Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST (continued) <br /> Test Method Developed by 0 Manufacturer © Industry Standard © Professional Engineer <br /> Test Type © Pressure © Vacuum Ej Hydrostatic <br /> Test Equipment Used: INCON -STS Operations -Level 4 <br /> Sump/UDC ID UDC#5-6 UDC#7-8 UDC#S9 UDC#9-S10 <br /> Sump Manufacturer Bravo (Steel) Bravo (Steel) Bravo (Steel) Bravo (Steel) <br /> Sump Depth (inches) 9 9 9 9 <br /> Sump Bottom to Top of Bottom Bottom Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 12:24 12:24 13:33 13:33 <br /> Initial Reading 1.8169 1.0696 0.4881 0.0229 <br /> Test End Time 12:39 12:39 13:48 13:48 <br /> Final Reading 1.8168 1.0696 0.4881 0.0217 <br /> Change in Reading -0.0001 0.000 0.000 -0.0012 <br /> Pass Fail Criteria +i-0.002 +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results [71 Pass rl Fail Iāœ“ Pass r] Fail El Pass © Fail El Pass r] Fail <br /> Sump/UDC ID UDC#10-S11 UDC#11-S12 UDC#12-S13 UDC#13-S14 <br /> Sump Manufacturer Bravo (Steel) Bravo (Steel) Bravo (Steel) Bravo (Steel) <br /> Sump Depth (inches) 9 9 9 9 <br /> Sump Bottom to Top of Bottom Bottom Bottom Bottom <br /> Highest Pipe Penetration <br /> (inches) <br /> Test Start Time 13:33 13:33 12:07 12:07 <br /> Initial Reading 0.1765 0.2005 0.6644 0.2845 <br /> Test End Time 13:48 13:48 12:22 12:22 <br /> Final Reading 0.1764 0.1999 0.6643 0.2845 <br /> Change in Reading -0.0001 -0.0006 -0.0001 0.0000 <br /> Pass Fail Criteria +i-0.002 +i-0.002 +i-0.002 +i-0.002 <br /> Tightness Test Results ®āœ“ Pass ® Fail © Pass ® Fail 0āœ“ Pass © Fail Eāœ“ Pass El Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail"and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 4 of 5 <br />