Laserfiche WebLink
8. Fill Riser Containment Sump Testing <br /> Test Method Developed By: ❑Tank Manufacturer Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑Pressure <br /> ❑Vacuum ❑JC Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:t0.002 <br /> Fill Sump# 87A Fill Sump# 87B Fill Sump# 91 FIII Sump# <br /> Sump Diameter: 48" 48" 48" <br /> Sump Depth: 27" 27" -- 28" <br /> Height from Tank Top to Top of 12" 11" <br /> Highest Piping Penetration: 14" <br /> Height from Tank Top to <br /> Lowest Electrical Penetration: 19" 23" 14" <br /> Condition of sump prior to <br /> testing: Ok Ok Ok <br /> Portion of Sump Tested: 100% 100%, 100% <br /> Sump Material: Fiberglass Fiberglass Fiberglass <br /> Wait time: 15 min 15 min 15 min <br /> Test StartTime: 11:02 am 11:02 am 11:02 am <br /> Initial Reading: 5.0160 4.4751 5.1295 <br /> Test End Time: 11:17 am 11:17 am 11:17 am <br /> Final Reading: _5.0168 4.4758 5.1309 <br /> Test Duration(hh:mm): 00:15 00:15 00:15 00:00 <br /> Change in Reading: 0.0008 0.0007 0.0014 0.0000 <br /> Pass/Fail Threshold or Criteda: 10.002 10.002 ±0.002 ;1:0.002 <br /> Pass. Fail Pass 0 Fail <br /> Pass Fail 0 Pass 0 Fail <br /> Is there a sensor in the sump? Yes Yes Yes <br /> Does the sensor alarm when <br /> either product or water is N/A WA WA <br /> detected? <br /> Was sensor removed for <br /> testing? ®Yes No NA ®Yes No 0 NA ®Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> Was sensor properly replaced <br /> and verified functional after *Yes 0 No 0 NA *Yes 0 No 0 NA ®Yes 0 No 0 NA 0 Yes 0 No 0 NA <br /> testing? <br /> Comments: <br /> 6 of 7 <br />