h. Diagrams shall include raceway numbers, raceway size, raceway type, <br /> cable numbers, wire color code, and wire numbers. <br /> i. Each wire size, and cable size and color code shall be shown. Each <br /> conduit with the conduit label and conduit size and wire fill shall be <br /> shown. Wire and cable routing through conduits, wireways, manholes, <br /> handholes, junction boxes, terminal boxes and other electrical <br /> enclosures shall be shown with the appropriate equipment labels. All <br /> spare wires, cable, and termination points shall be shown. Cable <br /> shields shall be shown. -- <br /> j. Labeling codes for terminal blocks, terminals, wires, cables, panels, <br /> cabinets, instruments, devices, and equipment shall be shown. Place <br /> "oA", "oB", and "oC" label next to each breaker to identify phase <br /> connected to. <br /> k. Schematic symbols shall be used for field devices, showing electrical _ <br /> contacts. Signal and DC circuit polarities shall be shown. <br /> I. The diagrams shall show all other Contract and Supplier Drawing <br /> numbers, for reference, that are associated with each device that is — <br /> interconnected. <br /> M. The diagrams shall show all other Contract and Supplier drawing <br /> numbers, for reference, that are associated with each device that is <br /> interconnected.Attached to each interconnect, a copy of all the support <br /> documents used in preparing interconnects shall be submitted. This <br /> includes current issues of panel schematics, elementary diagrams, <br /> panelboard schedules, conduit schedules, one-line diagrams, <br /> connection diagrams, terminal block diagrams, submittals, contract <br /> drawings, vendor drawings and all other data used to develop the - <br /> interconnection diagram as noted in the"Reference Documents"corner <br /> of interconnect drawings. <br /> n. Interconnects shall include list of all applicable reference drawings, — <br /> request for clarifications, field instructions and change orders. All <br /> deletions and additions of equipment, wire and cables shall be clearly <br /> shown. — <br /> o. Field wiring shall not start before the interconnection Drawing has been <br /> submitted by the Contractor and approved by the Owner. <br /> p. Do not show the same wires or jumpers, or panel wiring on both the <br /> connection and interconnection diagrams. All jumper, shielding, and <br /> grounding termination details not shown on the connection diagrams <br /> shall be shown on the interconnection diagrams. <br /> July 2007 Division III-177 NEI Phase II Water and Sewer <br /> CIP Nos. 7468, 7589, 7590 <br />