Laserfiche WebLink
SAN JOAQUIN AMENDED Environmental Health Department <br /> COUNTY— 1/8/2026 <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> GAVINKO PETROLEUM* 17700 MORELAND ST, STOCKTON TIOctober 16, 2025 <br /> 56 2716(a-e) 2030013- DO inspections completed at least every 30 days and meet all requirements (TCR 12) <br /> OBSERVATION: The following issues were discovered while reviewing the DO inspection reports: <br /> -> The 7/9/2025 DO inspection Report did not include follow up for the following alarms from 6/13/2025, no work orders <br /> were found. <br /> L14: Diesel STP annular- Fuel Alarm <br /> S1: 87 Line Vacuum <br /> S3: 91 line- No Vacuum <br /> S3: 91 line- Communication <br /> S5: Diesel Vent- High Liquid Alarm <br /> -> The 8/8/2025 DO inspection Report did not include follow up for the following alarm, no work orders were found. <br /> 7/29/2025 1-2: 87 Fill - Fuel Alarm <br /> -> The 10/8/2025 DO inspection Report did not include follow up for the alarm from 9/30/2025 L16: Dispenser 1/2 <br /> Annular Space - Fuel Alarm, no work orders were found. <br /> -> The 1/27/2025 DO inspection report did not indicate the 1/7/2025 1-9: 91 STP Sump- Fuel Alarm, Section 5 was not <br /> complete, No CERS ID was included in Section 1. No work order was found to indicate that the alarm was addressed. <br /> -> The 12/27/2024 DO inspection Report did not include the following alarms and no work orders were found. <br /> 12/16/2024 1-2: 87 Fill Sump - Fuel Alarm <br /> 12/19/2024 1-4: 87 STP Sump- Fuel Alarm <br /> -> The 11/29/2024 DO Inspection Report did not include the following alarms and no work orders were found. <br /> 11/22/2024 1-2: 87 Fill Sump - Fuel Alarm <br /> 11/1/2024 1-7: 91 Fill Sump- Fuel Alarm <br /> - Several DO visual inspection reports did not have section 6 complete, the "Name of UST Owner/Operator"was left <br /> blank. <br /> -Section 11 was left blank on the 5/9/25 report <br /> REGULATION GUIDANCE: During the inspection, the designated operator shall review the alarm history since the <br /> previous inspection, check that each alarm was documented and responded to appropriately, and attach a copy of the <br /> alarm history with documentation taken in response to any alarms to the inspection report. <br /> CORRECTIVE ACTION: Ensure that designated operators performing inspections at this facility are including all of the <br /> required information on the reports. <br /> This is a Repeat(Class 2)Violation. <br /> 58 2715(c)(3), 2715(c)(4) 2010015 - Copies of Facility Employee Training Certificates maintained <br /> OBSERVATION: The Facility Employee Training Certificate was not available for review at the time of inspection. <br /> REGULATION GUIDANCE: All site employees must be trained prior to taking responsibility as a facility employee if after <br /> October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training Certificate shall <br /> contain accurate information for all employees trained. <br /> CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and <br /> submit a copy of the updated form to the EHD. <br /> This is a Repeat(Class 2)Violation. <br /> EHD-CUPA Inspection Report IS03 Page 6 of 7 FA0003732 PR0231819 4565085 1/8/2026 <br /> CP22-UST FULL g <br /> 1868 E. Hazelton Avenue I Stockton, California 95205 1 T 209 468-3420 1 F 209 464-0138 1 www.sjgov.org/EHD <br />