Laserfiche WebLink
Underground Storage Tank <br /> Secondary Containment Testing Report Form <br /> 8. SUMP/UDC TEST <br /> Test Method Developed by ❑ Manufacturer ❑ Industry Standard ❑ Professional Engineer <br /> Test Type ❑ Pressure ❑ Vacuum ❑ Hydrostatic <br /> Test Equipment Used:Proteus OEL_8000111 Ct-D <br /> Sump/UDC ID 87-1 STP 87-2 STP 91 STP <br /> Sump Manufacturer Xerxes Xerxes Xerxes <br /> Sump Depth (inches) 41 42 39 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration 11 10 9 <br /> (inches) <br /> Test Start Time 10:16 10:16 10:16 <br /> Initial Reading 9.249 11.669 10.432 <br /> Test End Time 10:31 10:31 10:31 <br /> Final Reading 9.249 11.669 10.432 <br /> Change in Reading 0.000 0.000 0.000 <br /> Pass/Fail Criteria +-0.002 +-0.002 +-0.002 <br /> Tightness Test Results 0 Pass ❑ Fail 0 Pass ❑ Fail 0 Pass ❑ Fail ❑ Pass ❑ Fail <br /> Sump/UDC ID UDC 1-2 UDC 3-4 <br /> Sump Manufacturer Bravo Bravo <br /> Sump Depth (inches) 9 9 <br /> Sump Bottom to Top of <br /> Highest Pipe Penetration Bottom Bottom <br /> (inches) <br /> Test Start Time 11:29 11:29 <br /> Initial Reading 2.209 5.826 <br /> Test End Time 11:44 11:44 <br /> Final Reading 2.209 5.826 <br /> Change in Reading 0.000 0.000 <br /> Pass/Fail Criteria +-0.002 +-0.002 <br /> Tightness Test Results 0 Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Additional copies of this page may be attached. <br /> All tests marked "Fail'and any repairs made before or during the tightness test must be described in <br /> the COMMENTS section. <br /> Page 3 of 5 <br />