Laserfiche WebLink
I r r <br />•rComments/Recommendations <br />Good/corrosion free <br />Other <br />Valves <br />Anti Siphon Valve installed? <br />•.servations Commenti r. <br />Yes <br />Secondary Containment Type <br />Concrete wall/floor Not true secondary because the wall is just a curb 6" <br />Anti Siphon Valve Model <br />high. diesel tanks share this area. <br />Secondary Containment Length <br />66' <br />Secondary Containment Width <br />20' <br />Secondary Containment Height <br />6" <br />Secondary Containment Volume (gallons) <br />4937 gal <br />Secondary Containment Condition <br />N/A <br />(breaches, foreign material, liquid) <br />None <br />Secondary Containment Drain Valve <br />OPW <br />Installed? <br />es Open conduit w/plug <br />Drain Valve Locked? <br />No <br />Sump Pump Installed? <br />N/A <br />Is The Sump Pump Float or Manually <br />N/A <br />Activated? <br />Other <br />4.0 Tank Apputlenances <br />Piping <br />Ancillary Equipment: Piping / Piping <br />Connections (leaks, corrosion, supports) <br />•rComments/Recommendations <br />Good/corrosion free <br />Other <br />Valves <br />Anti Siphon Valve installed? <br />•.servations Commenti r. <br />Yes <br />Anti Siphon Valve Manufacturer <br />Unknown <br />Anti Siphon Valve Model <br />150 swp/300wog <br />Is the Anti Siphon Valve Operational And <br />ProperlySized? <br />es <br />Fire Valve Installed? <br />N/A <br />Fire Valve Manufacturer <br />N/A <br />Fire Valve Model Number <br />N/A <br />Is the Fire Valve Operational? <br />N/A <br />Other <br />Normal Vent Manufacturer <br />OPW <br />Normal Vent Size <br />2" <br />Normal Vent Model <br />OPW/no23 <br />Normal Vent Condition <br />Good <br />Normal Vent Properly Sized? <br />Yes <br />