MONITORING ALTERNATIVE 7 <br /> Implementation of this monitoring alternative will require <br /> Weekly Tank Gauging and Annual Tank Integrity testing. If <br /> this monitoring alternative is chosen implementation should <br /> be carried out as follows: <br /> 1) Perform the initial tank integrity test/tests to confirm <br /> that the tank/tanks do/does not leak at the time of <br /> implementation of the monitoring alternative. Integrity <br /> testing must be done within one year prior to <br /> implementation of the monitoring alternative. Based on <br /> information obtained from facility personnel all/the <br /> tanks/tank at this facility have passed an integrity test <br /> within the last year. <br /> 2) Weekly tank gauging will require that the tank be secured <br /> for a period no less than 36 hours. During this time no <br /> inputs or withdrawals will be allowed from the tank. The <br /> fuel level at the beginning and end of this period will be <br /> measured manually using a calibrated stick (or using <br /> automatic liquid level sensing equipment) with an accuracy <br /> of ±9 gallons. Weekly gauging shall be as specified in <br /> Section 2641, Alternative 7 in the Underground Storage Tank <br /> Regulations. <br /> 3) Tank integrity testing to determine that total product loss <br /> from the tank does not exceed 0. 05 gallons per hour, shall <br /> be performed yearly. Integrity testing shall be carried <br /> out as described in Section 2543 of the Underground Storage <br /> Tank Regulations. <br />