Laserfiche WebLink
0 � 0 <br />Page I of 1 <br />SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Fill Riser Containment sumps r <br />Fill Riser Containment Sumps are Present, but <br />were Not Tested <br />I <br />Test Method Developed By: r Spill Bucket Manufacturerre Industry Standard Professional Engineer <br />(- Other (Specify): <br />Test Method Used By: (' Pressure vacuum to Hydrostatic <br />r Other (Specify): <br />Test Equipment Used: 0 <br />Equipment Resolution: <br />Spill Box # Spill Box <br />Tank T1:SUPREME UNLEADED PREMIUM Tank T2:REGULAR UNLEADED REGULAR. <br />Spili Box = <br />Spill Box <br />Fill - Direct Fill - Direct <br />Bucket Diameter: 12.00 12.00 <br />Bucket Depth: 12.25 12.25 <br />Wait time between <br />applying <br />pressure/vacuurn/water 5 min 5 min <br />min <br />rn i n <br />and starting test <br />Test Start Time: 09:05:00 09:05:00 <br />Initial Reading a,,): 12.00 in. 12.00 in. <br />Test Fncl Time: 10:05:00 10:05:00 <br />Final Reading �,): 12.00 in. 12.00 in. <br />Test Duration: 60 min 60 min <br />Change In Reading m,+,j <br />0.00 in. 0.00 in. <br />Pass/Fail Threshold or <br />+/- 0.00 0.00 <br />Criteria: <br />Test Result.- Pass .. .. .. .. .. .. Pass <br />