Laserfiche WebLink
A dOAQU1N Environmental Health Department <br /> COUNTY <br /> CP22 - UST FULL Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CAGASOLINE INC 2115 W YOSEMITE AVE MANTECA March 20 2025 <br /> 87 CA Code of Regulations 2060021-Striker plate installed and positioned correctly. ❑OUT ❑R ❑COS <br /> 2631(c),2662(d) <br /> 88 CA Code of Regulations 2060007-Primary and secondary containment designed and constructed to an engineering ❑OUT ❑R ❑COS <br /> 2631(b&d),2666(b&e) specification. <br /> 89 CA Health and Safety 2060008-Enhanced leak detection testing performed before the tank is placed in use ❑OUT ❑R ❑COS <br /> Code 25290.10) <br /> 90 CA Code of Regulations 2060029-SW piping has been upgraded to continuously monitored DW piping when replacement ❑OUT ❑R ❑COS <br /> 2666(b)(2) or repair needed <br /> 91 CA Health and Safety 2010-Administration/Documentation-General ❑OUT ❑R ❑COS <br /> Code 25291(e) <br /> 92 2015-Administrative/Documentation-General Local Ordinance ❑OUT ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 7 CA Code of Regulations 2715(a)(1)(B), 2715(a)(3)2010003-Owner/Operator submitted DO form and/or informed the <br /> CUPA of any change(s)within 30 days(TCR 10). <br /> OBSERVATION: The"Designated Underground Storage Tank Operator Identification Form" was not observed on <br /> latest CERS submittal. <br /> REGULATION GUIDANCE:The owner or operator shall submit a"Designated Underground Storage Tank Operator <br /> Identification Form". <br /> CORRECTIVE ACTION: This was corrected on-site via CERS. <br /> This is (Minor)Violation. <br /> 49 CA Health and Safety Code 25290.1, 25290.2, 25291 2030047-Secondary containment maintained tight and has <br /> been confirmed by testing. <br /> OBSERVATION:About a cup of brine was found in UDC 3/4 indicating a leak in the secondary containment. <br /> REGULATION GUIDANCE: Secondary containment shall be impervious to the liquid and vapor of the substance <br /> contained and constructed to prevent structural weakening as a result of contact with any hazardous substances <br /> released from the primary containment. <br /> CORRECTIVE ACTION: Immediately contact a properly licensed,trained, and certified contractor to make repairs to <br /> the UST system under permit and inspection of the EHD. <br /> This is a repeat violation (Class 2) Violation. <br /> 56 CA Code of Regulations 2716(a-e)2030013-DO inspections completed at least every 30 days and meet all <br /> requirements(TCR 12). <br /> OBSERVATION:The designated operator failed to document all the alarms from the attached alarm history on the <br /> designated operator inspection reports and failed to check that they were responded to appropriately. The missing <br /> alarms include: <br /> 4/30 DO Report <br /> -4/18, L15 91 turbine brine piping sump fuel alarm <br /> 5/29 DO Report <br /> -5/15, L4 Vent brine piping sump fuel alarm <br /> FA0017819 PR0526335 SCO01 03/20/2025 <br /> EHD Rev.12/06/2021 Page 5 of 7 CP22-UST FULL OIR <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />