Laserfiche WebLink
General Notes - PLUMBING jmwelisd _ <br /> sign <br /> 1. ALL WORK SHALL CONFORM TO THE UNIFORM PLUMBING CODE, LOCAL CODES, INCLUDING 713 Washington street <br /> INSTALLATION OF ALL REQUIRED CLEANOUTS kerrville,texas 78028 <br /> 2. VERIFY SIZE, DEPTH, LOCATION AND ADEQUACY OF ALL UTILITIES, INCLUDING METER LOCATIONS AND "0' ' <br /> 95.9770 <br /> SEWER INVERTS. Sacramento,ca.916.980.9165 <br /> 3. BEFORE STARTING WORK ALL PIPING IN FINISHED AREAS SHALL BE CONCEALED WHERE POSSIBLE, AND jmwellsdesign@gmail.com/ <br /> EXPOSED PIPING SHALL BE RUN AS HIGH AS POSSIBLE AND TIGHT TO WALLS. jackmwells@outlook.com <br /> COPY RIGHT 2 0 24 <br /> 4. ALL LINES TO BE AWAY FROM BEARING FOOTINGS,OR AS DIRECTED BY STRUCTURAL ENGINEER. NOT PUBLISHED.ALL RIGHTS RESERVED BY DESIGNER. DRAWINGS <br /> AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE AND SHALL <br /> REMAIN THE PROPERTY OF THE DESIGNER.THEY SHALL NOT BE USED <br /> 5. INSTALL BACK FLOW PROTECTION DEVICES AS REQUIRED BY LOCAL CODE. ON OTHER PROJECTS OR EXTENSION$TO THIS PROJECT EXCEPT BY <br /> AGREEMENT IN WRITING AND WITH APPROPRIATE COMPENSATION TO <br /> THE DESIGNER.CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND <br /> OT <br /> 6. INSTALL PRESSURE REDUCING VALVE(S)WITH SHUT-OFF WHERE CITY PRESSURE EXCEEDS 80 PSI. CORRELATION DIMENSIONS AT THECONSTJOB RUCTION <br /> THE DESIGNER ETL DS, <br /> BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, <br /> TECHNIQUES, SEQUENCES OR FOR SAFETY PRECAUTIONS AND <br /> PROGRAMS IN CONNECTION WITH THE PROJECT. <br /> 7. ALL APPLIANCE AND PLUMBING VENTS SHALL BE AT LEAST TEN (10) FEET IN HORIZONTAL DIRECTION OR <br /> THREE(3) FEET ABOVE THE OUTSIDE AIR INTAKES FOR HVAC UNITS. 3RAW110"WIME&W <br /> 8• SEWER TO BE RUN AT 1/4"SLOPE, UPC (2019 CPC) SEC 718.1 LARGER MAY BE LAID AT A SLOPE OF NOT Company, LLC <br /> Daryl LESS THAN 1%WHEN FIRST APPROVED BY THE BUILDING DEPARTMENT. y <br /> 1 Jordan,P.E. <br /> 9. ALL REQUIRED CLEANOUTS SHALL BE INSTALLED AS PER UPC (2019 CPC.)SEC 707 AND 719. CLEANOUTS PO Box 467 <br /> SHALL BE PLACED INSIDE THE BUILDING NEAR THE CONNECTION BETWEEN THE BUILDING DRAIN AND THE Mount Hermon,CA 95941 <br /> BUILDING SEWER OR INSTALLED OUTSIDE THE BUILDING AT THE LOWER END OF THE BUILDING DRAIN AND (209) 485-8620 <br /> EXTENDED TO GRADE. <br /> �pF ESSIO <br /> 01 10. ALL EXTERIOR HOSE BIBS SHALL BE PROVIDE WITH NON REMOVABLE BACK FLOW PREVENTION DEVICES. �OOP��� X019 �F •�' <br /> -1116, 11. GAS PIPING SHALL NOT INSTALLED IN OR ON THE GROUND UNDER THE BUILDING.CPC SEC 1211.3 J <br /> A4.0 12. PROVIDE BONDING FROM COLD TO HOT WATER PIPING TO COMPLY WITH NEC ART.250-104 <br /> * • �` o <br /> 13. WATER CLOSETS SHALL BE TYPE WHICH USES 1.25 GALLONS PER FLUSH AND URINALS SHALL BE NOT MORE <br /> THAN 1.25 GALLON PER FLUSH. SEC 1921.3(8)STATE HEALTH AND SAFETY CODE. CIV1� <br /> ��� FOF CA��Ep� <br /> 14. PROVIDE AN ADEQUATE AMOUNT OF HOT WATER, 120 DEGREES F MAX,AT LAVS.,IN ADDITION TO COLD <br /> I i <br /> WATER. <br /> 15. ALL PLUMBING FIXTURES AND PIPING ARE TO BE LISTED BY AN APPROVED LISTING AND TESTING AGENCY date of issue/revisions: <br /> AND PROPERLY LABELED. CPC SEC 301.1.1 <br /> 16. MATERIALS: no. date description <br /> I i <br /> I i <br /> I i <br /> A. ALL DRAINAGE PIPING AND FITTINGS SHALL BE CAST-IRON, GALVANIZED STEEL, GALVANIZED <br /> I i <br /> WROUGHT IRON, LEAD, COPPER, BRASS OR OTHER APPROVED MATERIALS HAVING A SMOOTH <br /> AND UNIFORM BORE. (NO PLASTIC VENTING ALLOWED).CPC 701.1 <br /> B. ALL DRAINAGE FITTINGS SHALL BE COMPATIBLE WITH TYPE OF PIPE USED HAVING A INTERIOR <br /> it WATERWAY SMOOTH AND OF THE SAME DIAMETER AS THE PIPING SERVED. CPC 701.2 DRAINAGE <br /> AND VENTING SYSTEMS SHALL BE TESTED WITH A 10 FOOT HEAD OF WATER. <br /> j C. NO FITTING, FIXTURE AND PIPING CONNECTION, DEVICE OR METHOD OF INSTALLATION WHICH <br /> OBSTRUCTS OR RETARDS THE NORMAL FLOW OF WATER, SEWAGE OF AIR IN A DRAINAGE OR <br /> VENTING SYSTEM SHALL BE USED. <br /> D. NO GALVANIZED WROUGHT IRON OR GALVANIZED STEEL PIPE SHALL BE USED UNDERGROUND AND <br /> 1 SHALL BE KEPT AT LEAST 6 INCHES ABOVE GROUND. CPC 701.1.1 <br /> E. COPPER TUBE FOR UNDERGROUND DRAINAGE AND VENT PIPING SHALL HAVE A WEIGHT OF NOT <br /> I <br /> LESS THAN THAT OF COPPER DRAINAGE TUBE TYPE DWV. CPC 701.1.4.THIS MEANS COPPER TUBING <br /> TYPES K,L AND M WOULD BE ACCEPTABLE. <br /> F. COPPER TUBE FOR ABOVE GROUND DRAINAGE AND VENT PIPING SHALL HAVE WEIGHT OF NOT <br /> LESS THAN THAT OF COPPER DRAINAGE TUBE TYPE DWV CPC 701.1.4 <br /> G. ALL WATER PIPING AND FITTINGS SHALL BE OF BRASS, COPPER, GALVANIZED MALLEABLE IRON, <br /> GALVANIZED STEEL OR OTHER APPROVED MATERIALS. CPC 604.4 <br /> H. COPPER TUBE FOR ABOVE OR UNDERGROUND WATER PIPING SHALL HAVE A WEIGHT OF NOT LESS <br /> THAN TYPE 1". CPC 604.0 EXCEPTION: TYPE"M" MAY BE USED FOR WATER PIPING WHEN <br /> INSTALLED ABOVE GROUND IN, OR ON, A BUILDING OR UNDERGROUND OUTSIDE OF BUILDINGS. <br /> CPC 604.2 <br /> I j 1 j I• CAST IRON FITTINGS UP TO 2 INCH IN SIZE, WHEN USED IN CONNECTION WITH POTABLE WATER <br /> PIPING SHALL BE GALVANIZED. CPC 604.1 AND 601.5 <br /> = J. ALL MALLEABLE IRON WATER FITTINGS SHALL BE GALVANIZED. <br /> I I K. WATER LINES SHALL NOT BE EMBEDDED IN CONCRETE. CPC 313.1 O <br /> -- - L. WRAP WATER PIPES PASSING THROUGH CONCRETE. CPC 313.1 <br /> M. WATER PIPING SYSTEM TESTING: 50 PSI OF AIR PRESSURE AND WITHSTAND TEST WITHOUT LEAKING A/ <br /> �r FOR AT LEAST 15 MINUTES. CPC 609.4 �j� <br /> I WATER SUPPLY FIXTURE UNITS: rO <br /> I MOP SINK 1 3.0 <br /> o <br /> KITCHEN SINK 1 1.5 O <br /> I SHOWER 1 2.0 }i <br /> j CLOTHES WASHER 1 4.0 L <br /> ------ ---- - DRINKING FOUNTAIN 1 0.5 <br /> HOSE BIBB 1 2.5 <br /> LAV SINKS 4 4.0 }� <br /> I I LAUNDRY SINK 1 1.5 <br /> I <br /> WATER CLOSETS 4 10.0 <br /> 02 - SHAMPOO SINKS 3 3.0 <br /> i <br /> A4.0 I i TOTAL 32.0 E � <br /> i <br /> WATER PRESSURE 40 TO 60 PSI <br /> 80'WATER RUN AT 32.0 FIXTURE UNITS O O <br /> }♦ DC <br /> METER AT 1 Yd'WATER SERVICE <br /> 1 Ya"RP DEVICE ° <br /> O � •� <br /> I oc J ° <br /> i � <br /> ' --_ • 3 v <br /> ENERGY NOTES to 0 r <br /> _ _ <br /> 1. DOMESTIC HOT WATER HEATERS SHALL BE CERTIFIED AND LISTED BY THE CALIFORNIA ENERGY W Y <br /> 1 COMMISSION. • U <br /> EXCEPTION: NON-STORAGE TYPE ELECTRIC WATER HEATERS. ° <br /> 2. ALL HOT WATER PIPING SHALL BE INSULATED IN ACCORDANCE WITH THE TABLS BELOW. �� M N <br /> 3. SERVICE WATER HEATING SYSTEM SHALL BE EQUIPPED WITH AUTOMATIC TEMPERATURE CONTROLS <br /> I 1 OV INSTANT HOT CAPABLE OF ADJUSTMENT FROM THE LOWEST TO THE HIGHEST ACCEPTABLE TEMPERATURE SETTING FOR Q Q <br /> 70 1 THE INTENDED USE, AS LISTED IN TABLE 3, CHAPTER 54 OF THE ASHRAE HANDBOOK, HVAC SYSTEMS <br /> WATER HEATER APPLICATION VOLUME. <br /> G 4. LAVATORY FAUCETS AND SINKS (NOT INCLUDING SERVICE SINK FAUCET) SHALL MEET THE FLOW <br /> tZ REQUIREMENTS OUTLINED IN THE APPLIANCE EFFICIENCY STANDARDS. � ,y <br /> 1 5. LAVATORIES IN PUBLIC RESTROOMS SHALL HAVE HOT WATER CONTROLS THAT COMPLY WITH THE <br /> FOLLOWING REQUIREMENTS: <br /> O 1) MAXIMUM FLOW RATE(GPM):0.5;OR 0.75(WITH A DEVICE THAT LIMITS THE <br /> oa SS C�r.O. TIE IN TO EXISTING <br /> - - - - - PERIOD OF WATER DISCHARGE,I.E.FOOT SWITCH OR OCCUPANCY SENSOR. <br /> II WATER SUPPLY 2) FLOW RATE(GAL/CYCLE) FOR SELF-CLOSING VALVES: 0.25 0 <br /> 4 CNS CIRCULATING;OR 0.5 NON-CIRCULATING;OR 0.75(WITH A DEVICE THAT LIMITS THE PERIOD <br /> 3 OF WATER DISCHARGE,I.E.FOOT SWITCH OR OCCUPANCY SENSOR. <br /> 3) MAXIMUM OUTLET TEMERATURE: 1 10°F. <br /> (�/I HOT WATER INSULATION REQUIREMENT <br /> O N 1 W DOMESTIC HOT WATER SUPPLY AND RETURN PIPING SHALL BE INSULATED <br /> THICKNESS TO COMPLY WITH TABLE BELOW: <br /> z I (�/ KLU <br /> o O W WATER RUNOUTS 1"OR 1 1/4 TO 2 1/2 TO 5 AND <br /> z U Z TEMP UP TO 2" LESS 2 4 6 .._j <br /> CO � <br /> cn (K ii INSULATION THICKNESS <br /> ry z _ 9, 44p U <br /> ry <br /> X I 105-200 1/2" 1" 1" O 1 1/2" 1 1/2" l <br /> _ I--1 <br /> 0 is) W z THE THICKNESS OF INSULATION LISTED IN TABLE ABOVE IS BASED ON MATERIAL w <br /> - 0 HAVING THERMAL CONDUCTIVITY RANGE OF 0.24- 0.28 IN BTU-INCH PER HOUR PER SQUARE <br /> FLAN <br /> NORTH FOOT DEGREE F. I= O O Q� U o 0 <br /> LJ_i ADJUSTMENTS ARE REQUIRED IN INSULATION MATERIAL OUTSIDE THIS RANGE. cv <br /> W04 'saJ � �7 � r- <br /> CD W05 � Z � o00 <br /> Ln HOT WATER OPERATING TEMPERATURE SHALL NOT EXCEED 110 DEGREES F. a 004. ° W <br /> W O Qcnrn <br /> AFFROXIMATE 0 ca o, rn <br /> S <br /> II <br /> Ln NORTH *RUNOUTS TO INDIVIDUAL FIXTURE NOT OVER 2"IN SIZE OR 12 FEET IN LENGTH. ago 0 CD <br /> Electrical Schematic <br /> sh eet contents <br /> D <br /> 1/4"= 1'-0 Plumbing <br /> O <br /> i= Schematic <br /> U <br /> z <br /> O project no <br /> U 9162024 <br /> THESE DRAWINGS ARE FOR THE drawn by <br /> J EXPRESS USE OF checked by 1m <br /> c i JMW/DJ <br /> Z E.J. PLUMBING E.J. PLUMBING project architect <br /> 3 STATEMENT OF RESPONSIBILITY 2310 Fay Drive <br /> E.J.PLUMBING SHALL CHECK AND VERIFY ALL ASPECTS OF DESIGN/ENGINEERING,AND SHALL ENSURE THAT ALL WORK CONFORMS Atwater, Ca. 95301 <br /> n 3 TO CURRENT CODES AND INDUSTRY STANDARDS. E.J.PLUMBING SHALL BE RESPONSIBLE FOR ALL ENGINEERING AND DRAWINGS 209-589-5742 plot date 06242024 <br /> AND SHALL PLACE HIS OR HER NAME,SIGNATURE, LICENSE NUMBER AND DATE ON THE CONSTRUCTION DRAWINGS SO AS TO sheet number <br /> } O INDICATE SUCH RESPONSIBILITY (PRIOR TO START OF WORK) . ANY MODIFICATIONS To THE DRAWINGS,CALCULATIONS,OR FIELD <br /> CONDITIONS SHALL BE E.J.PLUMBING RESPONSIBILITY. BY BEGINNING WORK,E.J.PLUMBING AGREES TO THE ABOVE STATEMENT OF <br /> a> 0 RESPONSIBILITY. ALL OTHER USE BY WRITTEN MEP DISCLAIMER: <br /> N PERMISSION ONLY OF <br /> JMWELLS DESIGN is not a engineering firm. The mep design/system and and/or elements,either noted or implied,are foreg neral <br /> Uuideline purposes only. These drawings have not been reviewed by a licensed Engineer, (unless an official stamp of an licensedmepi <br /> 0 o EJ E.J. PLUMBING engineer appears on these drawings). it is the responsibility of the owner and General Contractor to obtain the services of a licensed • <br /> Q = 683610 Engineer to review these drawings prior to construction. By accepting these drawings,JMWELLS Designer/Jack Wells is released from <br /> a: all liability for any MEP defects and/or failures. <br /> PRINTED NAME LICENSE NUMBER DATE SIGNATURE Of <br /> 0 - - <br />