Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Form <br /> 7. LINE LEAK DET TOR TESTING <br /> ❑Check this box if lin leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rat verified: (Check all that apply.) Yes No NA <br /> x3 GPH ❑0.1 GPH❑3.2 GPH <br /> Has the testing apparatus been properly calibrated? X ❑ ❑ <br /> For emergency generator tank systems, does the LLD create an audible and visual alarm ❑ ❑ X <br /> when a leak is detected? <br /> For mechanical LLDs does the LLD restrict the flow through the pipe when a release is X D ❑ <br /> detected? <br /> For electronic LLDs, oes the turbine automatically shut off when a release is detected? X ❑ <br /> For electronic LLDs, oes the turbine automatically shut off if any portion of the monitoring X ❑ <br /> system is disabled or disconnected? <br /> For electronic LLDs, oes the turbine automatically shut off if any portion of the monitoring X ❑ <br /> system malfunctions r fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected for x O <br /> kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? X D ❑ <br /> Were all LLDs confirmed operational within regulatory requirements? X ❑ <br /> LLD ID LLD Model Lines Monitored Pass Fail <br /> 01 V/R 8484 87 x ❑ <br /> 02 V/R 84f 14 91 x ❑ <br /> T3 VM199 D2000 Diesel x ❑ <br /> Describe all answe s marked "No"or"Fail"and proposed remedy in Section 9. <br /> List all monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />