Laserfiche WebLink
All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 2 of 7 <br />Test Method Developed by Manufacturer Industry Standard Professional <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: 0 to 30 in Hg glycerin filled vacuum gauge(s) <br />Tank ID T1 Diesel <br />Tank Manufacturer Xerxes <br />Tank Capacity 550 <br />Test Start Time 11:15 <br />Initial Reading 10 <br />Test End Time 12:15 <br />Final Reading 10 <br />Change in Reading 0 <br />Pass/Fail Criteria 0 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Test Method Developed by Manufacturer Industry Standard Professional <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: 0 to 15 psi glyceride filled pressure gauge(s) <br />Pipe Run ID Supply Return Vent <br />Pipe Manufacturer Environ Environ Environ <br />Test Start Time 11:15 11:15 11:15 <br />Initial Reading 5 5 5 <br />Test End Time 12:15 12:15 12:15 <br />Final Reading 5 5 5 <br />Change in Reading 0 0 0 <br />Pass/Fail Criteria 0 0 0 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Pipe Run ID <br />Pipe Manufacturer <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br />6. TANK SECONDARY CONTAINMENT TEST <br />7. PIPE SECONDARY CONTAINMENT TEST