRIBED HEREIN SHALL REMAIN THE PROPERTY OF <br />THE ARCHITECT AND NO PART THEREOF CAN BE COPIED, <br />DUPLICATED, DISCLOSED TO OTHERS OR USED IN <br />CONNECTION WITH ANY WORK OR PROJECT OTHER THAN <br />THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN <br />PREPARED AND DEVELOPED WITHOUT EXPRESS WRITTEN <br />PERMISSION OF THE ARCHITECT. <br />EDMOND T. JACOBS ARCHITECT COPYRIGHT 2022 <br />:ONSULTANT: <br />PROJECT ADDRESS: <br />MANTECA FOOD <br />TENANT IMPROVEMENT <br />KITCHEN <br />& MEAT AREA <br />REMODEL <br />441 N. MAIN ST. <br />MANTECA, CA 95336 <br />CLIENT: <br />MR. EMAD MCIHSEN <br />447 N. MAIN STREET <br />MANTECA, CA 95336 <br />DATE: MARCH 11, 2022 <br />DRAWN: ETJ <br />FILE: 331-21-M 1 -MECHANICAL <br />PROJECT NO: 329-21 <br />PERMIT NO: <br />DESCRIPTION: <br />MECHANICAL NOTES <br />& DETAILS <br />SHEET NO. <br />M-1 <br />- TOP CHORD <br />TPO ROOF — TRUSS <br />OF CONDENSATE PAN. <br />NOT USED <br />PATCH AS REQUIRED <br />3" <br />3/4" DIA.xl2"L LAG BOLT <br />TYP. OF 4 (ONE PER SIDE) 4X6 BLOCKING W/ <br />SIMPSON HU416 HANGER <br />TRAP FORMED OF <br />LONG RADIUS ELBOWS <br />SLOPE 1/8" PER <br />FOOT TO DRAIN. <br />SEE PLAN FOR CONTINUATION <br />8 <br />1 MANUFACTURED CURB <br />7 <br />CONDENSATE DRAIN DETAIL N.T.S. <br />4 <br />2 3 0 1 Coffee Road #B ♦ Modesto, CA 95355 <br />Phone: 209 - 408-0674 p edmond@etjarchitect.com <br />IRCHITECT: <br />THE DRAWINGS, SPECIFICATIONS, DESIGN AND IDEAS <br />DESCRIBED HEREIN SHALL REMAIN THE PROPERTY OF <br />THE ARCHITECT AND NO PART THEREOF CAN BE COPIED, <br />DUPLICATED, DISCLOSED TO OTHERS OR USED IN <br />CONNECTION WITH ANY WORK OR PROJECT OTHER THAN <br />THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN <br />PREPARED AND DEVELOPED WITHOUT EXPRESS WRITTEN <br />PERMISSION OF THE ARCHITECT. <br />EDMOND T. JACOBS ARCHITECT COPYRIGHT 2022 <br />:ONSULTANT: <br />PROJECT ADDRESS: <br />MANTECA FOOD <br />TENANT IMPROVEMENT <br />KITCHEN <br />& MEAT AREA <br />REMODEL <br />441 N. MAIN ST. <br />MANTECA, CA 95336 <br />CLIENT: <br />MR. EMAD MCIHSEN <br />447 N. MAIN STREET <br />MANTECA, CA 95336 <br />DATE: MARCH 11, 2022 <br />DRAWN: ETJ <br />FILE: 331-21-M 1 -MECHANICAL <br />PROJECT NO: 329-21 <br />PERMIT NO: <br />DESCRIPTION: <br />MECHANICAL NOTES <br />& DETAILS <br />SHEET NO. <br />M-1 <br />