Laserfiche WebLink
' Page S of 8 rnx <br /> 7. UNDER-DISPENSER CONTAINMENT UDC TESTING_ <br /> Test Method Developed By: ❑ Sump Manufacturer 0 Industry Standard ❑ Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ® Hydrostatic <br /> ❑Other(Specify) <br /> Test Equipment Used: Lake Test Equipment Resolution.- <br /> UDC <br /> esolution:UDC# 1 2 UDC # 314 UDC # 516 UDC# 7 8 <br /> UDC Manufacturer: Bravo Box Bravo Box Bravo Box Bravo Box <br /> UDC Material: Steel Steel Steel Steel <br /> UDC Depth: 9" g„ 91, 9" <br /> Height from UDC Bottom to Top of 0" 0" 0" 0" <br /> Highest Piping Penetration: <br /> Height from UDC Bottom to Lowest 0'" 0" 0" 0" <br /> Electrical Penetration: <br /> Condition of UDC prior to testing: Dry Dry Dry Dry <br /> Portion of UDC Tested' 50% 500/0 50% 50% <br /> Does turbine shut down when UDC <br /> sensor detects liquid(both product ❑ Yes ❑ No O NA ❑Yes ❑ No IM NA 0 Yes ❑ No ® NA ❑ Yes ❑ No D NA <br /> and water)?' <br /> Turbine shutdown response time <br /> Is system programmed for fail-safe ❑ Yes ❑ No ® NA ❑ Yes ❑ No 0 NA ❑Yes '❑ No ® NA ❑ Yes ❑ No ® NA <br /> shutdown?` <br /> Was fail-safe verified to be ❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No MINA ❑ Yes Q No MINA <br /> o erationalT <br /> Wait time between applying <br /> pressure/vacuum/water and starting <br /> test <br /> Test Start Time: 02:00 02:00 02:00 02:00 <br /> Initial Reading Ri): 4 3/4" 4 1/2" 4 3/4" 5" <br /> Test End Time: <br /> 03:00 03:00 03:00 03:00 <br /> Final Reading(RF): 4 3/4" 4 1/2" 4 3/4" 5" <br /> Test Duration: 1 hr 1 hr 1 hr 1 hr_ <br /> Change in Reading(RF-Ri): 0 0 0 0 <br /> PasslFail Threshold or Criteria: 0 0 0 0 <br /> Test Result: d Pass ❑ Fail IHI Pass ❑ Fail I] Pass ❑ Fail 0 Pass ❑ Fail <br /> Was sensor removed for testing? ❑ Yes ❑ No MI NA ❑ Yes ❑ No 1XI NA ❑ Yes ❑ No ® NA ❑ Yes ❑ No 0 NA <br /> Was sensor properly replaced after ❑Yes ❑ No [9 NA ❑Yes ❑ No ® NA ❑Yes ❑ No ® NA ❑Yes ❑ No 0 NA <br /> testin ? <br /> Comments— include information on repairs made prior to testing,and recommended follow-up for failed tests <br /> 1 If the entire depth of the UDC is not tested,specify how much was tested. if the answer to an of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWR.CB LG-160) <br />