Laserfiche WebLink
San Joaquin County <br /> Environmental Health Department <br /> 1868 East Hazelton Avenue, Stockton, California 95205-6232 <br /> Telephone: (209)468-3420 Fax:(209)468-3433 Web:www.sggov.org/ehd <br /> Underground Storage Tank Program Inspection Report <br /> Facility Name: Facility Address: Date: <br /> CHEVRON#92033' 508 W Charter Way, Stockton <br /> UST System Observations <br /> 323 CCR 2636(f)(2) Leak detector failed to detect a 3.0 gph leak at 10 psi ❑V u R ❑COS <br /> 324 CCR 2635(b) No spill bucket installed or failed to provide a means to keep it empty ❑V ❑R in COS <br /> 325 CCR 2635(b) Spill container failed to contain a minimum capacity of five gallons ❑V ❑R ❑COS <br /> 326 CCR 2635(b)(2) Overfill prevention system not present,was overridden,or failed to meet overfill requirements ❑V ❑R ❑COS <br /> 327 HSC 25283.5 Unburied below grade UST failed to meet exemption status ❑V ❑R in COS <br /> 328 CCR 2717.1(g) Tampered with red tag ❑V ❑R ❑COS <br /> 329 CCR 2717.1(f) Deposited petroleum into a red tagged UST ❑V ❑R ❑COS <br /> 330 HSC 25299(f)(2) Tampered with or disabled leak detection devices or alarms ❑V ❑R ❑COS <br /> 331 CCR 2631.1 UST system not compatible with the substance stored ❑V ❑R ❑COS <br /> 332 HSC 25298(b) Failed to comply with temporary closure requirements ❑V ❑R ❑COS <br /> 333 HSC 25298(c) Failed to comply with permanent closure requirements ❑V ❑R ❑COS <br /> Non-Pressurized Piping <br /> 401 CCR 2636(a)(3) Suction piping not properly sloped or incorrectly located check valve ❑V ❑R ❑COS <br /> 402 CCR 2643(d) Daily monitoring of suction pipe(pre-Jan 1984)not performed ❑V ❑R ❑COS <br /> 403 CCR 2643(d) Triennial 0.1 gph line test for conventional suction piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> 404 CCR 2643(e) Biennial 0.1 gph test for gravity piping not performed(pre-January 1984) ❑V ❑R ❑COS <br /> Other Violations <br /> 2010 See below Unlisted Administration/Documentation violation ❑V ❑R ❑COS <br /> 2030 See below Unlisted Operations/Maintenance violation n V ❑R ❑COS <br /> 2060 See below Unlisted Design/Construction violation V ❑R ❑COS <br /> SUMMARY OF VIOLATIONS <br /> (CLASS I,CLASS II,or MINOR-Notice to Comply) <br /> Item# Remarks <br /> 205 CCR 2712(i) Operating permit not on site. <br /> A copy of the 2014 UST operating permit was not found on site. A copy of the UST operating permit and all <br /> attachments and conditions shall be retained at the facility. A copy was provided by EHD at the time of inspection. This <br /> is a minor violation. <br /> 207 CCR 2715 Designated operator did not inspect all required items and/or the inspection reports not completed. <br /> The designated operator failed to document all the alarms from the attached alarm history on the designated operator <br /> monthly inspection reports and failed to check that they were responded to appropriately. The missing alarms include: <br /> L6 (87B STP sump) sensor out on 7/29/14 <br /> Q1 (87 PLLD)gross line fail on 11/28/13, 11/29/13, and 1/16/14 <br /> Q2 (91 PLLD)gross line fail on 10/17/14 <br /> During the monthly inspection, the designated operator shall review the alarm history for the previous month, check that <br /> each alarm was documented and responded to appropriately, and attach a copy of the alarm history with documentation <br /> taken in response to any alarms to the monthly report. Ensure that designated operators performing monthly <br /> inspections at this facility are including all of the required information on the reports. This is a repeat violation, Class II. <br /> Repeive{1 by(initial): Inspector: Phone: Date: <br /> Rep <br /> J 1 STACY RIVERA, Senior REHS (209)468-3440 10/14/2014 <br />