Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> NATIONAL PETROLEUM MANTECA 2072 W YOSEMITE AVE, MANTECA September 17 2024 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> CORRECTIVE ACTION: Take all necessary precautions to ensure testing and submittal of test reports are performed <br /> in a timely manner. <br /> This is (Minor)Violation. <br /> 28 CA Code of Regulations 2638(a), 26410)2030043- Leak detection equipment properly installed, calibrated, operated, <br /> and maintained (TCR 9d). <br /> OBSERVATION:The racing fuel 100 and 110 tanks annual leak detector testing were last performed on 01/29/2020 <br /> and were due by 09/2021, 09/2022, 09/2023, 09/2024. Testing has not been completed and is 57 months past due. <br /> REGULATION GUIDANCE:All monitoring equipment shall be installed, calibrated, operated, and maintained in <br /> accordance with manufacturer's instructions, and certified for operability, proper operating condition, and proper <br /> calibration. Immediately contact a properly licensed and certified contractor to ensure leak detectors are operating in <br /> accordance with manufacturer's instructions. <br /> CORRECTIVE ACTION: Ensure that all leak detection equipment is properly programmed and maintained at all times. <br /> This is (Class 2)Violation. <br /> 45 CA Code of Regulations 2636(f)(2)2030025-LLD on DW press piping monitors hrly, detects a 3.0 gph leak, and <br /> restricts/shuts off flow(TCR 9d). <br /> OBSERVATION:The racing fuel 100 and 110 line leak detector has not been tested to ensure its ability to detect a <br /> leak. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: Immediately have a properly licensed, trained, and certified contractor repair or replace the <br /> failed leak detector(LG 113-x listed, if applicable)and obtain a permit within one business day from the EHD, if <br /> needed. If the failed leak detector can't be replaced immediately,there is a possibility that the racing fuel 100 and 110 <br /> tanks UST system may be red tagged to prevent fuel inputs. <br /> This is a repeat violation (Class 2) Violation. <br /> 50 CA Code of Regulations 2635, 2637.1, 2665, 2712 2060020-Spill buckets meet requirements, have been tested as <br /> required, and records kept for 36 mths(TCR 9a). <br /> OBSERVATION: Spill Container test results for 2022 were not available at time of inspection. <br /> REGULATION GUIDANCE: Records of spill container test are to remain on site for 36 months. <br /> CORRECTIVE ACTION: Immediately locate test results and ensure they remain on site for 36 months and send proof <br /> to EHD. <br /> This is a repeat violation (Class 2) Violation. <br /> 53 CA Health and Safety Code 25292.2; CCR 2711(a)(11)2010007-Submitted/maintained current Cert of Financial <br /> Responsibility/mech of financial assurance(TCR 11). <br /> OBSERVATION: Financial responsibility documents have not been submitted to the EHD. The most recent financial <br /> FA0004625 PR0231426 SCO01 09/17/2024 <br /> EHD Rev.12/06/2021 Page 7 of 9 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />