Laserfiche WebLink
Underground Storage Tank <br /> Monitoring System Certification Farm <br /> T. LINE LEAK DETECTOR TESTING <br /> ❑Check this box if Iin leak detectors ARE NOT installed. (Do not complete this section.) <br /> Simulated release rate verified. (Check all that apply.) Yes No NA <br /> x3 GPH 00.1 GPH❑ .2 GPH <br /> Has the testing apparatus been properly calibrated? x ❑ ❑ <br /> For emergency gene ator tank systems, does the LLD create an audible and visual alarm ❑ ❑ x <br /> when a leak is detected? <br /> For mechanical LLDs does the LLD restrict the flow through the pipe when a release is x ❑ ❑ <br /> detected? <br /> For electronic LLDs, c oes the turbine automatically shut off when a release is detected? ❑ ❑ x <br /> For electronic LLDs, c oes the turbine automatically shut off if any portion of the monitoring ❑ El x <br /> system is disabled or disconnected? <br /> For electronic LLDs, oes the turbine automatically shut off if any portion of the monitoring ❑ ❑ x <br /> system malfunctions pr fails a tightness test? <br /> For electronic LLDs, have all accessible wiring connections been visually inspected for 11 El x <br /> kinks and breaks? <br /> Were all items on the equipment manufacturer's maintenance checklist completed? x ❑ ❑ <br /> Were all LLDs confirmed operational within regulatory requirements? x ❑ <br /> LLD 1D LLD Model Lines Monitored Pass Fail <br /> T1 VMI99 D2000 87 x ❑ <br /> T2 VMI99 1)2000 DIESEL x ❑ <br /> T3 FE ST -MLD 91 x ❑ <br /> ❑ ❑ <br /> ❑ 0 <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> ❑ ❑ <br /> Describe all answers marked "No"or "Fail"and proposed remedy in Section 9. <br /> List all monitoring equipment either replaced or repaired in Section 9 <br /> Page 4 of 6 <br />