Laserfiche WebLink
Page 9 of 9 <br />9. SPILL/OVERFILL CONTAIAMF,NT BOXLCS <br />Facility is Not Equipped With SpiIYOverfill Contaimnent Boxes ❑ _ r <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ _ <br />Test Method Developed By: _ ❑ Spill Bucket Manufacturer ® Indust D, Standard ❑ Professional Engineer <br />[I Other (Spec) <br />Test Method Used: El Pressure F] Vacuum Z Hydrostatic <br />El (Specify <br />Test Equipment Used: See attached testing procedures <br />Equipment Resolution <br />Spill Box # 87 vapor <br />Spill Sax #9I vapor <br />Spill Box # 87 illi Spill Box 91 EU <br />Bucket Diameter &Brand: <br />12" Philtite <br />12" Philtite <br />12" Phiitlte <br />12" — Philtite <br />Bucket Depth: <br />Wait time between applyuig <br />pressure/vacuum/water and <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />30 Minutes <br />starting test: <br />_. <br />Test Start Time: <br />Visual Fail <br />Visual Fail <br />10:07am <br />9:56am <br />Initial Reading (RI): <br />1.1249 <br />1.1585 <br />Test End Time: <br />10:22am <br />10:11am <br />Final Reading (RF): <br />1.1261 <br />1.1596 <br />Test Duration: <br />15 min <br />15 nein <br />15 min <br />15 min <br />Change in Reading (RF -RI): <br />0.00115 <br />0.00106 <br />Pass./Fail Threshold or <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Criteria: <br />- <br />Test ReSul#:. <br />❑ Pass ® Fail : ; <br />❑Pass MFA <br />Z_ Pass ;' ❑Fail <br />Pass ❑Fail <br />_Comments — (include information on repairs made prior to testing and recommended follow-up for faided test) <br />87 & 91 Fill Buckets leak at drain valve (Philtite) — 91 Fill Bucket also has a bad upper O'ring <br />