Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMPIUDD TESD` <br /> Test Method Developed by 97 Manufacturer Industry Standard Professional Engineer <br /> Test Type g7 Pressure Vacuum Hydrostatic <br /> Test Equipment Used, 1N ON-TS1000-Hyd-15min <br /> SumplUDD ID 87 STP 91 STP DSL STP 1-2 <br /> Sump Manufacturer {SIA N/A N/A N/A <br /> Sump Depth (inches) N/A NIA IIF N/A <br /> Sump Bottom to Tap of N/A NIA NIA N/A <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Btart Ti-me 12:15 12:15 10:26 14:15 <br /> Initial Reading 4.5466 2.5787 2.0607 3.3757 <br /> Test End Time 12:30 12:30 10:41 14:30 <br /> Final Reading 4.6456 2.5790 2,0605 3.3742 <br /> Change in Reading .0010 .0003 0002 ,0015 <br /> PasslFail Criteria 0.002 10,002 0.002 0.002 <br /> Tightness Test ResuIts 0 Pass n Fail Pass ® Fail El Pass E] Fail 21 Pass 97 Fa 11 <br /> FSum.pVULDC ID 3-4 5-6 7-8 9-10 <br /> Manufacturer NIA NIA NIA NIA <br /> Dpth (inches) NIA NIA NIA NIA <br /> Sump Bottom to Top of NIA NIA N/A NIA <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 13:55 13:34 13:55 13:34 <br /> Initial Leading 2.2347 3.2714 3.7498 4.5877 <br /> Test End Time 14:11 13.49 14:11 13:49 <br /> Final Beading 2.2354 3.2716 3.7497 4.5870 <br /> Change in Reading 0007 .0002 .0001 .0007 <br /> Pass/Fail Criteria 0.002 0.002 0.042 0.002 <br /> Tightness Test Results I IVJ Pass Fail Ej Pass 0 Fail Pass Fail Pass Fail <br /> Additional copies of this page may be attached. <br /> A11 tests marked "Fall"and any repairs made before or daring the tfghfness test rrmU st be described in <br /> time COMMENTS section. <br /> Page 3of5 <br />