My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2025
EnvironmentalHealth
>
EHD Program Facility Records by Street Name
>
G
>
GRANT LINE
>
2420
>
2300 - Underground Storage Tank Program
>
PR0231580
>
COMPLIANCE INFO_2025
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
2/22/2026 12:40:24 PM
Creation date
2/26/2025 1:55:02 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2025
RECORD_ID
PR0231580
PE
2361 - UST FACILITY
FACILITY_ID
FA0003963
FACILITY_NAME
TRACY 76
STREET_NUMBER
2420
Direction
W
STREET_NAME
GRANT LINE
STREET_TYPE
RD
City
Tracy
Zip
95377
APN
23802006
CURRENT_STATUS
Active, billable
QC Status
Approved
Scanner
SJGOV\kblackwell
Supplemental fields
Site Address
2420 W GRANT LINE RD Tracy 95377
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
43
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> TRACY 76 1 2420 W GRANT LINE RD, Tracy March 21 2025 <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> as installed do not monitor all grades of fuel in the UDCs. <br /> REGULATION GUIDANCE:These tests are required once every 12 months. <br /> CORRECTIVE ACTION: Immediately schedule these tests and provide 48 hours notification to the EHD. Please be <br /> aware that all EHD staff time associated with a follow up inspection will be billed at our current hourly rate ($172). <br /> This is a repeat violation (Class 2) Violation. <br /> 24 CA Code of Regulations 2632(c), 2634(d), 2636(f)2030003-Leak detection system maintains continuous monitoring <br /> that activates an audible and visual alarm. <br /> OBSERVATION:The float&chain in all the UDCs(1/2, 3/4, 5/6, 7/8) failed to stop the flow of product at the <br /> dispenser when tested. 3 float&chains in UDC 1/2, 3/4, 7/8 were disconnected from the pipe. 2 float&chains in UDC <br /> 5/6 were disconnected from the pipe. <br /> REGULATION GUIDANCE:All monitoring equipment shall be maintained to activate an audible and visual alarm or <br /> stop the flow of product at the dispenser when it detects a leak. <br /> CORRECTIVE ACTION: Correct immediately by having a properly licensed,trained, and certified contractor replace <br /> the failed component with a functional component(LG 113-x listed, if applicable), and obtain a permit within one <br /> business day from the EHD, if needed. If the failed component can't be replaced immediately,there is a possibility <br /> that the 87, 91, E-85 UST system may be red tagged to prevent fuel inputs. <br /> This is a repeat violation (Class 2) Violation. <br /> 45 CA Code of Regulations 2636(f)(2)2030025-LLD on DW press piping monitors hrly, detects a 3.0 gph leak, and <br /> restricts/shuts off flow(TCR 9d). <br /> OBSERVATION:The 91 VMI line leak detector failed to detect a leak when tested. <br /> REGULATION GUIDANCE:All line leak detectors shall be capable of detecting a 3-gallon per hour leak at 10 psi. <br /> CORRECTIVE ACTION: This was corrected on site.The service technician adjusted the leak detector, retested it, and <br /> it passed. <br /> This is a repeat violation (Class 2) Violation. <br /> 52 CA Code of Regulations 2635(c)(1)2030036-Overfill prevention system has not been overridden and meets overfill <br /> requirements(TCR 9b). <br /> OBSERVATION: Overfill Prevention Equipment testing was last performed on 9/27/2021 and was due by September <br /> 2024. Testing has not been completed and is 6 months past due. The designated operator has been writing 3/12/2024 <br /> on all DO reports as the Overfill Prevention Equipment date. EHD does not have a record of testing notification or <br /> results for Overfill Prevention Equipment testing for that date. <br /> REGULATION GUIDANCE: Overfill prevention equipment inspections were required to be conducted by October 13, <br /> 2018, and every 36 months thereafter, and within 30 days of completion of a repair. <br /> CORRECTIVE ACTION: Immediately schedule this test and provide 48 hours notification to the EHD. <br /> FA0003963 PR0231580 SCO01 03/21/2025 <br /> EHD Rev.12/06/2021 Page 6 of 9 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />
The URL can be used to link to this page
Your browser does not support the video tag.