Laserfiche WebLink
All tests marked "Fail" and any repairs made before or during the tightness test must be described in <br />the COMMENTS section. <br />Page 3 of 7 <br />Test Method Developed by Manufacturer Industry Standard Professional <br />Test Type Pressure Vacuum Hydrostatic <br />Test Equipment Used: INCON TS STS <br />Sump/UDC ID Fill Piping Vault Vent Box <br />Sump Manufacturer Xerxes Bravo Bravo <br />Sump Depth (inches) 74 30 30 <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) 31 13 11 <br />Test Start Time 11:27 11:27 11:27 <br />Initial Reading 4.9353 2.9255 6.5632 <br />Test End Time 11:42 11:42 11:42 <br />Final Reading 4.9354 2.9252 6.5632 <br />Change in Reading 0.0001 0.0003 0 <br />Pass/Fail Criteria 0.002 0.002 0.002 <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Sump/UDC ID <br />Sump Manufacturer <br />Sump Depth (inches) <br />Sump Bottom to Top of <br />Highest Pipe Penetration <br />(inches) <br />Test Start Time <br />Initial Reading <br />Test End Time <br />Final Reading <br />Change in Reading <br />Pass/Fail Criteria <br />Tightness Test Results Pass Fail Pass Fail Pass Fail Pass Fail <br />Additional copies of this page may be attached. <br />8. SUMP/UDC TEST