Laserfiche WebLink
San Joaquin County <br />Environmental Health Department <br />1868 f=ast Hazelton Avenue, Stockton, California 95205-6232 <br />Telephone; (209) 468-3420 Fax: (209) 468-3433 Web, www. s' ov.or /ehd <br />Facility Name. Underground Storage Tank Program lns,pection Report <br />Costco Wholesale #1031 Facility Address: <br />2440 Daniels 5T, Manteca Date: <br />August 18, 2016 <br />UST System Observations <br />322 HSC 25281.6(a) Unburied below grade emergency 9 y generator system failed to meet exemption status <br />323 HSC 25283.5(a) Unburied below grade UST system failed to meet exemption status n V r_' R COS <br />324 CCR 2717.1(g) Tampered with red tag n V E7 R c COS <br />325 CCR 2717-1(0 Deposited petroleum into a red tagged UST J V ER o COS <br />326 HSC 25299(a)(9) Tampered with or disabled leak detection devices or alarms n V R � COS <br />327 CCR 2631.1 UST system not compatible with the substance stored e V R c COS <br />328 HSC 25298 Failed to comply with temporary closure requirements e V ° R c COS <br />329 HSC 25298 Failed to comply with permanent closure req it emen is 0 V n R e COS <br />330 CCR 2636(f (6) Failure to meet all requirements in lieu of a line leak detector for emergency n V ❑ R e COS <br />9 y generator tank system � V ❑ R <br />Non -Pressurized Piping , C05 <br />401 CCR 2636(a)(3) Suctionp�P 9 i in not properly sloped or incorrectly located check valve <br />402 CCR 2643(d) Dail monitoring of suction Pipe re -Jan 1984) not performed " V ° R ❑ COS <br />Daily g P�p (P <br />403 CCR 2643(d) Triennial 0,1 gph line test for conventional suction Piping not Performed ° V e R n COS <br />404 CCR 2643(e) P P 9 P (Pre -January 1984) <br />O Biennial 0,1 gph test for ravit pi g performed u V rj R c COS <br />9 y pi in not (pre -January 1984) <br />" ❑ n <br />Other Violations V R COS <br />2010 See below Unlisted Administration/Documentation violation <br />2030 See below Unlisted OperationslMaintenance violation n V ° R ❑ COS <br />2060 See below Unlisted Design/Construction violation ' V ° R ❑ COS <br />SUMMARY OF VIOLATIONS V ° R D COS <br />Item # (CLASS 1, CLASS 11, or MINOR - Notice to Comply) <br />201 Remarks <br />CCR 2712(b) Failed to maintain alarm logs and/or records of follow up actions. <br />Maintenance and monitoring records for the last three years were not found on site. The missing records include <br />responses to the following alarms: <br />L3 (91 Annular) High Liquid alarm - 7131/16 <br />S11 (87A Vent Vacuum) Communication alarm - 7/22/16 <br />S11 (87A Vent Vacuum) Communication alarm - 7120/16 <br />The designated operator noted "no documentation on site" for these alarms. The 7/31 alarm was on the site alarm <br />log, but no response was noted. The 7/22 and 7/20 alarms were not documented on the site alarm log. <br />These records shall be maintained on site for at least three years. Monitoring records include: <br />off moni(1) date and time of <br />toring or sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visna! <br />observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other <br />monitoring equipment, ground water elevations, or other test results, (6) results of inventory readings and <br />reconciliations. Immediately locate and maintain all maintenance and monitoring records for the last three years on <br />site and submit copies of the missing maintenance records to the EHD. <br />This is a repeat violation, Class If. <br />Page 3 of 6 <br />