SAN JOAQUIN <br />COUNTY <br />Environmental Health Department <br />Underground Storage Tank Program Inspection Report <br />Facility Name: <br />Facility Address: <br />TOctober <br />Date: <br />SUNWEST CHEVRON <br />12758 W KETTLEMAN LN, LODI <br />16, 2025 <br />45 <br />CA Code of Regulations <br />2030025 - LLD on DW press piping monitors hrly, detects a 3.0 gph leak, and <br />❑ OUT ❑ R ❑ COS <br />2636(f)(2) <br />restricts/shuts off flow (TCR 9d) <br />46 <br />CA Code of Regulations <br />2030053 - SW Safe Suction piping drains back into storage tank, one check valve <br />❑ OUT ❑ R ❑ COS <br />2636(a)(3), 2641(b) <br />and inspections conducted <br />47 <br />CA Health and Safety <br />2030008 - Secondary containment installed after July 1, 2003 is free of water <br />❑ OUT ❑ R ❑ COS <br />Code 25290.1(c3), <br />25290.2(c3) <br />48 <br />CA Code of Regulations <br />2030040 - Secondarily contained piping allows liquid to flow into the sump in the <br />❑ OUT ❑ R ❑ COS <br />2630(d), 2641(a) <br />event of a leak (TCR 9d) <br />49 <br />CA Health and Safety <br />2030047 - Secondary containment maintained tight and has been confirmed by <br />❑ OUT ❑ R ❑ COS <br />Code 25290.1, 25290.2, <br />testing <br />25291 <br />50 <br />CA Code of Regulations <br />2060020 - Spill buckets meet requirements, have been tested as required, and <br />❑ OUT ❑ R ❑ COS <br />2635, 2637.1, 2665, 2712 <br />records kept for 36 mths (TCR 9a) <br />51 <br />CA Health and Safety <br />2030035 - UST system is operated to prevent unauthorized release, including spills <br />❑ OUT ❑ R ❑ COS <br />Code 25292.1(a) <br />and overfills <br />52 <br />CA Code of Regulations <br />2030036 - Overfill prevention system has not been overridden and meets overfill <br />❑ OUT ❑ R ❑ COS <br />2635(c)(1) <br />requirements (TCR 9b) <br />53 <br />CA Health and Safety <br />2010007 - Submitted/maintained current Cert of Financial Responsibility/mech of <br />❑ OUT ❑ R ❑ COS <br />Code 25292.2; CCR <br />financial assurance (TCR 11) <br />2711(a)(11) <br />54 <br />CA Code of Regulations <br />2030007 - Documentation of compatibility for UST system components submitted <br />❑ OUT ❑ R ❑ COS <br />2631, 2640.1, 2665, 2711 <br />and/or maintained. <br />55 <br />CA Code of Regulations <br />2010004 - Copies of DO inspections for last 12 months maintained, 36 months for <br />■ OUT ❑ R ❑ COS <br />2716(f) <br />those after 10/1/18 (TCR 12) <br />56 <br />CA Code of Regulations <br />2030013 - DO inspections completed at least every 30 days and meet all <br />■ OUT ❑ R ❑ COS <br />2716(a -e) <br />requirements (TCR 12) <br />57 <br />CA Code of Regulations <br />2030012 - Initial and annual training provided to employees and at least one <br />❑ OUT ❑ R ❑ COS <br />2715(c) <br />trained employee is present <br />58 <br />CA Code of Regulations <br />2010015 - Copies of Facility Employee Training Certificates maintained <br />❑ OUT ❑ R ❑ COS <br />2715(c)(3), 2715(c)(4) <br />59 <br />CA Code of Regulations <br />2030001 - Records of release detection monitoring and maintenance properly <br />❑ OUT ❑ R ❑ COS <br />2712(b)(1-2) <br />maintained (TCR 9d) <br />60 <br />CA Health and Safety <br />2030020 - Unburied fuel piping visually inspected at least monthly and log kept <br />❑ OUT ❑ R ❑ COS <br />Code 25281.5(b)(3) <br />61 <br />CA Code of Regulations <br />2030049 - Monitoring conducted and written records maintained for SW <br />❑ OUT ❑ R ❑ COS <br />2643(d) <br />conventional suction system (TCR 9d) <br />62 <br />CA Health and Safety <br />2030032 - Unburied fuel piping at marinas visually inspected at least daily and log <br />❑ OUT ❑ R ❑ COS <br />Code 25281.5(b)(2) <br />kept <br />63 <br />CA Code of Regulations <br />2030057 - The facility met all corrective action requirements when SIR results failed <br />❑ OUT ❑ R ❑ COS <br />2646.1(d ) <br />64 <br />CA Code of Regulations <br />2030058 - All Statistical Inventory Reconciliation (SIR) requirements met (TCR 9d) <br />❑ OUT ❑ R ❑ COS <br />2643(b)(2), 2646.1 <br />65 <br />CA Health and Safety <br />2010012 - UST records sufficiently maintained to document compliance <br />❑ OUT ❑ R ❑ COS <br />Code 25293 <br />66 <br />CA Code of Regulations <br />2010008 - Monitoring, maintenance, repairs, linings, and upgrade records <br />❑ OUT ❑ R ❑ COS <br />2712(b)(6) <br />maintained for life of UST <br />67 <br />CA Code of Regulations <br />2030078 - Owner/Operator retained a paper or electronic copy of the permit to <br />❑ OUT ❑ R ❑ COS <br />2712(1) <br />operate at the facility <br />68 <br />CA Code of Regulations <br />2030046 - A current UST Response Plan has been submitted <br />❑ OUT ❑ R ❑ COS <br />2712(i), 2634(e) <br />69 <br />CA Code of Regulations <br />2030033 - A current UST monitoring plan has been submitted and is readily <br />❑ OUT ❑ R ❑ COS <br />2712(1) <br />accessible at the facility <br />EHD - CUPA Inspection Report IS02 Page 3 of 5 FA0023733 PRO541416 4564779 10/16/2025 <br />1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />