Ultimate Loads by Anchor System Component <br />Strap ult_load 25000lbf IDtk 48in=if <br />25000lbf IDtk 72in=if <br />25000lbf IDtk 92in=if <br />25000lbf IDtk 120in=if <br />25000lbf IDtk 138in=if <br />0 otherwise <br /> Turnbuckleult_load 6000lbf IDtk 48in=if <br />17500lbf IDtk 72in=if <br />26000lbf IDtk 92in=if <br />26000lbf IDtk 120in=if <br />26000lbf IDtk 138in=if <br />0 otherwise <br /> <br />Wire_Ropeult_load 13120lbf IDtk 48in=if <br />23000lbf IDtk 72in=if <br />23000lbf IDtk 92in=if <br />23000lbf IDtk 120in=if <br />23000lbf IDtk 138in=if <br />0 otherwise <br /> Eye_Boltult_load 26000lbf IDtk 48in=if <br />26000lbf IDtk 72in=if <br />26000lbf IDtk 92in=if <br />26000lbf IDtk 120in=if <br />26000lbf IDtk 138in=if <br />0 otherwise <br /> <br />Tank Buoyancy, Rotten Robbie No 69, <br />Manteca CA, dwg 17366-001, 10ft DWT <br />Date Printed: 9/7/2023 Page 30 of 46