Laserfiche WebLink
INDIVIDUAL TANK INFORMATION AND TEST RESULTS <br />i Tanlaxvh W <br />8501 N MOPAC EXPRESSWAY, SUITE 400 WORK ORDER NUMBER: 2234627 <br />TEST DATE: 03/28/05 AUSTIN, TEXAS 78759 (512) 451-6334 <br />CLIENT: RYDER FUEL COMPLIANCE SITE: RYDER 1071A <br />Tank ID: 6k <br />Product: DIESEL <br />Capacity in gallons: 6,086 <br />Diameter in inches: 96.00 <br />Length in inches: 197 <br />Material: DW STEEL <br />TANK INFORMATIO <br />2 Tank manifolded: <br />Vent manifolded: YES <br />Vapor recovery manifolded: NO <br />Overfill protection: YES <br />Overspill protection: YES <br />Installed: ATG <br />CP installed on: / / <br />Bottom to top fill in inches: 166.5 <br />Bottom to grade in inches: <br />Fill pipe length in inches: 70.5 <br />Fill pipe diameter in inches: 4.0 <br />Stage I vapor recovery: NONE <br />Stage II vapor recovery: NONE <br />COMMENTS <br />Note that line "A" refers to the RESERVE DIESEL Main line, line "B" refers to sat 3, line "C" refers <br />to sat 4, NOTE that line "D" refers to sat 6 (this is supplied by the Main Diesel system). <br />PSI at tank bottom: <br />Fluid level in inches: <br />UFT/OFT: <br />Fluid volume in gallons: <br />Tank water level in inches: <br />Test time: <br />Number at thermisters: <br />Specific gravity: <br />Water table depth in inches: <br />Determined by (method): <br />Leak rate in gph: <br />Result: <br />COMMENTS <br />Test time: <br />Ullage volume: <br />Ullage pressure: <br />Results: <br />-.,: ` <br />LEAK DETECTOR TEST_RESuLTS j - S l.Qs> tx>e[nOCI ,- <br />New/passed Failedireplaced New/passed Failed/replaced <br />L.D. #1 L.D. #1 L.D. #2 L.D. #2 <br />Make: VAPORLESS <br />Model: LD2000 <br />S/N: 02081011 <br />NOT <br />Open time in sec: 4.00 <br />TESTED <br />Holding psi: 23 NOT <br />Resiliency cc: 145 TESTED <br />Test leak rate mllm: 189.0 <br />Metering psi: 12 <br />Calib. leak in gph: 3.00 <br />Results: PASS <br />COMMENTS <br />DATA FOR UTS-4T ONLY: <br />Time of test 1: <br />Temperature: NOT <br />Flow rate (cfh): TESTED <br />Time of test 2: <br />Temperature: <br />Flow rate (cfh): <br />Time of test 3: <br />Temperature: <br />Flow rate (cfh): <br />COMMENTS <br />Material: <br />Diameter (in): <br />Length (ft): <br />Test psi: <br />Bleedback cc: <br />Test time (min): <br />Test 1: Start time: <br />Finish psi: <br />Vol change cc: <br />Test 2: Start time: <br />Finish psi: <br />Vol change cc: <br />Test 3: Start time: <br />Finish psi: <br />Vol change cc: <br />Final gph: <br />Result: <br />Pump type: <br />Pump make: <br />COMMENTS <br />DW FIBERG <br />2.0 <br />100.0 <br />NOT <br />TESTED <br />DW FIBERG FIBERGLASS FIBERGLASS <br />2.0 <br />25.0 <br />NOT NOT <br />TESTED TESTED <br />PRESSURE PRESSURE NONE <br />RED JACKET NONE NONE <br />Impact Valves Operational: YES <br />NOT <br />TESTED <br />NONE <br />NONE <br />Printed 04/15/2005 07:52 SBOWERS <br />