Laserfiche WebLink
Page6cif8 % p <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested o <br /> Test Method Developed By: ❑Sump Manufacturer El Industry Standard LI Professional Engineer <br /> ❑Other(Specify) <br /> Test Method Used: ❑'Pressure ❑Vacuum ®Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: Equipment Resolution: <br /> Fill Sump # Fill Sump # Fell Sump # Fill Sump # <br /> SumTSumpDiame!ter: 7Height from <br /> ank Top to <br /> op of <br /> Highest <br /> Height from Tank Top to Lowest <br /> Electrical Penetration: <br /> Condition of sump prior to testing: <br /> Portion of Sump Tested <br /> Sump Material: <br /> Wait time between applying <br /> pressurelvacuumlwater and starting <br /> test: <br /> Test Start Time: <br /> Initial Reading Ri): <br /> Test End Time: <br /> Final Reading(RF): <br /> Test Duration: <br /> Change in Reading Rr-Ri : <br /> Pass/Fail Threshold or Criteria: <br /> Test Result: ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Is there a sensor in the sump? ❑ Yes ❑ No ❑ Yes U No ❑ Yes ❑ No ❑ Yes ❑ No <br /> Does the sensor alarm when either ❑ Yes U No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> product or water is detected? <br /> Was sensor removed for testing? ❑ Yes ❑ No ❑ NA ❑Yes ❑ No DNA ❑ Yes ❑ No ❑ NA ❑Yes ❑ No ❑ NA <br /> Was sensor properly replaced after ❑Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br /> testing? <br /> Comments— include information on repairs made prior to testikq,and recommended follow-up for failed tests <br />