Laserfiche WebLink
Leak Test: 191(g)(9)/192(k)(10) <br /> Secondary Containment Assessment <br /> The secondary containment calculations provided for on this page are for secondary containment <br /> The waste oil storage tank and ancillary equipment Were <br /> systems that utilize a double walled tank for containment. <br /> pneumatically pressure tested during the inspection.The system <br /> held a pressure of 1.25 psig for 15 minutes with no pressure drop. Please refer to Attachments"A"and"B"for arrangement of tank and <br /> ancillary equipment including secondary containment. <br /> ntegrity testing findings: Based on the above noted integrity test and the Design of tank:66264.193(e)(3) <br /> esults obtained from that test,the tank has sufficient integrity for its intended <br /> use. Initials: Z)-8 Provide a brief description of the construction and design of the lank,including materials of <br /> construction,corrosion protection measures for both inner and outer surfaces of the metal tanks, <br /> and leak detection equipment. <br /> Tank Drawing:191(g)(2)(E)/192(k)(2)(E)) <br /> The waste oil storage tank is of double wall construction,fabricated of <br /> Tank and Fittings:See Attachment"A" welded 8 gauge carbon steel.No corrosion protection is provided for the <br /> inner liner and none is required due to the petroleum based contents. <br /> Ancillary Equipment:See Attachment"B" External corrosion protection is provided by a coating of primer and <br /> enamel paint.A level indication device is installed in the primary <br /> Tank Dimensions: containment section.An audible high level alarm is also installed.When <br /> tested during the inspection,it was in good working order. <br /> Primary Containment:4'-2"wide x 3'-7"deep <br /> A daily documented inspection is performed which will detect any leaks <br /> Secondary Containment:5'-0"wide x T-9"deep within 24 hours per 22CCR66265.1920)(3). <br /> Tank Height: <br /> Overall:5'-1 1/2" <br /> Primary Containment:4'-6" Ancilla Conveyance System Volume <br /> Item Len th CrossSection Area Volume <br /> Copper Tube 1 125"OD 910° 0.785 in 715 in 3.09 allons <br /> Secondary Containment:4'-9 1/2" 1"Graco Husk 1040 Pum 0.79 gallons <br /> Transfer Hose 1.00"ID 60° 0.795 m 47 in 0.20 gallons <br /> Tank Gross Capacity(Volume):500 gallons Total Volume 4.08 gallons <br /> The combined volume of the tank and ancillary equipment: <br /> 500 gallons(primary)+4.1 gallons(ancillary equipment)=504.1 gallons <br /> The secondary containment capacity of 670 gallons will contain 100%of <br /> the tank capacity and ancillary equipment.This meets the requirement <br /> specified in 22CCR66265.1920)(1). <br />