Laserfiche WebLink
Inspection <br />An STI SP001 formal external inspection that included visual examination was conducted. The inspection was completed on <br />10/2/2015. The tank is located at Martin -Brower, 4704 Fite Court in Stockton, CA. The following is a detailed report of the <br />inspection including findings and recommendations. <br />1.0 GenerailTank Information <br />Information <br />ObservationsGeneral <br />Facility Name <br />Martin -Brower <br />Facility ID <br />MARTIN-BROWER <br />Compliance Records Available? <br />No <br />Tanknology Work Order No. <br />6700447 <br />Other <br />Tank Data <br />•.Comments/Recommendations <br />Tank Nameplate <br />Yes <br />STI -Secondary Contained -F921 <br />s.n. 00520 <br />Tank Name / Number <br />1 <br />Tank Layout (Horizontal, Vertical, other) <br />Horizontal <br />Tank Design (Single wall, double wall, other) Double Wall <br />Tank Construction Material (carbon, <br />Carbon <br />stainless, other) <br />Tank size (nominalgallons) <br />10000 <br />Tank Shape <br />Cylindrical <br />Tank Length <br />27' <br />Tank width / diameter / circumference <br />8' <br />Tank Height <br />N/A <br />Tank Contents <br />Diesel <br />Cathodic Protection <br />None <br />Continuous Release Detection Method <br />Elevated <br />CRDM <br />Release Prevention Barrier (RPB) <br />Concrete Pad <br />Spill Control <br />Double Wall <br />Other <br />Foundations And Supports <br />Observations <br />Comments/Recommendations <br />Tank Foundation Type <br />Concrete pad <br />Tank Foundation Condition <br />Good/some small cracks <br />Tank Support Type <br />Steel Saddles <br />Tank Support Condition <br />Good <br />Tank Protection (bollards, fence, other) <br />Bollards around tanks <br />Other <br />Signage As Required By NFPA 30 <br />•._Comments/Recommendations <br />Filling Procedures Posted At Fill As <br />Yes <br />Required? <br />"No Smoking" Signage Present As Re uired. <br />Yes <br />Emergency Contact Numbers Posted As <br />No <br />Emergency plan is required and should include posting <br />Required? <br />of emergency contact numbers. ** <br />Tank Capacity And Tank ID Posted On The <br />No <br />Clearly label tank with capacity and ID. ** <br />Tank As Required? <br />NFPA Signage - On The Tank, At Facility <br />Entrance, And As Designated By Fire Code <br />Official. Labels Include Contents And NFPA <br />es <br />704 Diamond Hazard Signs. <br />Other <br />