Laserfiche WebLink
The following is an itemized list of CP22 - UST FULL violations that have not been <br /> addressed for GAVINKO PETROLEUM* as of January 07, 2026. <br /> Open violations from October 16, 2025 inspection <br /> Violation#3-2010013-Facility has submitted a complete and accurate UST Monitoring Plan.. <br /> OBSERVATION: The monitoring plan is not approved by the EHD. <br /> 1.) For the Premium and Regular Tanks -> In the monitoring plan the"ELLD Model' is listed as 84-84-01,this is <br /> incorrect.The correct model is 848480-001 or it can be listed as 8484 to represent the series name. <br /> 2.)For all 3 tanks-> In the monitoring plan,the names listed under"Personnel Responsibilities"are the names of the <br /> former owners, please update. <br /> REGULATION GUIDANCE:The monitoring plan must be uploaded to the California Environmental Reporting System <br /> (CERS). <br /> CORRECTIVE ACTION: Immediately log into CERS, make the necessary changes, and submit for review by the EHD. <br /> ❑ This violation was corrected ❑This violation will be corrected by(date): <br /> ❑ Supporting documents included <br /> Describe actions taken or will be taken to correct violation: <br /> Violation#5-2030041 -A current facility plot plan is maintained and has been submitted. <br /> OBSERVATION:An accurate UST Monitoring Site Plan was not submitted. <br /> -The UST Monitoring Site Plan currently indicates that all three Leak Detectors on site are a "LD2000"this is <br /> incorrect, it is a 8484 or it may be listed as 848480-001. <br /> -The location of the monitoring panel is not indicated in the map <br /> REGULATION GUIDANCE:A site plan must be submitted identifying the locations where monitoring will be performed. <br /> The site plan must show the general layout of tanks and clearly identify locations of the following equipment, if <br /> installed: 1)monitoring panels; 2)in-tank liquid level probes (if used for leak detection); 3)devices monitoring tank <br /> annular spaces or vault;4)devices monitoring product piping; 5)devices monitoring fill piping; 6)devices monitoring <br /> vent piping; 7)devices monitoring vapor recovery piping; 8)devices monitoring vent/transition sumps; 9)devices <br /> monitoring under-dispenser containment; 10)line leak detectors; and 11)devices monitoring any other secondary <br /> containment areas. <br /> CORRECTIVE ACTION: Immediately log into the California Environmental Reporting System (CERS)at <br /> http://cers.calepa.ca.gov/and upload a copy of the UST Monitoring Site Plan. <br /> Page 1 of 5 <br />