API 653 In-Service Inspection Report r <br /> for m m m m <br /> Pacific Ethanol HMT Inspection <br /> Tank No. T-6105 August 7,2013 <br /> Stockton, CA Page 7 of 45 <br /> SUMMARY AND REPAIR RECOMMENDATIONS (CONT'D.) <br /> NOZZLES AND APPURTENANCES (CONTD.): The vertical ladder coating is <br /> weathered and is starting to show signs of failure with light surface rust present. <br /> Consideration should be given to properly re-coating this detail to minimize further <br /> corrosion. <br /> FIXED ROOF: <br /> Visual (VT) inspection and Ultrasonic (UT) testing was performed in accessible <br /> locations. <br /> Visual (VT) inspection noted the entire roof and handrail coating is weathered and is <br /> showing signs of chalking. The coating is intact with no areas of failure that expose the <br /> underlying carbon steel. There is product residue on the roof plates. Consideration <br /> should be given to properly cleaning the product residue and monitoring the coating <br /> integrity. <br /> Nominal thickness of the roof is 0.250 inch and the lowest thickness obtained during this <br /> inspection was 0.236 inch. <br /> R 1E C"'J Ez 1114,f D <br /> +� AUG 14 2014 <br /> APIRPTNE.00T REV 2 23262668fT-6105r(Rev 1) $p(V,1 - HEALTH <br /> DEPARTMENT <br />