A. A daily production log.
<br /> B. Reports of all visual weld inspections and NDT.
<br /> C. Radiographs and radiographic reports,and other required NDT reports.
<br /> D. A summary of welding and NDT activities that occurred during the reporting period.
<br /> E. Reports of each application of heat straightening.
<br /> F. A summarized log listing the rejected lengths of weld by welder, position, process,joint configuration, and piece
<br /> number.
<br /> G. Documentation that the Contractor has evaluated all radiographs and other nondestructive tests and corrected all
<br /> rejectable deficiencies, and that all repaired welds have been reexamined using the required NDT and found
<br /> acceptable.
<br /> The following information shall be clearly written on the outside of radiographic envelopes: name of the QCM,name of
<br /> the nondestructive testing firm,name of the radiographer,date,contract number, complete part description, and all included
<br /> weld numbers,report numbers,and station markers or views,as detailed in the WQCP. In addition,all interleaves shall have
<br /> clearly written on them the part description and all included weld numbers and station markers or views, as detailed in the
<br /> WQCP. A maximum of 2 pieces of film shall be used for each interleave.
<br /> Reports of all visual inspections and NDT shall be signed by the inspector or technician and submitted daily to the QCM
<br /> for review and signature prior to submittal to the Engineer. Corresponding names shall be clearly printed or typewritten next
<br /> to all signatures. Reports of all NDT,whether specified, additional, or informational,performed by the Contractor shall be
<br /> submitted to the Engineer.
<br /> The Engineer will review the Welding Report to determine if the Contractor is in conformance with the WQCP. Unless
<br /> otherwise specified, the Engineer shall be allowed 2 weeks to review the report and respond in writing after the complete
<br /> Welding Report has been received. Prior to receiving notification from the Engineer of the Contractor's conformance with
<br /> the WQCP, the Contractor may encase in concrete or cover welds for which the Welding Report has been submitted.
<br /> However, should the Contractor elect to encase or cover those welds prior to receiving notification from the Engineer, it is
<br /> expressly understood that the Contractor shall not be relieved of the responsibility for incorporating material in the work that
<br /> conforms to the requirements of the plans and specifications. Material not conforming to these requirements will be subject
<br /> to rejection. Should the Contractor elect to wait to encase or cover welds pending notification by the Engineer, and in the
<br /> event the Engineer fails to complete the review within the time allowed,and if,in the opinion of the Engineer,completion of
<br /> the work is delayed or interfered with by reason of the Engineer's delay in completing the review, the Contractor will be
<br /> compensated for any resulting loss, and an extension of time will be granted, in the same manner as provided for in
<br /> Section 8-1.09,"Right of Way Delays,"of the Standard Specifications.
<br /> In addition to the requirements in AWS D1.1 and AWS D1.5, second-time excavations of welds or base metal to repair
<br /> unacceptable discontinuities,regardless of NDT method,and all repairs of cracks require prior approval of the Engineer.
<br /> The Engineer shall be notified immediately in writing when welding problems, deficiencies,base metal repairs, or any
<br /> other type of repairs not submitted in the WQCP are discovered, and also of the proposed repair procedures to correct them.
<br /> For requests to perform second-time repairs or repairs of cracks,the Contractor shall include an engineering evaluation of the
<br /> proposed repair. The engineering evaluation,at a minimum,shall address the following:
<br /> A. What is causing each defect?
<br /> B. Why the repair will not degrade the material properties?
<br /> C. What steps are being taken to prevent similar defects from happening again?
<br /> The Contractor shall allow the Engineer one week to review these procedures. No remedial work shall begin until the
<br /> repair procedures are approved in writing by the Engineer. In the event the Engineer fails to complete the review within the
<br /> time allowed, and if, in the opinion of the Engineer, completion of the work is delayed or interfered with by reason of the
<br /> Engineer's delay in completing the review, the Contractor will be compensated for any resulting loss, and an extension of
<br /> time will be granted, in the same manner as provided for in Section 8-1.09, "Right of Way Delays," of the Standard
<br /> Specifications.
<br /> The QCM shall sign and furnish to the Engineer, a Certificate of Compliance in conformance with the provisions in
<br /> Section 6-1.07, "Certificates of Compliance," of the Standard Specifications for each item of work for which welding was
<br /> performed. The certificate shall state that all of the materials and workmanship incorporated in the work, and all required
<br /> tests and inspections of this work, have been performed in conformance with the details shown on the plans, the Standard
<br /> Specifications,and these special provisions.
<br /> WELDING FOR POLE STRUCTURES -
<br /> The Contractor shall meet the following requirements for any work welded in conformance with the provisions in
<br /> Section 86-2.04, "Standards,Steel Pedestals and Posts,"of the Standard Specifications.
<br /> Contract No. 10-OM7104