Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by © Manufacturer 0 Industry Standard El Professional Engineer <br /> Test Type © Pressure El Vacuum E Hydrostatic <br /> Test Equipment Used: ONMTEC - PROTEUS OEL8000111-CLD Series <br /> Sump/UDC ID 87 STP 91 STP Die#3 (Retail) STP Die#3(Commercial)STP <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 60 60 64 60 <br /> Sump Bottom to Top of 15 18 20 17 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 10:55 10:55 10:55 11:38 <br /> Initial Reading 3.918 10.899 10.655 9.488 <br /> Test End Time 11:10 11:10 11:10 11:53 <br /> Final Reading 3.918 10.899 10.655 9.487 <br /> Change in Reading 0.000 0.000 0.000 -0.001 <br /> Pass Fail Criteria +i-0.002 +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results © Pass © Fail © Pass rl Fail r Pass © Fail © Pass El Fail <br /> Sump/UDC ID Die#4(Retail) STP Die#4(Siphon) STP <br /> Sump Manufacturer Unknown (FRP) Unknown (FRP) <br /> Sump Depth (inches) 67 70 <br /> Sump Bottom to Top of 19 20 <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 11:38 11:38 <br /> Initial Reading 13.166 12.884 <br /> Test End Time 11:53 11:53 <br /> Final Reading 13.166 12.884 <br /> Change in Reading 0.000 0.000 <br /> Pass Fail Criteria +/-0.002 +/-0.002 <br /> Tightness Test Results 0 Pass 0 Fail © Pass 0 Fail 0 Pass © Fail LM Pass Ll Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />