Laserfiche WebLink
0 0 <br />RECOVERY REQUIREMENTS <br />Refrigerant Recovery and/or Recycling equipment manufactured after November 15, 1993, must be certified and labeled <br />by an EPA approved equipment testing organization to meet EPA standards. All equipment must have low loss fittings to <br />minimize refrigerant loss when hoses are disconnected. <br />The following is a list of the required levels of evacuation for Low Pressure appliances: <br />Using recovery or recycling equipment manufactured or imported before Nov. 15, 1993 <br />25 inches Hg <br />Using recovery or recycling equipment manufactured or imported on or after Nov. 15, 1993 <br />25 mm Hg absolute <br />Once the required vacuum has been achieved, the technician should wait for a few minutes and monitor the system <br />pressure. If the pressure rises, indicating that there is refrigerant remaining in the system, recovery must be repeated. <br />When leaks in an appliance make evacuation to the prescribed level unattainable, the appliance should be evacuated to the <br />lowest attainable level prior to a major repair. <br />REFRIGERA TION NOTES (Review vapor/compression system in introduction) <br />The use of a large vacuum pump could cause trapped water to freeze. During evacuation of systems with large amounts <br />of water, it may be necessary to increase pressure by introducing nitrogen to counteract freezing. <br />If a strong odor is detected during the recovery process, a compressor burn -out has likely occurred. When recovering <br />refrigerant from a system that experienced a compressor bum -out, watch for signs of contamination in the oil. <br />Because chillers using refrigerants such as CFC -11 and HCFC -123 operate below atmospheric pressure, they require a <br />purge unit. The primary purpose of a purge unit is to remove non-condensables from the system. A centrifugal chiller's <br />purge condensing unit takes its suction from the top of the condenser, removes air and other non-condensables from the <br />system, and returns refrigerant to the evaporator. Although a high efficiency purge unit discharges a low percentage of <br />refrigerant with the air they remove, frequent purging and subsequent refrigerant loss can indicate that a leak is allowing <br />air into the system. High discharge pressure is also an indication of air in the system Excessive moisture collection in the <br />purge unit can indicate tube leakage. <br />To protect the system from over -pressurization, low-pressure chillers typically use a rupture disc mounted on the <br />evaporator housing. The typical design burst pressure for a rupture disc is 15 psig. <br />SAFETY (Additional Safety and shipping information is covered in the core section of this manual.) <br />ASHRAE standard 15 requires a refrigerant monitor that will sound an alarm and automatically start a ventilation system <br />in equipment rooms before the refrigerant concentration reaches the TLV -TWA, (threshold limit value — time weighted <br />average). <br />A refrigerant monitor is required for all ASHRAE refrigerant safety groups. <br />CFC -12, CFC -11, and HFC -134a are code grouped as A-1. R-123 is code grouped as B-1. <br />All refrigeration systems must be protected by a pressure relief valve (s) (must not be installed in series). <br />Additional Safety and shipping information is covered in the core section of this manual <br />gg;EW �� <br />MpY l a 2015 <br />eWkRONME�TAT <br />