Laserfiche WebLink
• <br /> 9. Spill/Overfill Containment Boxes <br /> Test Method Developed By: . ❑Tank Manufacturer Industry Standard ❑Professional Engineer <br /> Test Method Used: ❑Pressure ❑vacuum 0 Hydrostatic <br /> Test Equipment Used: Incon TS STS Leak Detector Equipment Resolution:10.002 <br /> Spill Box# 87A Spill Box# 87B Spill Box# 91 Spill Box# <br /> Bucket Diameter: <br /> Bucket Depth: 14" 14" 14" <br /> Wait time: 15 min 15 min 15 min <br /> Test Start Time: 9:24 am 10:04 am 10:26 am <br /> Initial Reading: 6.0537 6.9761 4.4034 <br /> Test End Time: 9:39 am 10:19 am 10:41 am <br /> Final Reading: 6.0523 6.9768 4.4019 <br /> Test Duration(hh:mm): 00:15 00:15 _ 00:15 00:00 <br /> Change In Reading: -0.0014 0.0007 -0.0015 0.0000 <br /> Pass/Fail Threshold or Criteria: 30.002 ±0.002 ±0.002 ±0.002 <br /> ra <br /> Test Result: * Pass O Fail * Pass O Fail O Pass O Fail Op.. 0 Pari s; <br /> Comments: <br /> 7 of 7 <br />