A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: 7642 <br /> ity Address: Date: <br /> PARK ST PETROLEUM INC N HUNTER ST, STOCKTON May 27 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> This is (Minor)Violation. <br /> 10 CA Code of Regulations 2638(c), 2638(d)2030074-Annual Monitoring System Certification Form to the CUPA within <br /> 30 days of completion of the test. <br /> OBSERVATION:A monitoring system certification and leak detector testing was performed on 5/29/2024. A test <br /> report has not been submitted to the EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> This is (Minor)Violation. <br /> 11 CA Code of Regulations 2637(a-d), 2712(b)(1)(F)2030048-Sec containment testing conducted per requirements& <br /> records kept for 36 mths(TCR 9d). <br /> OBSERVATION: Secondary containment testing was scheduled to be performed on 7/11/2023. A test report has not <br /> been submitted to the EHD or the California Environmental Reporting System (CERS). No record of testing was <br /> observed on site. <br /> REGULATION GUIDANCE: Secondary containment testing is required once every 36 months. A copy of the test <br /> report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately schedule this test and provide 48 hours notification to the EHD. <br /> This is (Class 2)Violation. <br /> 13 CA Code of Regulations 2637.1(d),2637.1(e)2010017- Spill bucket testing results submitted to the UPA within 30 <br /> days of testing. <br /> OBSERVATION: Spill container testing was performed on May 29,2024 . A test report has not been submitted to the <br /> EHD or the California Environmental Reporting System (CERS). <br /> REGULATION GUIDANCE:A copy of the test report must be submitted within 30 days of the test. <br /> CORRECTIVE ACTION: Immediately provide this report to the EHD. <br /> This is(Minor)Violation. <br /> 30 CA Code of Regulations 2630(d),2641(a)2060015-Leak detection equipment located so leak is detected at the <br /> earliest possible opportunity(TCR 9d). <br /> OBSERVATION:The following sensors were not located to detect a leak at the earliest opportunity: <br /> - The 87 unleaded STP sump sensor was raised approximately 12 inches off the lowest point of the sump with <br /> approximately 20 gallons of liquid inside the sump. <br /> - The#9/10 UDC 001 sensor was raised approximately 8 inches off the lowest point of the under dispenser container <br /> with 1 approximately gallon of liquid. <br /> REGULATION GUIDANCE: Monitoring equipment shall be maintained to be able to detect a leak at the earliest <br /> possible opportunity. <br /> FA0000799 PR0231148 SCO01 05/27/2025 <br /> EHD Rev.12/06/2021 Page 6 of 9 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />