Laserfiche WebLink
HtL;t:1 V crr <br /> SEP 2 S 2016 <br /> 9. TANK ANNULAR TESTING HPALTH <br /> Test Method Developed By: ❑Tank Manufacturer ®Industry Standardro ef�I° '$IOfE?!`1T <br /> [I Other(Spec) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used:VACUUM GAUGE Equipment Resolution:OS" <br /> Tank#DSL 2 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes ®No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: <br /> Tank Material: FG <br /> Tank Manufacturer: UNKNOWN <br /> Product Stored: DSL <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN <br /> starting test: <br /> Test Start Time: 11:30 <br /> Initial Reading(Rd: -10" " <br /> Test End Time: 12:30 <br /> Final Reading(RF): -10" <br /> Test Duration: IHR 1 HR IRR 1 HR <br /> Change in Reading(RF-Rr): 0 <br /> Pass/Fail Threshold or Criteria: 0 0 0 0 <br /> Test Result: ®Pass Fail ❑Pass ❑Fail ❑Pass ❑Fail ❑Pass ❑FaU` <br /> Was sensor removed for testing? .. ®YeEEIZEI NA ❑Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> Was sensor properly replaced and ®ye ❑NA El Yes❑No❑NA ❑Yes❑No❑NA ❑Yes❑No❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing and recommended follow-upjor failed tests) <br /> 10. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {Cal ifomia Code of Regulations,Title 23,Section 2637(a)(6)) <br /> Secondary Containment Test Results 4 of 15 <br />