SHEET NUMBER:
<br />SHEET CONTENTS:
<br />PROJECT NUMBER:PROJECT DATE:
<br />CONSULTANTS:
<br />REVISIONS:
<br />18-046 12-24-2020
<br />DEVELOPER:
<br />CONTRACTOR:
<br />PROJECT:
<br />PROFESSIONAL SEALS:
<br />1014 S. Airport Road
<br />Manteca, California
<br /> 95336
<br />1
<br />2
<br />Robinson Oil Corporation
<br />955 Martin Ave.
<br />Santa Clara, CA 95050
<br />Sacramento, CA 95827
<br />PH:(916) 455-6500 FAX:(916) 455-8100
<br />3090 Fite Circle, #104
<br />K12 Architects, Inc
<br />CONVENIENCE STORE &
<br />FUELING CANOPY
<br />MANTECA
<br />3
<br />4
<br />PLAN CHECK JAN. 12, 2023
<br />OWNER CHANGE MARCH 17, 2023
<br />PLAN CHECK AUGUST 17, 2023
<br />PLAN CHECK MARCH 29, 2024
<br />PLAN CHECK hzmt MAY 10, 2024
<br />5 PLAN CHECK hzmt MAY 31, 2024
<br />6 PLAN CHECK hzmt AUGUST 7, 2024
<br /> November 06, 2024
<br />8 PLAN CHECK hzmt OCT. 26, 2024
<br />7 PLAN CHECK hzmt SEPT. 26, 2024
<br />GENERAL FUEL SYSTEM NOTES
<br />CONTRACTOR SHALL HAVE THE FOLLOWING LICENSES AT A MINIMUM:
<br />GENERAL ENGINEERING "A"
<br />HAZARDOUS MATERIAL SUBSTANCE HANDLING
<br />CONTRACTOR SHALL HAVE AND MAINTIAN THE FOLLOWING INSURANCE:
<br />PERMITS
<br />EXCAVATE AS NECESSARY FOR THE INSTALLATION OF NEW SUMPS AND PIPING.
<br />INSTALL EQUIPMENT AS LISTED IN EQUIPMENT LIST.
<br />PIPING SYSTEMS SHALL BE TESTED AS FOLLOWS:
<br />ALL CONDUIT SHALL BE 3/4"(MIN). MIN. BURIAL DEPTH OF 24"
<br />1.
<br />2.
<br />3.
<br />4.
<br />5.
<br />A.
<br />B.
<br />6.
<br />7.
<br />8.
<br />1.
<br />2.
<br />3.
<br />4.
<br />SCOPE OF WORK
<br />1.
<br />2.
<br />3.
<br />4.
<br />5.
<br />6.
<br />7.
<br />8.
<br />12.
<br />13.
<br />14.
<br />15.
<br />A.
<br />B.
<br />C.
<br />D.
<br />A.STEEL PIPING:
<br />A.PETROLEUM PIPING TEST PROCEDURE:
<br />1.
<br />2.CONFIRM TESTING PROCEDURE WITH LOCAL AGENCIES PRIOR TO TESTING.
<br />3.PRIMARY TESTING:
<br />(1)
<br />(2)BEFORE APPLYING PRESSURE, VERIFY THE FOLLOWING HAVE BEEN COMPLETED:
<br />*VERIFY SHEAR VALVES ARE CLOSED.
<br />*VERIFY THE BALL VALVE CLOSEST TO THE TURBINE IS CLOSED.
<br />*
<br />(3)PROCEDURES TO FOLLOW WHEN APPLYING PRESSURE:
<br />*
<br />*
<br />*
<br />*
<br />*SYSTEM SHOULD BE KEPT AT 20 PSI FOR DURATION OF
<br />CONSTRUCTION AND SHALL BE CHECKED FREQUENTLY.
<br />4.SECONDARY TESTING:
<br />(1)
<br />5.VENTS, VAPOR, AND TANK RISER TESTING:
<br />(1)UPON COMPLETION OF VAPOR RECOVERY PIPING, TEST SYSTEM AS FOLLOWS:
<br />(a)
<br />6.DUE TO WEATHER CONDITIONS, PRESSURES MAY RISE OR FALL OVER A
<br />PERIOD OF TIME. PRESSURES SHALL BE MONITORED AT REGULAR INTERVALS
<br />7.VENT AND VAPOR RECOVERY PIPING WITH PHASE II RECOVERY.
<br />(1)
<br />8.UPON COMPLETION OF THE FUELING SYSTEM, THE FOLLOWING ITEMS ARE REQUIRED:
<br />(1)ST-27 TEST.
<br />(2)ST-30 TEST.
<br />(3)A over L TEST (IF REQUIRED).
<br />(4)PLACED IN SERVICE REPORT.
<br />(5)
<br />(6)ALL METERS SEALED.
<br />(7)TANK AND LINE TEST (3rd PARTY).
<br />(8)FUEL SYSTEM CHECK TEST.
<br />(9)AS BUILT DRAWINGS.
<br />(10)MONITORING SYSTEM FINAL WITH APPROPRIATE AGENCY APPROVALS.
<br />*
<br />*
<br />TO PREVENT FALSE READINGS.
<br />ALL BLACK IRON PIPING TO BE PAINTED GREY.11.
<br />INSTALL MONITORING SYSTEM WITH LIQUID SENSORS IN EACH TANK ANNULAR SPACE. INSTALL MONITOR
<br />CONTROL PANEL IN NEW BUILDING AS DIRECTED BY OWNER. INSTALL LIQUID LEVEL PROBES IN TANKS.
<br />SEE SITE ELECTRICAL PLAN FOR TANK CONDUIT CONFIGURATION. WHEN A LEAK IS DETECTED, AN
<br />AUDIO/ VISUAL ALARM WILL GO ON. LEAK DETECTION @ SUMP WILL CAUSE SUMP SHUT DOWN LEAK
<br />DETECTION @ DISPENSER SUMP WILL CAUSE DISPENSER SHUT DOWN. AUDIO/ VISUAL ALARM WILL GO
<br />OFF IF ANNULAR SPACE MONITOR OR SUMP. MONITORING SYSTEM SHALL BE INSTALLED TO PERMIT
<br />CONDITIONS. MONITORING SYSTEM TO BE INSTALLED TO THE SAME STANDARD FOR COMMUNICATIONS
<br />AS REQUIRED BY OWNER.
<br />INSTALL NEW CONCRETE TANK MAT AND OTHER CONCRETE AS INDICATED ON SITE PLAN. DRIVE SLAB
<br />SHALL BE PER BUOYANCY CALCS.
<br />INSTALL DISPENSERS AND CONSOLES AS INDICATED ON SITE PLAN AND DESCRIBED IN THE EQUIPMENT
<br />LIST.
<br />THE ABOVE MENTIONED LIST IS FOR REFERENCE ONLY. CITY, COUNTY, OR OTHER
<br />GOVERNING AGENCIES, MAY HAVE OTHER REQUIREMENTS THAT MUST BE ADHERED TO. IT
<br />IS THE CONTRACTORS RESPONSIBILITY TO CONFIRM AND MEET ALL REQUIREMENTS.
<br />CONTRACTOR IS RESPONSIBLE FOR VENT AND VAPOR RECOVERY PIPING SYSTEM
<br />PASSING ANY LOCALLY IMPOSED TEST REQUIREMENTS.
<br />METER CALIBRATION, CONFIRMED AND ADJUSTED. (RESULTS MUST BE SENT TO WEIGHTS
<br />& MEASURES WITHIN 24 HOURS OF COMPLETION)
<br />UPON COMPLETION OF PRIMARY PIPING AND BEFORE GLUING. SECONDARY HAS
<br />TO BE INSTALLED PRIOR TO GLUING OF PRIMARY. PRESSURE TESTING NOT TO
<br />EXCEED THE MAXIMUM WORKING PRESSURE OF FUEL PIPING COMPONENTS.
<br />IMPACT VALVES ARE RATED AT 50PSI TESTING TO BE ACCORDING TO PIPE
<br />MANUFACTURER'S INSTRUCTIONS.
<br />CONTRACTOR SHALL PROVIDE OWNER 48 HOUR NOTICE FOR TESTING
<br />AND COMPLY WITH PERMIT CONDITIONS FOR LOCAL INSPECTORS..
<br />UPON COMPLETION OF SECONDARY PIPING AND BEFORE PLACEMENT OF ANY
<br />BACKFILL, TEST SECONDARY PIPING AS REQUIRED BY PIPE MANUFACTURER.
<br />THERE MUST BE TWO (2) GAUGES (0-100 PSI) PER PRODUCT BEING
<br />TESTED.
<br />MAKE SURE PERSONNEL ARE KEPT AWAY FROM PIPING SYSTEM DURING ANY
<br />TIME INITIAL PRESSURIZATION IS BEING APPLIED.
<br />APPLY PRESSURE IN 15-20 PSI INTERVALS UNTIL REACHING A MAXIMUM OF 60
<br />PSI.
<br />MARK CRITICAL PRESURES ON GAUGES WITH ELECTRICAL TAPE AT THE
<br />BEGINNING OF EACH TEST.
<br />AFTER PROVING SYSTEM TIGHTNESS, APPLY 50 PSI PRESSURE, HOLD FOR ONE
<br />MINUTE, THEN RELEASE PRESSURE. REPEAT PRESSURIZATION CYCLE A MINIMUM
<br />OF (5) TIMES.
<br />UPON COMPLETION OF THE ABOVE TESTS, KEEP PRESSURE AT 50 PSI FOR A
<br />MINIMUM OF (3) HOURS. OBSERVE PRESSURE GAUGES FOR ANY LOSS.
<br />THIS SITE IS PREVIOUSLY UNDEVELOPED AND HAS NO FUEL CONTAMINATION.
<br />CONTRACTOR EMPLOYEES SHALL HAVE COMPLETED "APPROPRIATE
<br />MANUFACTURERS PIPES TRAINING" (CERTIFICATE REQUIRED). CONTRACTOR SHALL
<br />COMPLETE THE "PIPING SYSTEMS INSTALLATION CHECKLIST FOR UNDERGROUND
<br />PETROLEUM PIPES" AND SHALL FURNISH THE OWNER WITH COPIES OF ALL
<br />APPROPRIATE CERTIFICATES.
<br />CONTRACTOR SHALL HAVE BEEN TRAINED BY "TANK MANUFACTURER FOR TANK
<br />INSTALLATION" CONTRACTOR SHALL COMPLETE THE "TANK INSTALLATION CHECKLIST"
<br />(SUPPLIED TO CONTRACTOR BY MANUFACTURER DURING TANK DELIVERY) AND SHALL
<br />FURNISH A COPY OF THIS DOCUMENT TO THE OWNER.
<br />CONTRACTOR SHALL DEVELOP A SPECIFIC SITE SAFETY PLAN PRIOR TO THE START OF
<br />WORK. CONTRACTOR SHALL CONDUCT WEEKLY JOB SITE SAFETY MEETINGS WITH IT'S
<br />EMPLOYEES.
<br />CONTRACTOR SHALL SUBMIT PROOF OF ALL REQUIRED INSURANCE TO THE
<br />OWNER AND SHALL NAME "ALLIED FUELS " AS "ALSO INSURED."
<br />COMPREHENSIVE GENERAL LIABILITY, INCLUDING CONTRACTOR'S PROTECTIVE
<br />LIABILITY, COMPLETED OPERATIONS LIABILITY, AND CONTRACTUAL LIABILITY,
<br />WITH A COMBINED SINGLE LIMIT OF NOT LESS THAN $1,000,000 PER
<br />OCCURRENCE FOR BODILY INJURY AND PROPERTY DAMAGE.
<br />EMPLOYEES LIABILITY WITH A MINIMUM LIMIT OF LIABILITY OF $1,000,000 FOR
<br />EACH OCCURRENCE.
<br />AUTOMOBILE LIABILITY COVERING USE OF ALL OWNED HIRED VEHICLES WITH
<br />A COMBINED SINGLE LIMIT OF SINGLE UNIT OF LIABILITY OF NOT LESS THAN
<br />$1,000,000 PER OCCURRENCE FOR BODILY INJURY AND PROPERTY DAMAGE.
<br />GENERAL CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, AND
<br />SERVICES NECESSARY FOR OR REASONABLY INCIDENTAL TO THE SATISFACTORY
<br />COMPLETION OF ALL WORK SHOWN ON, CALLED FOR, OR REQUIRED BY THE
<br />DRAWINGS.
<br />ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CURRENT 2016
<br />CALIFORNIA FIRE, BUILDING, ELECTRICAL AND MECHANICAL CODES, CCR TITLE
<br />23,DIVISION 3, CHAPTER 16, ARTICLE 3; AND CALIFORNIA AIR RESOURCES BOARD
<br />REQUIREMENTS.
<br />ALL EXCAVATIONS SHALL BE PERFORMED IN COMPLIANCE WITH OSHA AND STATE
<br />REGULATIONS. THE CONTRACTOR IS REFERRED TO THE OSHA BOOKLET, "EXCAVATING
<br />AND TRENCHING OPERATIONS, FOR SAFE WORK PRACTICES GUIDE" FOR PERFORMING
<br />EXCAVATION WORK.
<br />UPON COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL PROVIDE THE
<br />OWNER WITH "AS BUILT" DRAWINGS OF ALL ITEMS INSTALLED BY THE CONTRACTOR.
<br />"AS BUILTS" SHALL BE COMPLETED ON-SITE.
<br />CONTRACTOR SHALL PROVIDE A WORK SCHEDULE TO THE OWNER BEFORE
<br />COMMENCING ANY CONSTRUCTION WORK.
<br />CONTRACTOR SHALL COORDINATE ALL INSPECTIONS AND APPROVALS AND
<br />SHALL OBTAIN, AT THE COMPLETION OF THE PROJECT, ALL CERTIFICATES
<br />REQUIRED TO OPERATE THE FACILITY.
<br />FENCE OFF FUEL SYSTEM WORK AREA WITH 6' HIGH CHAIN LINK FENCE. AT THE
<br />END OF EACH WORK DAY SECURE FENCING PANELS TOGETHER.
<br />THE OWNER SHALL PROVIDE FOR TRANSPORTATION AND DISPOSAL OF EXCAVATED SOIL
<br />AFTER COMPLETION OF ANY NECESSARY REMEDIATION, INCLUDING AERATION.
<br />INSTALL NEW PETROLEUM PRODUCT, VENT & VAPOR LINES PER SITE PLAN, STANDARD
<br />TANK DRAWINGS, AND PER PIPING GENERAL NOTES ON SHEET FS-1.
<br />ALL PIPING OTHER THAN FIBERGLASS SHALL BE
<br />BLACK IRON (GALVANIZED PIPE IS NOT
<br />ALLOWED). ALL BELOW GRADE PIPING SHALL BE
<br />FRP, NO EXCEPTIONS.
<br />NEW HIRT VENT SYSTEM, INSTALL PER MANUFACTURER'S
<br />INSTRUCTIONS.
<br />DO NOT SUBJECT THE EVR APPROVED EQUIPMENT TO PRESSURES HIGHER THAN THE
<br />MANUFACTURERS RECOMMENDATIONS.
<br />(b)TANKS TO BE TESTED PER MANUFACTURER'S WRITTEN INSTRUCTIONS AS TO NOT VOID THE
<br />WARRANTY.
<br />FS1.0
<br />A.ALL PIPING SHALL BE INSTALLED IN ACCORDANCE WITH ALL APPLICABLE
<br />MANUFACTURER'S INSTALLATION SPECIFICATIONS AND INSTRUCTIONS SEE
<br />NOTES BELOW.
<br />B.FIBERGLASS PIPING SHALL BE LIMITED TO THE FOLLOWING:
<br />SMITH FIBERGLASS RED THREAD IIA FOR PRODUCT, VENT AND VAPOR LINES,
<br />USING ONLY DS8000 SERIES ADHESIVES TO JOIN PRIMARY PRODUCT AND
<br />SECONDARY CONTAINMENT PIPE AND ALCOHOLS AND FITTINGS FOR
<br />ALCOHOL-GASOLINE MIXTURES. WHEN JOINING SECONDARY
<br />CONTAINMENT FITTINGS, A SPECIAL FILLER FROM SMITH FIBERGLASS
<br />PRODUCTS MUST BE ADDED TO THE DS8000 SERIES ADHESIVES.
<br />1.)UNDERGROUND PIPING: SMITH FIBERGLASS SYSTEMS:
<br />MIN. AMOUNT OF
<br />PEA GRAVEL
<br />ABOVE THE TOP
<br />OF THE PIPE
<br />MINIMUM
<br />BURIAL
<br />DEPTH
<br />SURFACE
<br />CONDITION
<br />PIPE
<br />SIZE
<br />PIPE
<br />MANUFACTURER
<br />SMITH FIBERGLASS
<br />RED THREAD IIA
<br />12"
<br />8"
<br />5"
<br />14"
<br />9"
<br />7"
<br />14"
<br />10"
<br />7"
<br />17"
<br />12"
<br />9"
<br />20"
<br />13"
<br />11"
<br />20"
<br />14"
<br />11"
<br />2"
<br />3"
<br />4"
<br />E.
<br />16.PIPING MANUFACTURER AND INSTALLATION REQUIREMENTS
<br />DRAWING INDEX
<br />MANTECA
<br />1014 S. AIRPORT ROAD
<br />MANTECA , CA 95336
<br />fuel system
<br />C.ABOVE GROUND PIPING FOR FUELS:
<br />1.) BLACK IRON AND BLACK IRON FITTINGS. SINGLE WALL.
<br />GALVANIZED PIPE IS NOT PERMITTED.
<br />D.
<br />MANTECA, CALIFORNIA
<br />FUELING SYSTEM
<br />FS1.0 FUEL SYSTEM COVER SHEET & GENERAL NOTES
<br />FS1.1 TANKS AND LINES SITE PLAN
<br />FS1.2 ENLARGED FUEL SYSTEM SITE PLAN
<br />FS2.0 EQUIPMENT LISTS
<br />FS3.0 TANK SECTIONS
<br />FS3.1 TANK SECTIONS
<br />FS4.0 DETAILS
<br />FS5.0 DIESEL TANK SUMPS, VENT DETAILS
<br />FS6.0 TANK AND LINE WET HOLE DETAILS
<br />FS7.0 MONITORING SYSTEM
<br />FS4.1 87 AND 91 TANK SUMP DETAILS
<br />CALIFORNIA FIRE CODE NOTES
<br />PRIOR TO FINAL, DOCUMENTATION FROM THE SAN JOAQUIN COUNTY ENVIRONMENTAL HEALTH
<br />DEPARTMENT HAZARDOUS MATERIAL DIVISION INDICATING THAT THE UNDERGROUND
<br />FLAMMABLE/COMBUSTIBLE LIQUIDS STORAGE TANKS HAVE BEEN APPROVED SHALL BE PROVIDED
<br />NOTE:
<br />THE TANK AND THE TANK SUMPS HAVE CALCIUM CHLORIDE IN
<br />THE INTERSTITIAL SPACE.
<br />THE DISPENSER SUMPS AND VENT SUMPS HAVE PROPYLENE
<br />GLYCOL IN THE INTERSTITIAL SPACE
<br />CONTRACTOR TO LABEL FILL PORTS WITH TYPE OF FILL.
<br />CODES
<br />THESE DRAWINGS HAVE BEEN PREPARED USING: THE 2022 CALIFORNIA BUILDING CODE,
<br />CALIFORNIA FIRE CODE, CALIFORNIA ELECTRICAL CODE, CALIFORNIA MECHANICAL CODE,
<br />CALIFORNIA PLUMBING CODE, CALIFORNIA ENERGY CODE, AND CALIFORNIA GREEN BUILDING
<br />STANDARDS CODE(S) AND ORDINANCES. ALL WORK SHALL COMPLY WITH CURRENT
<br />ACCESSIBILITY REQUIREMENTS.
<br />NOTE: PERSONS INSTALLING PIPING MUST BE CERTIFIED AS HAVING
<br />BEEN TRAINED BY THE PIPING MANUFACTURER.
<br />PIPING TO BE INSTALLED WITH THE MINIMUM DEPTHS LISTED BELOW. ALL
<br />CROSSOVERS OF PIPING SHALL HAVE 6" MINIMUM BETWEEN PIPES.
<br />UNPAVED
<br />PAVED, ASPHALT
<br />(4" MINIMUM)
<br />PAVED,
<br />CONCRETE (4"
<br />MINIMUM)
<br />UNPAVED
<br />PAVED, ASPHALT
<br />(4" MINIMUM)
<br />PAVED,
<br />CONCRETE (4"
<br />MINIMUM)
<br />UNPAVED
<br />PAVED, ASPHALT
<br />(4" MINIMUM)
<br />PAVED,
<br />CONCRETE (4"
<br />MINIMUM)
<br />SCALE: N.T.S.
<br />SITE
<br />1
<br />3
<br />3
<br />3
<br />FS7.1 MONITORING SYSTEM
<br />5
<br />FUEL SYSTEM COVER
<br />SHEET & GENERAL
<br />NOTES
<br />6
|