Laserfiche WebLink
23500 Kasson Road, Tracy Record ID PR0505989 <br /> 5-24-16 and 5-25-2016 PHOTO#2 <br /> SPCC plan excerpt documenting outstanding issues that need corrections <br /> Spill Prevention, Control and Counte'771 Fe Plan <br /> For Deuel Vocational Institution <br /> Table A-1. (Continued) <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> <br /> ) 3. Automatic volume and interstitial space monitoring provided. <br /> 4. No signage for tank contents,hazard,and no smoking. <br /> 5. Normal and emergency vents provided. <br /> 6. Tank properly grounded. <br /> 7. Tank bolted to concrete pad for earthquake restraint_ <br /> 8. Vehicle protection provided by traffic bollards. <br /> 9. No lighting provided for spill/leak identification on generator <br /> package. <br /> 10. No spill kit present. <br /> Three emergency generators are present within the inmate housing area.The fuel tanks for these generators have capacities of 50 gallons and are,therefore,not subiect to the <br /> requirements of 40 CFR 112.Active spill containment will be used to address any releases from these tanks.The emergency generators and tanks are located on the Culinary Root; <br /> D Vault Roof,and C-Wing Roof <br /> Comments associated with multiple tanks at one location are provided in same row. <br /> ` Items in bold indicate deficiencies needing correction.See recommendations in Appendix A,Table A-3. <br /> AST—aboveground storage tank <br /> Elena Manzo, REHS Page 2 of 14 <br />