Laserfiche WebLink
General Notes - Reflected Ceiling Plan jmw_ _ <br /> sign <br /> 1. SUSPEND CEILINGS IN STRUCTURES SHALL BE DESIGNED AND INSTALLED IN 713 Washingtonstreet <br /> ACCORDANCE WITH ASTM C535,ASTM C635,AND THE CISCA FOR SEISMIC ZONES 3-4. kerrville,texas 78028 <br /> 2. A HEAVY TYPE"T-BAR"CEILING SYSTEM SHALL BE USED. 830.890.8808/830.895.9770 <br /> Sacramento,ca.916.980.9165 <br /> 3. THE WIDTH OF PERIMETER CLOSURE SHALL BE 2 INCHES MINIMUM IN WIDTH. jmwellsdesign@gmail.com/ <br /> jackmwells@outlook.com <br /> 4. IN EACH ORTHOGONAL HORIZONTAL DIRECTION, ONE END OF CEILING GRID SHALL BE COPY RIGHT 2 0 24 <br /> ATTACHED TO THE CLOSURE ANGLE. THE OTHER END IN EACH HORIZONTAL DIRECTION NOT PUBLISHED.ALL RIGHTS RESERVED BY DESIGNER. DRAWINGS <br /> AND SPECIFICATIONS AS INSTRUMENTS OF SERVICE ARE AND SHALL <br /> SHALL HAVE A MINIMUM 0.75 INCH CLEARANCE FROM THE WALL END AND SHALL REST UPON ON OT ER PROJECTS ERTY <br /> EXEDESIGNER.THEYSHJECTEALL EXCEPT BY ON OTHER PROJECTS OR EXTENSIONS TO THIS PROJECT EXCEPT BV <br /> THE <br /> IN WRITING AND WITH APPROPRIATE COMPENSATION TO <br /> AND BE FREE TO SLIDE ON THE CLOSURE ANGLE. THE DESIGNER.CONTRACTOR IS RESPONSIBLE FOR CONFIRMING AND <br /> CORRELATION DIMENSIONS AT THE JOB SITE,THE DESIGNER WILL NOT <br /> BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS, <br /> 5. FOR CEILING AREA EXCEEDING 1,000 SQUARE FEET, HORIZONTAL RESTRAINS OF THE TECHNIQUES, SEQUENCES OR FOR SAFETY PRECAUTIONS AND <br /> PROGRAMS IN CONNECTION WITH THE PROJECT. <br /> CEILING TO THE STRUCTURE SYSTEM SHALL BE PROVIDED. THE TRIBUTARY AREAS OF THE <br /> HORIZONTAL RESTRAINS SHALL BE APPROXIMATELY EQUAL. 3RgO"WIM8►r <br /> 6. FOR CEILING AREAS EXCEEDING 2,500 SQUARE FEET, A SEISMIC SEPARATION JOINT OF Company, LLC <br /> FULL HEIGHT PARTITION THE BREAKS THE CEILING SYSTEM INTO AREAS NOT EXCEEDING 2,500 Daryryl Jordan,P.E. <br /> S.F. SHALL BE PROVIDED UNLESS STRUCTURAL ANALYSIS ARE PREFORMED ON THE CEILING e Box 467 <br /> H <br /> BRACING SYSTEM FOR THE PRESCRIBED SEISMIC FORCES THAT DEMONSTRATES CEILING Mount Hermon,CA 95941 <br /> (209) 485-8620 <br /> SYSTEM PENETRATIONS AND CLOSURE ANGLES PROVIDE SUFFICIENT CLEARANCE TO <br /> ACCOMMODATE THE ANTICIPATED LATERAL DISPLACEMENT. EESSI <br /> 0 <br /> 6.1 THE SMALLER, BROKEN-UP AREAS SHALL COMPLY WITH ITEMS 5, 4 AND 5 <br /> 'l <br /> �►� <br /> A4.0 7. SPRINKLER HEADS AND OTHER SIMILAR TYPE OF PENETRATIONS THAT DO NOT BEHAVE <br /> INTEGRALLY WITH THIS CEILING SYSTEM IN THE LATERAL DIRECTION, SHALL HAVE A 2 INCH <br /> OVER SIZE RING, SLEEVE OR ADAPTOR THRU THE CEILING TILE WHICH SHALL ALLOW FOR THE CIV1l_ <br /> 1 MOVEMENT OF AT LEAST 1 INCH IN ALL DIRECTIONS. 4'0 CA %,I <br /> I I � <br /> I i <br /> I i <br /> 7.1 EXCEPT WHERE RIGID BRACES ARE USED TO LIMIT LATERAL DEFLECTIONS. <br /> I i <br /> 7.2 AS AN ALTERNATIVE SWING JOINT ACCOMMODATING AN INCH OF CEILING date of issue/revisions: <br /> MOVEMENT IN ALL DIRECTIONS MAY BE USED AT THE SPRINKLER HEAD EXTENSION. <br /> ------------- ------------ -------------------------7 no. date description <br /> I � 8 CHANGES IN PLAN ELEVATIONS SHALL BE PROVIDED WITH POSITIVE BRACING. <br /> I I i <br /> photocell 1 1 9 CABLE TRAYS AND ELECTRICAL CONDUITS SHALL BE SUPPORTED INDEPENDENTLY OF <br /> THE CEILING. <br /> � I I <br /> 10 A STRUT IS TO BE ATTACHED TO THE SUSPENSION SYSTEM AND TO THE STRUCTURE ABOVE <br /> AT EACH BRACE. <br /> I `,, �, 1 1 ATTACHMENT OF THE BRACING WIRES TO THE MAIN BEAM AND THE STRUCTURE SHOULD <br /> I I <br /> SUPPORT THE GREATER 200# OR THE ACTUAL DESIGN LOAD WITH A SAFETY FACTOR OF 2. <br /> 112 IF PARTITIONS ARE ATTACHED TO THE SUSPENSION SYSTEM, THEY MUST BE LATERALLY <br /> P <br /> � ) BRACED TO THE BUILDING STRUCTURE. <br /> 13 LIGHT FIXTURES: <br /> / I 13.1 PENDENT MOUNTED FIXTURES MUST BE SUPPORTED FROM THE STRUCTURE. THEY MAY <br /> NOT USE THE CEILING SUSPENSION SYSTEM FOR SUPPORT. <br /> 13.2 MUST BE POSITIVELY ATTACHED TO WITHSTAND 100%OF THE FIXTURE WEIGHT. <br /> _J1 <br /> I — <br /> I 1 % 13.3 THERE MUST BE TWO 12-GA. WIRES ATTACHED AT DIAG CORNERS. IF THE FIXTURE IS 58# <br /> iI i OR LESS. IF THE FIXTURE IS MORE THAN 58#, FIXTURE MUST BE INDEPENDENTLY SUPPORTED O <br /> 1 <br /> P FROM THE BUILDING STRUCTURE. <br /> General Notes - ELECTRICAL <br /> C <br /> LIGHTING _� <br /> I <br /> ii I PROVIDE UNSWITCHED HOT TO ALL EMERGENCY AND EXIT LIGHTING }_i <br /> ' - - ----- - ---- --'- i- LIGHTING CONTROLS PROVIDED BY TIME CLOCK/ LIGHTING. INTERIOR LIGHTING SHALL BE CONTROLLED <br /> ` BY SWITCH,EXCLUDING EMERGENCY AND NIGHT LIGHTING. <br /> ALL FLUORESCENT FIXTURES IN KITCHEN/ SERVING AREAS SHALL BE PROVIDED WITH GASKETED LENS OR <br /> SHATTER PROOF LAMPS. <br /> 02 � _ _ <br /> POWER: <br /> �k ' <br /> A4.0 I / ALL NON-EMERGENCY INTERIOR LIGHTING SHALL BE CONTROLLED BY LOCAL SWITCHES, ALL EXTERIOR <br /> i LIGHTING AND SIGNAGE SHALL BE CIRCUITED THROUGH AND CONTROLLED BY CPI LIGHTING MANGER. <br /> e� <br /> AIR HANDLER PROVIDE HACR TYPE CIRCUIT BREAKER FOR HVAC EQUIPMENT. C a••r CC <br /> /I Mitsubishi Electric O <br /> r I SUZ-KA30NAHZ split system ALL SHUNT TRIP BREAKERS OR INTERLOCK ST W/FIRE SUPPRESSION SYSTEM TO TRIP BREAKER WHEN O C ca <br /> 208/230v 1 ph,60Hz SUPPRESSION IS ACTIVATED. L 16- <br /> 0 O <br /> 1 , I125 R�hGTRGAv SU�PANv ANY KITCHEN EQUIPMENT NOT IDENTIFIED IN THE KETCH SCHEDULE ABOVE IS EXPECTED TO NOT HAVE ANY <br /> I DIVISION 16 INSTALLATION REQUIREMENTS. CONFIRM ALL REQUIREMENTS FOR ALL EQUIPMENT ON THE ` ' tv <br /> P Min ARCHITECTURAL DRAWINGS WITH DESIGNER AND KITCHEN EQUIPMENT CONTRACTOR PRIOR TO THE ' V <br /> Min\ INSTALLATION OF EQUIPMENT AND/OR DIV. 16 WORK. A <br /> C <br /> P f PROVIDE OVER CURRENT PROTECTION AND BRANCH CIRCUITS PER UL LISTED REQUIREMENTS FOR ALL = W �0 <br /> ` I EQUIPMENT SERVED. REFER TO MANUFACTURER DATA AND EQUIPMENT CUT SHEETS FOR ROUGH-IN Y <br /> LOCATIONS OF ELECTRICAL CONNECTIONS AND INTERCONNECTIONS FOR ALL EQUIPMENT. COORDINATE • 0 <br /> IEXACT NAME PLATE DATA OF EQUIPMENT BEING INSTALLED. = 01 4+ <br /> I \ I i 4� <br /> GONDI=NSER • M N <br /> % � II COORDINATE EXACT LOCATIONS OF EQUIPMENT, RECEPTACLES, AND DEVICE CONNECTIONS WITH <br /> 3 \ IMitsubishi Electric ARCHITECTURAL PLANS AND ELEVATIONS PRIOR TO INSTALLATION. Q Q <br /> photo cell PEAD-A30AA split system <br /> 70 �{ 208/230v 1 ph,60Hz ELECTRICAL CONTRACTOR SHALL VERIFY POWER AND PHONE SERVICES AT SITE, SERVICES TO CONFORM <br /> \� TO UTILITY REQUIREMENTS. ELECTRICAL CONTRACTOR SHALL ARRANGE FOR SERVICE INSTALLATION PER <br /> \ 2019 CALIFORNIA ELECTRICAL CODE <br /> N % 10vINSTANT I \ <br /> \ FG40T WATER HTR I" ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2019 CALIFORNIA ELECTRICAL CODE. r <br /> O CALIFORNIA TITLE 24,PART 3 AND ALL APPLICABLE LOCAL CODES. <br /> ALL ELECTRICAL MATERIALS SHALL NEW AND LISTED WITH THE UNDERWRITERS LABORATORIES, INC., SHALL <br /> 3 \hoto cell I MEET THEIR REQUIREMENTS AND SHALL BEAR THEIR LABEL WHEREVER STANDARDS HAVE BEEN ESTABLISHED <br /> / AND LABEL SERVICE IS REGULARLY FURNISHED BY THAT AGENCY. <br /> ELECTRICAL DRAWINGS ARE ESSENTIALLY DIAGRAMMATIC AND ALTHOUGH THE SITE AND EQUIPMENT ARE <br /> O j SHOWN TO SCALE WHEREVER POSSIBLE, CONTRACTOR SHALL MAKE USE OF ALL DATA IN THE CONTRACT <br /> O N �___/� I DOCUMENTS AND VERIFY THIS INFORMATION AT THE JOB SITE. CONTRACTOR SHALL BE RESPONSIBLE FOR <br /> z I LAYING OUT AND INSTALLING HIS WORK TO AVOID INTERFERENCE WITH OTHER TRADES. <br /> 0 ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL PLANS FOR EXACT LOCATION OF ALL Q <br /> z U HVAC UNITS AND DEVICES. FURNISH AND INSTALL ALL CONDUITS AND LINE VOLTAGE , LOW VOTAGE <br /> O WIRING BY OTHERS,TO HVAC EQUIPMENT AND ASSOCIATED CONTROLS AND DEVICES AS SHOWN ON THE <br /> CO v ELECTRICAL AND MECHANICAL PLANS UNLESS OTHERWISE NOTED. Q� w <br /> ry ALL LUMINARIES AND BALLAST SHALL BE CERTIFIED BY THE MANUFACTURER TO THE CALIFORNIA ENERGY W O U <br /> O COMMISSION. ALL EXTERIOR AND CORRIDOR INCANDESCENT LAMPS TO BE LONG LIFE, GE SERIES 99 OR 0 c <br /> EQUAL. ALL FLOURECENT FIXTURES TO BE LAMPED WITH T12,T8 LAMPS,OR APPROVED EQUAL,AND HAVE P-J W U R. i <br /> O ENERGY SAVINGS ELECTRONIC BALLAST OR APPROVED EQUAL UNLESS OTHERWISE SHOWN. ALL HID <br /> PLAN LIGHTS FIXTURES SHALL HAVE HIGH POWER FACTOR BALLAST. z <br /> NORTH I O U o 00 <br /> I ALL EXIT SIGNS SHALL BE INSTALLED IN ACCORDANCE WITH CBD SECTION 1011. LOW LEVEL EXIT SIGNS <br /> w I <br /> WHERE APPLICABLE SHALL BE INSTALLED ON THE WALL SUCH THAT THE BOTTOM EDGE OF THE SIGN IS NOT ria � � � � ,� `D � <br /> LESS THAN 6"AND NOT MORE THAN 8"ABOVE THE FINISHED FLOOR. W05 w -44 R o 06 <br /> cy` APPROXI MATE m <br /> N NORTH WORK SHOWN ON THE DRAWINGS TO BE INSTALLED UNDERGROUND SHALL BE INSTALLED PER THE I' 0 O 0 0 <br /> • CALIFORNIA ELECTRICAL CODE. BACKFILL IN 6" MOISTURE CONDITIONED LIFTS, COMPACTED UTILIZING N N N <br /> Electrical S c h e m a t l c APPROVED COMPACTION EQUIPMENT. COMPACTION/ DENSITY SHALL NOT BE LESS THAN ADJACENT <br /> 0 UNDISTURBED EARTH. sheet contents <br /> 1/4"= 1'-0 RECEPTACLE/OUTLET HEIGHT OF 15"TO BOTTOM MINIMUM. LIGHT SWITCH HEIGHT 48"TO TOP MAXIMUM Electrical <br /> Z PER CODE REQUIREMENTS. ELECTRICAL CONTRACTOR SHALL VERIFY ALL OUTLET HEIGHTS AT COUNTERS <br /> O ETC.WITH THE OWNER IN FIELD PRIOR TO ROUGH IN. ELECTRICAL CONTRACTOR SHALL VERIFY COLOR OF Schematic <br /> ALL SWITCH,OUTLET,ETC.COVER PLATES WITH OWNER PRIOR TO INSTALLATION. <br /> U <br /> UNLESS OTHERWISE NOTED OR REQUIRED BY CODE, CONDUCTORS SHALL BE COPPER TYPE THWN FOR ** <br /> N OR SMALLER,AND COPPER TYPE THW FOR**OR LAGER. <br /> Z <br /> Q ACCEPTABLE CONDUITS ARE: project no <br /> U PVC CONDUIT-UNDERGROUND 9162024 <br /> THESE DRAWINGS ARE FOR THE LIQUID TIGHT STEEL FLEX-FINAL CONNECTION TO EQUIPMENT drawn by <br /> LU EXPRESS USE OF FLEXIBLE STEEL OR ALUMINUM-INDOOR FINAL CONNECTION TO EQUIPMENT OF lm <br /> LIGHTING FIXTURES checked by <br /> c GALVANIZED RIGID STEEL-THROUGHOUT JMW/DJ <br /> Z HADEN ELECTRIC HADEN ELECTRIC GALVANIZED EMT-THROUGHOUT project architect <br /> M/C A/C B/X CONCEALED IN WALLS AND CEILINGS <br /> 3 STATEMENT OF RESPONSIBILITY 3918 JUNIPER DRIVE <br /> Q DENAIR, CALIFORNIA <br /> QHADEN ELECTRIC SHALL CHECK AND VERIFY ALL ASPECTS OF DESIGN/ENGINEERING,AND SHALL ENSURE THAT ALL WORK 95316 plot date 06242024 <br /> CONFORMS TO CURRENT CODES AND INDUSTRY STANDARDS. HADEN ELECTRIC SHALL BE RESPONSIBLE FOR ALL <br /> } ENGINEERING AND DRAWINGS AND SHALL PLACE HIS OR HER NAME, SIGNATURE, LICENSE NUMBER AND DATE ON THE 209-261-0927 sheet number <br /> O CONSTRUCTION DRAWINGS SO AS TO INDICATE SUCH RESPONSIBILITY (PRIOR TO START OF WORK) . ANY MODIFICATIONS <br /> O TO THE DRAWINGS,CALCULATIONS,OR FIELD CONDITIONS SHALL BE HADEN ELECTRIC'S RESPONSIBILITY. BY BEGINNING <br /> WORK,HADEN ELECTRIC,AGREES TO THE ABOVE STATEMENT OF RESPONSIBILITY. MEP DISCLAIMER: <br /> E (� ALL OTHER USE BY WRITTEN JMWELLS DESIGN is not a engineering firm.The m�design/system and and/or elements,either noted or implied,are foreg neral <br /> o PERMISSION ONLY OF guideline purposes only. These drawings have not been reviewed by a licensed Engineer, (unless an official stamp of an licensed mep , <br /> engineer appears on these drawings). it is the responsibility of the owner and General Contractor to obtain the services of a licensed • <br /> n 984282 HADEN ELECTRIC Engineer to review these drawings prior to construction. By accepting these drawings,JMWELLS Designer/Jack Wells is released from <br /> PRINTED NAME LICENSE NUMBER DATE SIGNATURE all liability for any MEP defects and/or failures. <br /> o - of - <br />